Galvin Flowmatic Safe-Cell Product Installation Manualline Download Page 3

 

Version 2, 30 August 2017, Page 

3

 of 

8

 

MOUNTING DETAILS  

Face plate cut out position 

Locate push button faceplate at a suitable 

distance from the outlet (we recommend 300mm 

from the centre of the outlet and at a suitable 

height or to project specification). 

 

Note: 

The outlet can be either wall mounted or hub 

mounted (Outlets are not supplied and must  

be ordered separately). 

 

Typical Installation 

 

Cut out details for face plate  

-  The stainless steel face plate assembly should 

be mounted flush to the wall over a 98mm x 

60mm cut-out, ensure wall depth between 

45mm minimum - 70mm maximum from finished 

wall surface to the back of box. 

 

 

 

 

COMPONENT DIMENSIONS

 

 

52448- STAINLESS STEEL FACE PLATE ASSEMBLY 

 

 

52063 - SOLENOID ASSEMBLY 

 

 

 

 

52028 - TRANSFORMER 

 

52504/52504X - FLOWMATIC CONTROLLER 

 

Summary of Contents for Flowmatic Safe-Cell

Page 1: ...is a 24V AC electronic control system allowing connection of up to 5 button inputs and 5 solenoids Depending on the settings programmed the solenoids will open for a specific time once the appropriat...

Page 2: ...ange of installation types and surfaces it is important that surfaces which fixtures are mounted to are flat and free from defect This is especially important for our Flowmatic Safe Cell range where s...

Page 3: ...er wall mounted or hub mounted Outlets are not supplied and must be ordered separately Typical Installation Cut out details for face plate The stainless steel face plate assembly should be mounted flu...

Page 4: ...he wall cut out Fit the face plate to Galv Inwall box with supplied screws use supplied snake eye key If extension leads are required please contact Galvin Specialised Do not force the faceplate to fi...

Page 5: ...unting feet supplied with the control module to the back of the controller module box Measure the holes between centres as shown in pre installation page of control module dimensions Find a suitable p...

Page 6: ...ads please contact Galvin Specialised Do not cut the leads If the leads are too long it is recommended that any excess is coiled up and clipped to the wall 6 Connect power supply and check for correct...

Page 7: ...electrical connections replace solenoid valve Water or structural damage to electrical components Replace damaged electrical components Incorrect connections Check all connections Damage to sensor le...

Page 8: ...expressly and is the only warranty given by the Galvin Engineering Pty Ltd With respect to the product Galvin Engineering Pty Ltd makes no other warranties express or implied Galvin Engineering Pty Lt...