Version 2, 30 August 2017, Page
4
of
8
INSTALLATION
Avoid common installation errors
:
-
Incorrect supply pipe size installed.
-
Non-compliance to Australian Standards.
-
Water pressure not tested before installation
-
Lines not flushed before installation.
-
No access for service.
-
Valve not commissioned properly.
1. Mount face plate
-
The stainless steel face plate is always
mounted flush to the wall.
-
Mount supplied Galv Inwall box into the wall
1 or 2mm below the finished wall surface.
-
The Galv Inwall box can be fixed to a masonry
wall or wall frame using screws suitable for the
fixing method. (Fasteners to be supplied by
installer).
-
We recommended that all cabling is fed
through 25mm conduit to make servicing and
replacment easier.
-
Apply a thin bead of silicon on the edge of the
wall cut out.
-
Fit the face plate to Galv Inwall box with
supplied screws, use supplied snake eye key.
-
If extension leads are required, please
contact Galvin Specialised.
Do not force the faceplate to fit onto wall or
attempt to dissamble components, as this
could result in damage to sensor push
button.
2.
Connect solenoid
Connect solenoid assemblies to the outlet as
shown and in accordance with AS/NZS 3500.
Ensure that the solenoid is installed in the
correct direction (the arrow on the solenoid body
must align with the direction of water flow).
Line strainers are supplied attached to the
solenoid valves. Removal of these strainers may
void the warranty.
Ensure no thread tape, copper swarf, sand or
other debris enters and fouls the solenoid
valve.
Make sure solenoid valve is orientated such
that the electrical wiring is not twisted and
connectors are easily accessible.
Note: Refer to solenoid operating instructions
manual for installation and service maintenance
.