3. You can by setting Dip switch SW2 on both CC1 and CC2
(picture 2 and 3) reduce the charging current for left or right hand
side if needed. Normally, this is normally not necessary. Available
range is 6-32A (table 1 and picture 4).
It is allowed to set different values on left and right hand side.
4. Install the electrical power supply cable in the CEE inlet, see
picture 3.
(table1)
SW2 MAX Ampere
SW2
ON OFF
3
3=OFF
6A
2
2=OFF
1
1=ON
3
3=OFF
10A
2
2=ON
1
1=OFF
3
3=OFF
13A
2
2=ON
1
1=ON
3
3=ON
16A
2
2=OFF
1
1=OFF
3
3=ON
20A
2
2=OFF
1
1=ON
3
3=ON
25A
2
2=ON
1
1=OFF
3
3=OFF
29A
2
2=OFF
1
1=OFF
3
3=ON
32A
2
2=ON
1
1=ON
(picture 4)
(picture 3)
SW2
CC1
CC2
SW2
(picture 2)
GTC 7,4 kW = 32 A
6
EN
INSTALLATION OF STANDALONE GTC NOVA