13-8-623 Page 35
SECTION 6
ACCESSORIES
SPECIAL CONTROL ACCESSORIES
Auto Sentry software is available in the following versions. Installation requires the removal and
replacement of an IC on the main controller circuit board. Replacement should be performed by an
electronics technician. Refer to 304EBC1255 for detailed instructions. When changing between versions
V4.xx and V6.xx, add or remove the jumpers at terminals 5 and 6 as shown on the wiring diagrams.
V6.xx A software is optimized for use with external control systems which determine when
compressors must load and unload. A runs in Automatic mode at all times, does not have the
External device input, Remote input, nor alarm relay. It provides a Local/Master input, Load/Unload input,
and Compressor Available relay.
300EFD566 - V6.xxEE A control software, English only
301EFD566 - V6.xxEF A control software, English – French
302EFD566 - V6.xxES A control software, English – Spanish
V4.xx RS2000 software is optimized for use with other Gardner Denver screw compressors with RS2000
or ES+ controllers. RS2000 does not provide the Local/Master input, Load/Unload input, and
Compressor Available relay output. It does provide an External device input, Remote input, and an alarm
relay output. It provides four operating modes, and allows multiple units to be operated as a plant air
system.
300EBC566 - V4.xxEE RS2000 control software, English only
301EBC566 - V4.xxEF RS2000 control software, English - French
302EBC566 - V4.xxES RS2000 control software, English - Spanish
ACCESSORIES FOR AUTO SENTRY RS2000
The following kits contain all electrical parts and instructions for field installation of accessory inputs for
units with AUTO SENTRY RS2000 controllers, V4.xx only.
Kit number 205EAQ4014 provides a water pressure switch for installation on the water supply line.
Kit number 207EAQ4014 provides a voltage/phase monitor for 200-208 volt units.
Kit number 208EAQ4014 provides a voltage/phase monitor for 230-240 volt units.
Kit number 209EAQ4014 provides a voltage/phase monitor for 460-480 volt units.
Kit number 210EAQ4014 provides a voltage/phase monitor for 575-600 volt units.
Summary of Contents for AUTO SENTRY RS2000
Page 11: ...13 8 623 Page 7 Figure 3 1 FLOW CHART FOR SETUP PROGRAMMING V4 xx 300EBC1255 E Ref Drawing...
Page 21: ...13 8 623 Page 17 300EFC546 A Ref Drawing Page 1 of 2 Figure 3 2 TYPICAL WIRING DIAGRAM V4 xx...
Page 22: ...13 8 623 Page 18 WIRING DIAGRAM 300EFC546 A Ref Drawing Pag 2 of 2...
Page 30: ...13 8 623 Page 26 FIGURE 4 2 TYPICAL WIRING DIAGRAM V6 xx 303EFC546 A Ref Drawing Page 1 of 2...
Page 31: ...13 8 623 Page 27 303EFC546 A Ref Drawing Page 2 of 2...