13-8-623 Page 37
CONTROLS CHECKOUT
Lock the disconnect switch for the starter in the open position. Energize the compressor package control
panel. If the display indicates "SHUTDOWN - MAIN STRT CONTCT", the starter auxiliary contact is
misconnected. Remove all power and correctly wire as indicated above.
If the package has a separate fan motor, enter the adjustments menu and perform a jog to check for
proper fan rotation. If it is incorrect, disconnect power and switch two of the three wires to the fan motor.
Restore power to the control box when done.
Relieve all pressure at the compressor package. With the main motor power still disconnected, press the
[RUN] key. After a brief delay, The control should stop and display "SHUTDOWN - MAIN STARTER".
This properly indicates that the starter did not function because it is turned off by the disconnect switch.
Unlock and close the disconnect switch for the main motor. Enter the adjustments menu to jog the
compressor and check rotation. If it is incorrect, disconnect and lockout all power, reverse two of the
three power phases at the starter. Restore power when done.
Press the [RUN] key. If the controller displays "SHUTDOWN - MAIN STARTER" and stops the unit, the
starter auxiliary contact is misconnected. Remove all power and correctly wire as indicated above.
Press the [STOP/RESET] key to stop the compressor. The control should perform an orderly stop of the
compressor unit and motor.
Summary of Contents for AUTO SENTRY RS2000
Page 11: ...13 8 623 Page 7 Figure 3 1 FLOW CHART FOR SETUP PROGRAMMING V4 xx 300EBC1255 E Ref Drawing...
Page 21: ...13 8 623 Page 17 300EFC546 A Ref Drawing Page 1 of 2 Figure 3 2 TYPICAL WIRING DIAGRAM V4 xx...
Page 22: ...13 8 623 Page 18 WIRING DIAGRAM 300EFC546 A Ref Drawing Pag 2 of 2...
Page 30: ...13 8 623 Page 26 FIGURE 4 2 TYPICAL WIRING DIAGRAM V6 xx 303EFC546 A Ref Drawing Page 1 of 2...
Page 31: ...13 8 623 Page 27 303EFC546 A Ref Drawing Page 2 of 2...