UPS for 208 Vac Grid, Installation Guide, doc. rel. 3.0
18
System Start-Up
20. Remove all power modules, switch ON bypass
and rectifier input circuit breakers and keep
the output breaker OFF.
21. The system controller and static switch will
switch ON.
Note:
the static switch will supply output power
from the bypass.
LCD screen and system output
are on.
Initial Configuration
22. Type the password you receive from the Gama
app, Gamatronic support or at:
http://license.gamatronic.com/
Note the Hardware ID number
Password accepted
23. Enter the Ah value of the battery set.
When using multiple battery sets add the Ah
value of the # of sets.
24. Enter your local time zone.
25. Press the “Finish” button.
The controller restarts with the
new configuration.
26. From the System Menu screen choose
“Profile” and verify that the system is
configured as per your requirements or with
acceptable default values.
Verify time and date are correct.
The system configuration
matches your requirements
Comments on site preparation
–
electrical:
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________