Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
2
2.
I
MPORTANT
S
AFETY
I
NSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
This manual contains important instructions for the Power+ RM100 3x208 Vac model.
The PowerPlus UPS system is designed for industrial applications and harsh environments.
Nevertheless the PowerPlus system should be handled with appropriate care, according to the
following guidelines.
WARNING! HIGH TOUCH CURRENT!
EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY.
2.1
Do’s
•
Read this manual carefully before starting installation and operation of the UPS.
•
Review the safety precautions described below to avoid injury to users and damage to the
equipment.
•
This UPS is intended for installation in a temperature-controlled, indoor area that is free from
conductive contaminants.
•
All power connections must be completed by a
licensed electrician
who is experienced in wiring
this type of equipment, and who is familiar with the local electrical codes and regulations. Improper
wiring may cause injury or death to personnel, or damage to the equipment.
•
Pay attention to the warning signs, labels, and markings on the unit. A warning sign signals the
presence of a possibly serious, life-threatening condition.
•
Ensure all power is disconnected before performing installation or maintenance.
•
Leave at least 20 cm of clearance space between the ventilation openings of the UPS and other
objects or walls.
•
The UPS must be well grounded to the building’s grounding system with a conductor that has a
current carrying capacity that matches the rating of the UPS.
•
Battery installation, battery maintenance, and battery replacement shall be performed only by
authorized service personnel.
•
Pay attention to all DANGER, CAUTION, and WARNING notices affixed to the inside and outside
of the UPS.
•
Keep the surroundings clean, uncluttered and free from excess moisture.
•
Keep the operating environment within the parameters stated in this document.
•
Allow only qualified technicians to service the UPS. There are no user-serviceable components.
Do not try to repair it yourself!
•
Use the UPS only for its intended purpose.
•
The battery cabinet should preferably be installed next to the UPS, or as close to it as is practically
possible.
•
Fast-acting fuses (semiconductor fuses)
must be used between the battery and the UPS.
For
example, the Bussmann “FWH” fuse.
•
If you remove a UPS module from the PowerPlus while the module is operating, wait five minutes
before reinserting the module. This allows the module’s capacitors time to discharge.