TROUBLE SHOOTING

 

PROBLEM 

CAUSE 

RECTIFICATION 

Outer ring on push button 
not illuminated.

 

No Power

 

Check power is reaching transformer

 

Leads not connected correctly

 

Ensure  all  leads  are  firmly  pushed 
into connectors

 

No water flow

 

No power

 

Check power is reaching transformer

 

Faulty solenoid valve

 

Check electrical connections, replace 
solenoid valve

 

Water or structural damage to 
electrical components

 

Replace damaged electrical 
components

 

Incorrect connections

 

Check all connections

 

Damage to sensor lead or power 
supply lead

 

Check and replace lead & controllers

 

Pressure exceeding 500kPa

 

Reduce pressure to solenoid to 350kPa

 

Water corroded electrical 
connections

 

Replace electronic components

 

Continuous water flow

 

Solenoid valve jammed open

 

Remove obstruction from solenoid 
valve

 

Solenoid installed 
incorrectly

 

Reinstall valve correctly

 

 

 

Summary of Contents for Flowmatic Safe-Cell

Page 1: ...is a 24V AC electronic control system allowing connection of up to 5 button inputs and 5 solenoids Depending on the settings programmed the solenoids will open for a specific time once the appropriat...

Page 2: ...ange of installation types and surfaces it is important that surfaces which fixtures are mounted to are flat and free from defect This is especially important for our Flowmatic Safe Cell range where s...

Page 3: ...er wall mounted or hub mounted Outlets are not supplied and must be ordered separately Typical Installation Cut out details for face plate The stainless steel face plate assembly should be mounted flu...

Page 4: ...he wall cut out Fit the face plate to Galv Inwall box with supplied screws use supplied snake eye key If extension leads are required please contact Galvin Specialised Do not force the faceplate to fi...

Page 5: ...unting feet supplied with the control module to the back of the controller module box Measure the holes between centres as shown in pre installation page of control module dimensions Find a suitable p...

Page 6: ...ads please contact Galvin Specialised Do not cut the leads If the leads are too long it is recommended that any excess is coiled up and clipped to the wall 6 Connect power supply and check for correct...

Page 7: ...electrical connections replace solenoid valve Water or structural damage to electrical components Replace damaged electrical components Incorrect connections Check all connections Damage to sensor le...

Page 8: ...expressly and is the only warranty given by the Galvin Engineering Pty Ltd With respect to the product Galvin Engineering Pty Ltd makes no other warranties express or implied Galvin Engineering Pty Lt...

Reviews: