- 20 -
Problem
Possible Cause
Solution
Section 7
Troubleshooting Guide
RDS Series — 50-1000 SCFM
Water downstream of the dryer
Bypass valve is open
Drains in front of the dryer malfunctioning
Ambient air is lower than the dewpoint of the
compressed air.
Drain solenoid coil burned out
Open connection from the drain to the
control board
Drain valve is plugged
Airflow through the dryer is too high
Close bypass
Check drain for proper coil operation and
restrictions in valve. See drain cleaning
instructions.
Insulate or reroute air lines in problem areas.
Ohm coil and verify proper operation.
Replace if necessary.
Verify proper connections at the coil and the
control board
See drain cleaning instructions
See previous air flow instructions
Large pressure drop across the dryer
Inlet or outlet valves are closed
Dirty or plugged filters in air system
Frozen heat exchanger
Plugged heat exchanger
Airflow through the dryer is too high
Open valves and verify proper positions.
Check filters, Change if necessary
Adjust airflow to appropriate levels.
Adjust hot gas valve. See HGV
adjustment instructions.
Verify that exchanger is plugged. Clean
as necessary
See previous air flow instructions
Alarm lamp is on and dryer is not
running
Condenser high temperature safety is tripped
Compressor high temperature safety is
tripped
Clear conditions that caused alarm.
Remove and restore power to dryer
to reset.
Clear conditions that caused alarm.
Remove and restore power to dryer
to reset.
Alarm lamp and run lamp off and dryer
will not run
Disconnect switch or breaker is off
Voltage is out of range
Control fuse is blown
Restore power
Verify proper voltage
Verify and correct cause of problem.
Replace fuse.
Summary of Contents for RDS Series
Page 21: ...21 Notes...
Page 23: ...23 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 50 75 SCFM AIR COOLED...
Page 25: ...25 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 100 125 SCFM AIR COOLED...
Page 27: ...27 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 150 200 SCFM AIR COOLED...
Page 29: ...29 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 250 SCFM AIR COOLED...
Page 31: ...31 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 300 SCFM AIR COOLED...
Page 33: ...33 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 400 SCFM AIR COOLED...
Page 35: ...35 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 500 SCFM AIR COOLED...
Page 37: ...37 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 650 SCFM AIR COOLED...
Page 39: ...39 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 800 SCFM AIR COOLED...
Page 41: ...41 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 1000 SCFM AIR COOLED...
Page 43: ...43 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 150 200 SCFM WATER COOLED...
Page 45: ...45 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 250 SCFM WATER COOLED...
Page 47: ...47 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 300 SCFM WATER COOLED...
Page 49: ...49 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 400 SCFM WATER COOLED...
Page 51: ...51 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 500 SCFM WATER COOLED...
Page 53: ...53 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 650 SCFM WATER COOLED...
Page 55: ...55 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 800 SCFM WATER COOLED...
Page 57: ...57 Replacement Part Illustration RDS Series 50 1000 SCFM Section 8 1000 SCFM WATER COOLED...
Page 63: ...63 Wiring Diagrams Air Cooled Water Cooled RDS Series 50 1000 SCFM Section 9 650 SCFM 230 3 60...
Page 69: ...69 NOTES...