Q.uick Start Guide
Q.brixx
66
Gantner Instruments Inc.
USA | China | Singapore | India | Austria | Germany | France | Sweden
1550 Hotel Circle N ∙ Suite 180 ∙ San Diego CA ∙ 92108 ∙ T +1 888 ∙ 512 ∙ 5788
[email protected]
www.gantner-instruments.com
DATA LOGGER CONFIGURATION – Q.STATION
This section describes how to configure the Q.station’s data logger. For complete
information, please use this guide along with the Q.station manual (page 59-85).
Rules
The data logger built into the Q.station is very flexible but there are some rules to follow
in order to create a functional system.
•
It is possible to configure up to 4 x separate data buffers. Each data buffer can
have a unique sample rate. The 1
st
data buffer is the master rate; the 2
nd
, 3
rd
, and
4
th
buffers can be configured to have the same sample rate or smaller (can’t be
greater than the 1
st
)
•
•
It is possible to configure up to 4 x separate UARTs on a single Q.station. A
single UART can be configured for 1 x data buffer (i.e. 1 x sample rate).
Modules/channels under a single UART can’t be split into more than 1 x data
buffer.
Incorrect: