13-17-615 Page 15
Configuration of AirSmart G2 Controller
Once the required hardware is installed for sequencing operation, the AirSmart G2 Controller can be
configured for sequencing. A distributor level password is required for assigning the pressure input on the
controller to the system pressure transducer. To navigate through the menus, use the navigation soft
keys
to highlight a menu item, then use the enter soft key
to select the menu item. Refer to
the AirSmart G2 Controller Manual, document number 13-17-613, for more information.
1. Press the menu button
soft key while at the home screen to enter the settings menu.
2. If the distributor level password has not been entered, press the unlock button
soft key and
enter a distributor level or higher password using the onscreen number pad.
3. Navigate to and select
Machine Configuration
.
4. Navigate to and select
I/O M Diagnostics
.
5. Navigate to and select
I/O Mapping
.
6. Navigate to and select
Ain Addresses 1
.
7. Under this screen scroll down to
System Pressure
and press enter to bring up the onscreen
number pad.
Figure 2-2
– Analog Input Mapping
8. Using the number pad enter
19
as the
System Pressure
address and press enter. The numbers
should turn GREEN to show they have been accepted. If an invalid value has been entered the
numbers will turn RED.