13-18-603 Page 92
Figure 6-4 – WATER CONTROL VALVE
Adjustments –
The regulator valve shall be adjusted so that it closes when the cooling water entering
and exiting the package are at the same temperature
– a condition that is present after the compressors
have stopped and the heat exchangers have cooled down. Note that the bypass line allows a small
amount of water flow when the valve closes. Adjustment to the regulator valve can be made as follows:
·
To decrease water flow (e.g., increase exiting cooling water temperature) turn the adjusting screw
from left to right, increasing spring tension. (The groove at the lower edge of the adjusting screw is
an index line for use with the index scale 0 to 8 in obtaining a desired setting).
·
To increase water flow (e.g., decrease exiting cooling water temperature) turn the adjusting screw
from right to left, decreasing spring tension. (The groove at the lower edge of the adjusting screw is
an index line for use with the index scale 0 to 8 in obtaining a desired setting).
Care must be used when handling the capillary tube; a kink or break in the tubing or connections will
make the valve inoperative. Never attempt to change capillary length. Excess capillary tube should be
carefully coiled and placed so that damage will not occur with normal maintenance or traffic past the unit.
If a leak develops through the packing, tighten the packing gland nut firmly with a wrench to reseat the
packing around the valve stem, back off the nut until loose and finally retighten the nut finger tight.
Tightening the packing nut too tight may cause erratic operation. An occasional drop of oil on the valve
stem at the packing nut will prolong packing life.
If the valve malfunctions, check for a bend or binding in the capillary tube, paint or corrosion on valve
stem, foreign material in valve, erosion or thermal system (capillary) failure.
WATER FLOW SHUTOFF VALVE (Optional Hardware) -
This device completely shuts off the flow of
cooling water when the compressors are not operating. Its normally closed state prevents the waste of
cooling water even in the case of power failure. It is a common companion to the water flow regulating
valve.
The water flow regulating valve and the water shutoff valve are factory-installed options. If the presence
of foreign material or scale formation in the cooling water is likely, the use of a strainer in the inlet water
line is recommended.
Summary of Contents for AirSmart VS25A
Page 35: ...13 18 603 Page 34 Figure 4 1 ELECTRICAL ENCLOSURE HARDWARE 310CGC810 D Ref Drawing...
Page 39: ...13 18 603 Page 38 Figure 4 2 PIPING AND INSTRUMENTATION ILLUSTRATION 300CGC797 A Ref Drawing...
Page 41: ...13 18 603 Page 40 300CGC546 E Ref Drawing Page 2 of 4...
Page 42: ...13 18 603 Page 41 300CGC546 E Ref Drawing Page 3 of 4...
Page 43: ...13 18 603 Page 42 300CGC546 E Ref Drawing Page 4 of 4...
Page 45: ...13 18 603 Page 44 301CGC546 E Ref Drawing Page 2 of 4...
Page 46: ...13 18 603 Page 45 301CGC546 E Ref Drawing Page 3 of 4...
Page 47: ...13 18 603 Page 46 301CGC546 E Ref Drawing Page 4 of 4...
Page 49: ...13 18 603 Page 48 302CGC546 C Ref Drawing Page 2 of 4...
Page 50: ...13 18 603 Page 49 302CGC546 C Ref Drawing Page 3 of 4...
Page 51: ...13 18 603 Page 50 302CGC546 C Ref Drawing Page 4 of 4...
Page 53: ...13 18 603 Page 52 303CGC546 C Ref Drawing Page 2 of 4...
Page 54: ...13 18 603 Page 53 303CGC546 C Ref Drawing Page 3 of 4...
Page 55: ...13 18 603 Page 54 303CGC546 C Ref Drawing Page 4 of 4...
Page 57: ...13 18 603 Page 56 304CGC546 C Ref Drawing Page 2 of 4...
Page 58: ...13 18 603 Page 57 304CGC546 C Ref Drawing Page 3 of 4...
Page 59: ...13 18 603 Page 58 304CGC546 C Ref Drawing Page 4 of 4...
Page 61: ...13 18 603 Page 60 305CGC546 C Ref Drawing Page 2 of 4...
Page 62: ...13 18 603 Page 61 305CGC546 C Ref Drawing Page 3 of 4...
Page 63: ...13 18 603 Page 62 305CGC546 C Ref Drawing Page 4 of 4...
Page 65: ...13 18 603 Page 64 306CGC546 C Ref Drawing Page 2 of 4...
Page 66: ...13 18 603 Page 65 306CGC546 C Ref Drawing Page 3 of 4...
Page 67: ...13 18 603 Page 66 306CGC546 C Ref Drawing Page 4 of 4...
Page 69: ...13 18 603 Page 68 307CGC546 C Ref Drawing Page 2 of 4...
Page 70: ...13 18 603 Page 69 307CGC546 C Ref Drawing Page 3 of 4...
Page 71: ...13 18 603 Page 70 307CGC546 C Ref Drawing Page 4 of 4...
Page 73: ...13 18 603 Page 72 308CGC546 C Ref Drawing Page 2 of 4...
Page 74: ...13 18 603 Page 73 308CGC546 C Ref Drawing Page 3 of 4...
Page 75: ...13 18 603 Page 74 308CGC546 C Ref Drawing Page 4 of 4...
Page 77: ...13 18 603 Page 76 309CGC546 C Ref Drawing Page 2 of 4...
Page 78: ...13 18 603 Page 77 309CGC546 C Ref Drawing Page 3 of 4...
Page 79: ...13 18 603 Page 78 309CGC546 C Ref Drawing Page 4 of 4...
Page 104: ...13 18 603 Page 103 Figure 9 1 MINIMUM DISCHARGE PRESSURE CHECK VALVE...
Page 117: ......