13-8-623 Page 11
Unit Setup Adjustments
1. In the top line, "OIL CHANGE INTERVAL" is displayed. The bottom line will indicate a time interval of
1000 to 12000 hours. After the machine has run for the programmed setting, an advisory will be
displayed, requesting an oil change. Adjust as desired and press [ENTER] to proceed.
2. In the top line, "FILTER CHNG INTERVAL" is displayed. The bottom line will indicate a time interval
of 500 to 1200 hours. After the machine has run for the programmed setting, an advisory will be
displayed, requesting an oil filter change. Adjust as desired and press [ENTER] to proceed.
3. In the top line, "OVER TEMP LIMIT" is displayed. The bottom line will indicate 225 degrees F. This
is the proper setting for compressor operation with conventional coolant. It may be set higher for high
temperature oils, per the manufacturer's instructions. It may be temporarily lowered to verify the
function of the temperature shutdown system.
4. In the top line, "AUTO RESTART" is displayed. The bottom line will indicate either "OFF" or "ON".
The factory setting is "OFF", and the controller will display a power failure shutdown after power has
been restored.
Set this feature to ON when it is necessary to have the compressor automatically restart after a
power interruption. There will be a brief delay, then the control resumes the mode it was in prior to
the interruption. This feature shall only be enabled when the owner determines that it is safe to do
so. It is recommended that compressor access be limited to only trained service personnel when this
feature is used.
5. This step is only encountered if the AUTO RESTART function was set to ON in the previous step. In
the top line, "RESTART DELAY" is displayed. The bottom line will indicate a time between 5 and 30
seconds. It is factory set at 10 seconds. This is the amount of delay introduced before restarting
after power has been restored. Set it as desired to allow time for power to stabilize before starting
compressors.
6. The display now reads "JOG MOTOR?" and indicates the amount of time to energize the starter.
Adjust with the [+] or [-] key to the smallest value needed to bump the motor and check rotation. 0.1
to 0.2 seconds is normally adequate for factory-furnished full-voltage starters; wye-delta or remote
starters may require a little more time. Set back to zero to proceed to the next step.
7. In the top line, "AUX SD MESSAGE" is displayed. The bottom line will display the message which
will appear if power is removed from terminal 6. Select the most appropriate message for user-
furnished shutdown devices, and press [ENTER] to proceed.
8. On the top line,
“Oil Aging”
is displayed. Select between
“Standard”
or
“High Temp”
on the
second line. This will change how fast the oil change timer will increment when using high
temperature oil such as AEON 9000
TH
.
9. This completes the unit setup adjustments. The controller will return to the main adjustments menu.
SEQUENCING COMPRESSORS WITH THE
"AUTO SENTRY
®
RS2000"
General -
The sequencing mode is used to operate multiple compressors in a common plant air system.
The individual units operate similarly to operation in the automatic mode, except that the setpoints are
under control of the sequencing system. This system is actually distributed among the individual
controllers and compressor units, with communications between them to keep the system coordinated.
Sequencing is intended to start, run, unload, blowdown, and stop compressors in response to changes in
demand during the day or week.
Summary of Contents for AUTO SENTRY RS2000
Page 11: ...13 8 623 Page 7 Figure 3 1 FLOW CHART FOR SETUP PROGRAMMING V4 xx 300EBC1255 E Ref Drawing...
Page 21: ...13 8 623 Page 17 300EFC546 A Ref Drawing Page 1 of 2 Figure 3 2 TYPICAL WIRING DIAGRAM V4 xx...
Page 22: ...13 8 623 Page 18 WIRING DIAGRAM 300EFC546 A Ref Drawing Pag 2 of 2...
Page 30: ...13 8 623 Page 26 FIGURE 4 2 TYPICAL WIRING DIAGRAM V6 xx 303EFC546 A Ref Drawing Page 1 of 2...
Page 31: ...13 8 623 Page 27 303EFC546 A Ref Drawing Page 2 of 2...