6
Electric power connection
610.44434.40.000 · 08.2019
32
/
44
© Gardner Denver Deutschland GmbH
Parameterising the drive control
NOTICE
The G-BH1 | G-BH9 fails due to an overload of the motor!
!
G-BH1 | G-BH9 are not ventilators! Operation with the setting "
Variable
torque
" or "
Square characteristic
" is not permitted.
Always operate G-BH1 | G-BH9 with the setting "
Constant torque
" or "
Line-
ar characteristic
".
A clock frequency of 8 kHz is recommended. The minimum clock frequency is 4
Khz .
Parameterise integrated drive control 2FC4
The integrated drive control
2FC4
is already parameterised on delivery. Brake and
acceleration times must be adapted to the process. Adjust settings according to
the drive control operating instructions [
➙
6].
Parameterise wall-mounted drive control 2FC4
1. Parameterise drive control
2FC4
with motor data (rating plate [
➙
13]), the
drive control parameters [
➙
42] and the drive control operating instructions
[
➙
6].
2. Identify
the
motor.
Parameterise accompanying drive control from third party
set the optimum process parameters within the limits defined in these instructions
using the motor data (rating plate [
➙
13]), the drive control parameters [
➙
42] and
the operating instructions of the drive control manufacturer [
➙
6].
6.7
6.7.1
6.7.2
6.7.3