Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
38
50 kVA
Ac input
500 kcmils,
600 V,
75 °C copper wire
175 A
Ac input bypass
Load
60 kVA
Ac input
225 A
Ac input bypass
Load
70 kVA
Ac input
250 A
Ac input bypass
Load
80 kVA
Ac input
300 A
Ac input bypass
Load
90 kVA
Ac input
350 A
Ac input bypass
Load
100 kVA
Ac input
350 A
Ac input bypass
Load
* The recommended wire size is based on a 100 kVA system. The required circuit breaker size is based on
the actual maximum power of the system in kVA.
7.4.2
Dc wiring
To connect the battery cabinet to the UPS, use wire size of 300 kcmils, rated for 600 V,
75 °C copper wire.