background image

TR-RC1xx - User Manual

7

General description

Three modes of operation are provided for the light output:

Continuous

– the output is constant, but variable between 0% and 100%

in steps of 0.1%.

Pulse

(strobe) – the output is pulsed once per trigger. The delay from

trigger to pulse, the pulse duration and the brightness can all be set.

Switched

– the trigger input can be used to switch the output current on

and off.

The set-up is non-volatile, so the TR-RC resumes the same operation after
a power cycle.

7.1

Pulse and duty cycle limits

The output is off by default. Upon being triggered, the TR-RC pulses to the
output after a delay. The delay, pulse width, re-trigger delay, and pulse
intensity are all configurable (see

Section 10, Configuration commands

).

In pulse and switched modes, the brightness can be set up to 1000% of its
rating for short periods and low duty cycles. To avoid damage to the
lighting, the TR-RC limits the duty cycle by ignoring triggers that are too
soon after the previous trigger. The maximum pulse width and duty cycles
are shown below:

Output brightness

Maximum
pulse

width

Maximum
duty

cycle

0 to 100%

100ms

100%

101% to 200%

30ms

30%

201% to 300%

10ms

20%

301% to 500%

2ms

10%

501% to 1000%

1ms

5%

So for example, if the brightness is set to 250%, then the TR-RC does not
allow pulses greater than 10ms long. With 10ms pulses, any trigger
occurring within the next 50ms is ignored as the duty cycle would be
greater than 20%.

The TR-RC120 pulsed current cannot exceed 2A, so for a lighting rating of
0.2A, 1000% brightness is possible. For 0.5A lighting rating the maximum
brightness is 400%.

Similarly, the TR-RC122 pulsed current cannot exceed 10A, so for a
lighting rating of 1.0A, 1000% brightness is possible. For 2.5A lighting
rating the maximum brightness is 400%.

12

Summary of Contents for GigE Vision TR-RC Series

Page 1: ...TR RC120 122 LED Lighting Controllers Issue 004 User manual www gardasoft com...

Page 2: ...annot cause any dangerous situation or significant financial loss to occur Deliberate acts of endangerment and vandalism are not covered by this document and must be considered by the installer While...

Page 3: ...R RC 8 5 1 Environmental considerations 8 6 Connecting the TR RC 9 6 1 Power 9 6 2 Lighting output 9 6 3 Trigger input 10 6 4 Ethernet 11 6 5 Connectors general 11 7 General description 12 7 1 Pulse a...

Page 4: ...nternal trigger timer 27 10 2 8 Using the key lock 28 10 2 9 Viewing the trigger status 29 10 2 10 Viewing the output current 29 10 3 Ethernet commands 30 10 3 1 Ethernet communication 30 10 3 2 Comma...

Page 5: ...TR RC has Ethernet connectivity and may be controlled through a web portal and using triniti technology allows the control of your illumination system if it is triniti enabled The TR RC automatically...

Page 6: ...tally touch it and ensure there is a free flow of air around the unit 2 2 Electrical The TR RC produces high energy pulses Take care to connect the outputs correctly and protect the output wiring and...

Page 7: ...specific to each installation While Gardasoft Vision Ltd has taken every care in the preparation of this advice Gardasoft Vision Ltd and Gardasoft LLC accept no liability for damages of any kind exce...

Page 8: ...rper mehr als 65 C erreichen und folglich bei Ber hrung Verbrennungen verursachen Positionieren Sie sie an einem Ort an dem sie nicht aus Versehen von Personal ber hrt werden und an dem die Luft um d...

Page 9: ...tungsausschluss Diese Angaben dienen lediglich der Orientierung Der Monteur muss f r jede Installation eine eigene spezifische Risikobewertung durchf hren Gardasoft Vision hat bei der Zusammenstellung...

Page 10: ...ent d passer 65 C ce qui est suffisant pour occasionner des br lures en cas de contact Assurez vous que le personnel ne peut pas y toucher accidentellement et que l air circule autour de l unit 4 2 le...

Page 11: ...en tre alt r e 4 4 Clause de non responsabilit Ces informations sont seulement titre indicatif Les installateurs doivent tablir leur propre valuation de risques pour chaque installation Gardsoft Visio...

Page 12: ...the DIN rail to allow the display to be read easily If the average output power exceeds 15W the TR RC must be mounted vertically to allow air to pass through it Leave 25mm clear either side of the TR...

Page 13: ...ty Extra Low Voltage SELV output Route low voltage wiring to the TR RC controller separately from mains electricity wiring If this is not possible make sure the low voltage wiring has an insulation ra...

Page 14: ...not be commoned to any other controllers or grounded in any way The lighting output connections are shown below 6 3 Trigger input The trigger input is a Smart Input it accepts a range of trigger sour...

Page 15: ...s at 10MBits per second 6 5 Connectors general The connectors required to mate with the TR RC controller s connectors are as follows Connector Description Suppler Part number Power input W rth 351 ser...

Page 16: ...ss can be set up to 1000 of its rating for short periods and low duty cycles To avoid damage to the lighting the TR RC limits the duty cycle by ignoring triggers that are too soon after the previous t...

Page 17: ...Output is on when trigger is off Output is off when trigger is on Pulsed P Flag 1 Pulse is triggered on rising edge P Flag 0 Pulse is triggered on falling edge Note The P flag inverts the sense of th...

Page 18: ...this set the P flag to 0 see Section 7 2 Triggering PNP signal You can connect a PNP open collector drive to the TR RC s input Use the connections shown opposite The PNP transistor should not pull up...

Page 19: ...mation on this feature see the application note APP966 SafePower Technology available from www gardasoft com Downloads 7 5 Flags You can set flags on the TR RC controller to alter its operation They c...

Page 20: ...he voltage required for the lighting has decreased too much Check for ageing of the light or a failed LED Note When the output current falls below 100mA some fault detection is disabled Press SEL to c...

Page 21: ...ler 8 1 IP address The TR RC needs an Internet Protocol IP address to communicateover Ethernet There are two ways to get an IP address either programmed into the unit or using DHCP For DHCP mode the T...

Page 22: ...roperties iv From the list select Internet Protocol TCP IP press Properties If Obtain an IP address automatically is set then DHCP is probably used However there may be an alternative fixed IP address...

Page 23: ...P address displayed in GardasoftMaint into your web browser which will display the Main page GardasoftMaint software is available from www gardasoft com Downloads 9 1 Main page The main page shown bel...

Page 24: ...the measurements the TR RC makes during operation You can set the mode continuous pulsed or switched the light s brightness and pulse settings You must click the Submit button to effect any changes y...

Page 25: ...al 9 3 General setup page On the general setup page shown below you can set a password for the TR RC and send it commands Refer to Section 10 Configuration commands for the commands you can use to ope...

Page 26: ...n be set from 0 01A to 2 0A for the TR RC120 or 0 1A to 10A for the TR RC122 in steps of 0 01A The voltage rating can be set from 12V to 24V in steps of 1V When a voltage rated light is connected the...

Page 27: ...ut no rating specified To configure the TR RC from the front panel press and hold SEL for 1 second CH1 is displayed You can then use the p and q keys to scroll through the menu pressing the SEL button...

Page 28: ...in Amps or the voltage in volts Press the SEL button The light s rating is set up 10 2 3 Setting up continuous output Press and hold SEL for 1 second and follow the keystrokes below CH1 is displayed...

Page 29: ...p and q buttons to set the Trigger flag F P is enabled F P is disabled Press the SEL button Use the p and q buttons to set the Error Detect flag F E is enabled F E is disabled Press the SEL button Sw...

Page 30: ...ess to more than 100 the pulse width is limited to a safe value as described in Section 7 1 Pulse and duty cycle limits 10 2 6 Setting time periods When the TR RC requires you to enter a numeric value...

Page 31: ...7 Setting the internal trigger timer You can set an internal trigger timer when the TR RC is in pulse mode When set the TR RC triggers with the same delay and pulse width already set up as described...

Page 32: ...lock code use the p and q buttons to scroll to Lc Press the SEL button Use the p and q buttons to set a lock code value from 0 to 255 and press the SEL button The TR RC keypad is locked Note Setting...

Page 33: ...Viewing the output current You can view an approximate measure of the output current from the TR RC front panel The current measurement is updated roughly once per second but this can be slower when t...

Page 34: ...en A carriage return ASCII 13 character must be sent to terminate the command line in case multiple TCP packets become joined 10 3 2 Command structure Commands are sent by the host a PC connected to t...

Page 35: ...separated by a comma Time periods are specified in milliseconds by default but you can add s ms or us to the parameter to specify seconds milliseconds or microseconds Current is specified in amps by d...

Page 36: ...ated set the current rating to 0 Set continuous mode This command sets the output to continuous mode and allows the brightness to be set RS1 s Where s brightness as a percentage 0 to 100 Set pulse mod...

Page 37: ...Set the internal trigger These commands control the internal trigger When set the output is triggered using an internal trigger signal Type in TT0 to disable the internal trigger TT1 to enable the in...

Page 38: ...0 000A Where see overleaf CH Channel number this is always 1 MD Mode 0 continuous 1 pulsed 2 switched S Percentage brightness 50 0 50 the second part is always 0 0 DL Pulse delay PU Pulse width RT Ret...

Page 39: ...3 Event codes Clear any errors Use this command to read the last event or error code when Ethernet messaging has been disabled GR Any error displayed on the TR RC is cleared If this was a lighting err...

Page 40: ...C s settings using Ethernet commands and through its web page The settings of this command are restored after a power cycle 10 4 Command summary Command Example Effect AW AW Save changes CL CL Clear c...

Page 41: ...RC1xx User Manual Command Example Effect KB KB1 23 Disable the keypad buttons on the front panel Set the unlock code to 23 TR TR1 Generate one trigger pulse ST ST Show the unit s configuration details...

Page 42: ...ulsed Pulsed output average power Max 25W Max 30W Trigger input Smart input compatible with 3V 24V TTL NPN and PNP Input Impedance nom 8kohms Pulse timing From 100 s to 100ms in steps of 100 s Delay f...

Page 43: ...t is 2A for the TR RC120 and 10A for the TR RC122 11 2 3 Pulse mode The maximum pulsed output current is 2A for the TR RC120 and 10A for the TR RC122 When operating at high currents even if you set a...

Page 44: ...to 127 An error has occurred See Section 11 4 Error codes 128 A light has been connected and is working 129 A light has been connected but does not have a current or voltage rating 130 FAT An over tem...

Page 45: ...d Err 9 20 Settings could not be saved to EEPROM Err 19 A light has been connected but no rating has been set Err 21 23 A sensing error has occurred see Section 7 6 Fault detection Err 22 FAA The ligh...

Page 46: ...41 45 FAC Fatal error The unit is outputting more current than expected Err 42 SH The output current is too high Err 43 OP The requested output current requires too high a voltage Err 44 FAt Fatal err...

Page 47: ...TR RC1xx User Manual 43...

Page 48: ...yright 2017 Gardasoft Vision Ltd Gardasoft Vision Ltd Trinity Court Buckingway Business Park Cambridge CB24 4UQ UK tel 44 1954 234970 fax 44 1954 231567 Gardasoft LLC Oak Ridge Road Weare New Hampshir...

Reviews: