68

FC66000941  -  00

8

FRESH AIR INTAKE LOUVRE

8.2

SM

OUTDOOR AIR INLET MOTORIZED LOUVRE

OPERATION
The louvre is operated by the control panel that contains the position transducer
that regulates the opening of the louvre in proportional mode.
On setting the control (100% for the remote control panels) the position of the
louvre is that of total outdoor air inlet. Vice versa on setting the control (0% for the
remote control panels) the position of the louvre is that of total ambient air recycle.
The serigraphy on the control panel indicates the percentage of the fresh air.
CLEANING OF THE AIR FILTER
When removing the air filter for the periodic cleaning operations, the position of
the baffle should be that of total ambient air recycle (0%).
HOW TO PLACE YOUR ORDER
In order to properly identify the outdoor air inlet louvre, carefully read what is
stated below.
-

The servomotor should always be positioned on the side opposite the
hydraulic couplings of the heat exchanger that operates with cooled water:
choose the louvre with the motor on the right or on the left, accordingly.

-

For fan coil units with the DF supplemental 1-row heat exchanger, always
adopt the remote control panel.

-

If the SM louvre is coupled to ceiling-mounted equipment with the FU version
cabinet, the fan coil units are to be ordered indicating the “with blind panel
description.

-

The motorized louvre kits designed for serving more than one motor to a
unique control (centralized control) are not equipped with the voltage
transformer. For further information refer to the wiring diagrams.

LEGEND:
SMR:

Motorized louvre, motor on the right, with transformer

SML:

Motorized louvre, motor on the left, with transformer

SMRC: Motorized louvre, motor on the right, for centralized control
SMLC:

Motorized louvre, motor on the left, for centralized control

T

his louvre is intended for replacing the air in the room directly from the fan coil

unit.
The amount of outdoor air, filtered and treated thermally, may be regulated
proportionally from 0 to 100% by means of a built-in servomotor.
The SM kit, as shown in figure 1, essentially comprises the following components:
A

Outdoor air inlet louvre made of steel sheet painted in the same color as
the cover cabinet.

B

Servomotor connected directly to the louvre’s baffle, with a protection rating
of IP54 and power supply of ~ 24V.
The louvre may be opened or closed automatically at the signal of the external
auxiliary contacts (not supplied) such as antifreeze thermostats, timers,
etc., with the possibility of connecting multi-servomotors in parallel to an
individual position transducer.

C

230V - 24V voltage transformer, complete with support terminal strip.

D

Self-threading screws 4.2 x 13 for fixing the fan coil unit to the basic unit.

The control panels (accessories CSB and CSD), which activate the servocontrol,
are envisaged both for being installed on-board the fan coil unit and for the remote
installation (flush wall-mounting). They open or close the louvre from 0 to 100%.

One of the following control panels must be coupled to the louvre:

To prevent the water from freezing inside the heat exchanger during the winter,
close the outdoor air inlet when the system is not operational or use an antifreeze
solution checking its freezing point.

The kit may be installed on the whole range of the éstro series fan coil units.
INSTALLATION
1. 
Check that the desired installation complies with one of the configurations in

figure 2.
A

Flush-mounted fan coil unit with 90° air inlet louvre;

B

Flush-mounted fan coil unit with in-line air inlet louvre;

C

Ceiling-mounted fan coil unit with 90° air inlet louvre;

D

Ceiling-mounted fan coil unit with in-line air inlet louvre.The outdoor air
inlet louvre is always supplied with the sleeve in the back air inlet position.

2. Remove the sleeve as shown in figure 3.
3. Make an opening in the wall complying with the sizes shown in figure 4.

Note: As a rule the outdoor air inlet louvre is coupled with the outdoor air inlet
grid (GE+C).
To limit flow resistance of the sucked outdoor air, it is advisable to create the
opening as shown in figure 5.

4. Insert the sleeve into the opening and fix it as shown in figure 6 based on the

type of chosen installation.
A

Flush-mounted fan coil unit with 90° air inlet louvre;

B

Flush-mounted fan coil unit with in-line air inlet louvre;

C

Ceiling-mounted fan coil unit with 90° air inlet louvre;

D

Ceiling-mounted fan coil unit with in-line air inlet louvre.

5. Reassemble the sleeve on the louvre, remove the cover cabinet from the fan

coil unit, connect the basic unit to the louvre (figure 7) and fix the basic unit to
the wall using 4 anchor screws.

6. Install the control panel (accessory CSB or CSD, figure 8b), on-board or

remotely or flush-mounted as shown in figure 8a.

7. Make the electrical connections complying with the diagrams of figure 9a (SMR

SML), 9b (SMRC - SMRL), depending on the type of SM you have chosen.
Make the electrical connections, with power OFF, conforming to the prevailing
safety regulations.

Each fan-coil requires a switch (IL) on the feeder line with a distance of at least

3 mm between the opening contacts, and a suitable safety fuse (F).
The installer is in charge of carrying out the hatched connections.
The transformer is not supplied as a standard fitting for louvres setup for
the centralized control.

In these cases, provide a 24V-power supply line by sizing the transformer
according to the number of expected louvres. Consumption of every single
servomotor: 5 VA.
The SM louvres may be connected in parallel to a unique control up to a maximum
of 10.

8. If installed on fan coil units fitted with a cabinet (FLFA and FU), a pair of covering

bases must be coupled to the louvre, as outlined in the table below:

% of glycol in weight

0

10

20

30

40

Freezing point  (°C)

0

-4

-10

-16

-24

- Position transducer (control), built-in or remote

- Protection fuse

- Line circuit breaker

-  Louvre servomotor

- Terminal strip

- Supplied transformer

- Transformer for centralized 24V line

-  Auxiliary contacts (antifreeze thermostat, etc.):

A open + open = 0%,
A B open = 0 to 100%,
A B closed = 100%

- Fan coil unit power supply line

- Connection to the position transducer, cable cross-section 1.5 mm

2

- Power supply of the following motors (10 at the most)

C

F

IL

LM24SR

M

T

TI

A, B

1

2

3

Panels

Panels description

code

Control on-board the machine for the proportional opening and closing of

the SM motorized louvre

Flush wall-mounting control for the proportional opening and closing of

the SM motorized louvre

EYCSB

EYCSD

Covering base Covering base description

Version

code

EYZA1

ZA1 pair of covering bases F1-9 A

EYZA10

ZA10 pair of covering bases models  F10-12 A

EYZL1

ZL1 pair of covering bases F1-9

EYZL10

ZL10 pair of covering bases models F10-12 L

FL
FU

FA

Models

F1-F4

F5-F6

F7-F9

F10-F11

F12

SMR

EYSM1R

EYSM5R

EYSM7R

EYSM10R

EYSM12R

SML

EYSM1L

EYSM5L

EYSM7L

EYSM10L

EYSM12L

SMRC

EYSM1RC

EYSM5RC

EYSM7RC

EYSM10RC

EYSM12RC

SMLC

EYSM1LC

EYSM5LC

EYSM7LC

EYSM10LC

EYSM12LC

The following abbreviations are used in the diagrams:

SM

SM

SM

SM

SM

Summary of Contents for ESTRO FA

Page 1: ... SCHEDE PRODOTTO TO TO TO TO VENTILCONVET VENTILCONVET VENTILCONVET VENTILCONVET VENTILCONVETTORI TORI TORI TORI TORI ESTRO ESTRO ESTRO ESTRO ESTRO PRODUCT FILES PRODUCT FILES PRODUCT FILES PRODUCT FILES PRODUCT FILES F F F F FAN COILS AN COILS AN COILS AN COILS AN COILS ESTRO ESTRO ESTRO ESTRO ESTRO ...

Page 2: ... manuale 64 8 2 SM Serranda motorizzata di presa aria esterna 67 INDEX 1 Available accessoires 3 4 2 Control panels and thermostats 5 2 1 CB On board speed selector 5 2 2 TB Built in electromechanical control panel 6 2 3 TIB Built in electromechanical control panel 9 2 4 TC Fan stop thermostat 13 2 5 KPPowerinterface 15 2 6 CD Remote speed selection switch 22 2 7 CDE Wall mounted speed selector 24...

Page 3: ...ZA Coppia di zoccoli di sostengo e copertura FA ZAG Coppia di zoccoli di sostengo e copertura con griglia anteriore FA ZL Coppia di zoccoli di sostengo e copertura FL ZLG Coppia di zoccoli di sostengo e copertura con griglia anteriore FL D Distanziali di sostegno FC PVL Pannello posteriore verniciato per ventilconvettori ad installazione verticale con mobile FL FU PVA Pannello posteriore verniciat...

Page 4: ...TAND COVERING PANELS Accessory Description estro estro estro estro estro models ZA Pair of covering feet FA ZAG Pair of covering feet with front grilles FA ZL Pair of covering feet FL ZLG Pair of covering feet with front grilles FL D Supporting brackets FC PVL Rear painted panel for vertical mounting fan coils with cabinet FL FU PVA Rear painted panel for vertical mounting fan coils with cabinet F...

Page 5: ...ed IL Line switch not supplied M Fan motor RD Red minimum speed WH White common wire CB Control board TC Fan stop thermostat accessory Thiscontrolpanel tobeinstalledon boardthemachine isfitted with a 4 position rotary speed selection switch three speeds stop Installable on the estro versions F L F A F U F B this control boardchangestheoperatingspeedofthefancoilunitandstarts and stops it as well Th...

Page 6: ...an coil unit and for automatically setting the room temperature by operatingthemotor ventilatoroftheunitduringtheheatingphase only or in both modes in centralized systems Thiscontrolpanel whichmaybeinstalledinéstromodelsFL FA FU and FB comprises a 4 position rotary speed selector switch threespeeds stop andanelectromechanicalthermostatfitted with a fluid expansion probe setting range 6 30 C The co...

Page 7: ...0Hz RD BU BK WH S RL 4 1 2 3 1 2 3 TC C T TB CN WH BK BU RD RD L IL F N 230V 1 50Hz 2 3 1 2 3 1 9 8 7 6 5 4 M 1 9 8 7 6 5 4 M 1 RD RD TB TB TC TC SF T T 3 2 1 4 RL S C C 3 2 1 4 RL S CN CN RD BU BK WH RD BU BK WH RD BU BK WH WH BK BU RD 1 2 TB TB TB TB TB ...

Page 8: ...D BU BK WH S RL 4 1 2 3 1 2 3 C T TB VK H CN WH BU RD BK RD 3 L IL F N 230V 1 50Hz 9 8 6 5 4 M 1 9 8 7 6 5 4 M 1 2 3 1 2 3 1 VK C H RD RD CN CN SF TB TB VK C H T T 3 2 1 4 C 3 2 1 4 C S RL S RL WH BK BU RD WH BK BU RD RD BU BK WH RD BU BK WH 7 4 TB TB TB TB TB ...

Page 9: ...hefan coil unit and for automatically setting the room temperature by operating the motor ventilator of the unit both during the cooling and heating phases Thiscontrolpanel whichmaybeinstalledinéstromodelsFL FA FU and FB comprises a 4 position rotary speed selector switch threespeeds stop anelectromechanicalthermostatfittedwith a fluid expansion probe setting range 6 30 C and a cooling heating ope...

Page 10: ...L N F IL 230V 1 50Hz RD BU BK WH S RL 4 1 2 3 1 3 2 a 2 1 TC C T SF TIB CN WH BK RD BU RD RD BU 9 8 7 6 5 4 M 1 GNYE L N F IL 230V 1 50Hz RD BU BK WH S RL 4 1 2 3 1 3 2 a 2 1 C T SF TIB VK C H CN WH BK BU RD RD RD BU 2 1 TIB TIB TIB TIB TIB ...

Page 11: ...x temperature setting 30 C TIB A SPEEDSELECTOR SWITCH 0 Stop Maximum speed Average speed Minimum speed C THERMOSTAT Counterclockwise Minimum temperature setting 6 C Clockwise Maximum temperature setting 30 C B OPERATING SELECTOR Cooling Heating TIB C TERMOSTATO Senso antiorario Minima temperatura di regolazione 6 C Senso orario Massima temperatura di regolazione 30 C B SELETTOREDI FUNZIONAMENTO Ra...

Page 12: ...12 FC66000941 00 2 1 2 1 A B C 4 3 2 1 CB TB TIB CB TB TIB CB TB TIB CB TB TIB CB TB TIB ...

Page 13: ...ntype is used in the éstro range fan coil units centrifugal in the FC NTrange tangential andinthehot airheatingunitsoftheUTN range Its task is to prevent the motor ventilating unit from workingwhen duringtheheatingstage thewatertemperature insidetheheatexchangerislowerthanthesetvalue 42 C and also to prevent cold air circulation which is quite bothersome The fan stop thermostat is setup so as to b...

Page 14: ...B 90 90 1 5 6 7 9 8 7 6 5 4 M 1 GNYE L N F IL WH BK BU RD S RL 4 1 2 3 TC 230V 1 50 C CB CN WH BK BU RD N L S RL 4 1 2 3 4 5 6 7 8 9 WH BK GY BU RD 1 230 1 50 IL F CD CN GNYE M TC 4 3 9 8 7 6 5 4 M 1 GNYE L N F IL WH BK BU RD S RL 4 1 2 3 TC 230V 1 50 C CB CN WH BK BU RD TC TC TC TC TC ...

Page 15: ...ice EYKP GY Grigio velocità media UTN IL Interruttore di linea non fornito M Motore ventilatore RD Rosso velocità minima WH Bianco comune BK Nero velocità massima BU Blu velocità media C commutatore di velocità CN Connettore a faston F Fusibile di protezione non fornito GY Gray average speed UTN IL Line switch not supplied M Fan motor RD Red minimum speed WH White common BK Black maximum speed BU ...

Page 16: ... 5 4 6 5 N 4 3 2 1 ACC KP RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH TC TD SF C S T N 5 6 1 3 4 2 9 10 TDC 13 L 14 N 15 L 16 N 2 3 4 5 C 1 2 3 34 31 32 33 30 27 28 29 26 23 24 25 22 19 20 21 1 2 3 4 230V 1 50Hz L N IL F M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 ACC KP RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH T C S TC SF KP KP KP...

Page 17: ... VK C H VK C H VK C H RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH KP C SF T S M 1 9 8 7 6 5 4 VK H VK C M 1 9 8 7 6 5 4 VK H VK C M 1 9 8 7 6 5 4 VK H VK C M 1 9 8 7 6 5 4 VK H VK C ACC TD4T 13 L 14 N 15 L 16 N 2 3 4 5 C 1 2 3 34 31 32 33 30 27 28 29 26 23 24 25 22 19 20 21 1 2 3 4 230V 1 50Hz L N IL F RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH CN CN CN CN KP C S T...

Page 18: ...5 4 3 2 1 RF CDE TA RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH T C S KP 3 2 1 N N 5 13 L 14 N 15 L 16 N 2 3 4 5 C 1 2 3 34 31 32 33 30 27 28 29 26 23 24 25 22 19 20 21 1 2 3 4 230V 1 50Hz L N IL F M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 6 5 4 3 2 1 CDE 2 1 N N TA2 RF C S SF T RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH KP 6 KP KP...

Page 19: ... 3 2 1 N N TA RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH RD BU GY BK WH T KP CD S RL 4 1 2 3 C RF L N 13 L 14 N 15 L 16 N 2 3 4 5 C 1 2 3 34 31 32 33 30 27 28 29 26 23 24 25 22 19 20 21 1 2 3 4 230V 1 50Hz IL F M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 M 1 CN 9 8 7 6 5 4 2 1 N N TA2 SF T RD BU GY BK WH RD BU GY BK WH BU GY BK WH RD BU GY WH KP RL 3 2 1 4 S C CD RF BK RD 8 KP KP KP...

Page 20: ...ROPROD L IL F 230V 1 50Hz N EXT RD BU GY BK WH 32 33 31 34 RD BU GY BK WH 27 28 29 30 RD BU GY BK WH 23 24 25 26 RD BU GY BK WH 19 20 22 21 SA 13 L 14 N 15 L 16 N 2 3 4 5 C 1 2 3 34 31 32 33 30 27 28 29 26 23 24 25 22 19 20 21 1 2 3 4 KP N 230V 1 50Hz IL F L V3 V2 V1 L N N MICROD M 1 9 8 7 6 5 4 CN M 1 9 8 7 6 5 4 CN M 1 9 8 7 6 5 4 CN M 1 9 8 7 6 5 4 CN PE SA SW BK BU GY RD WH RD BU GY BK WH RD B...

Page 21: ...21 FC66000941 00 11 KP KP KP KP KP ...

Page 22: ...erruttore di linea non fornito M Motore ventilatore RD Rosso velocità minima WH Bianco comune BK Nero velocità massima BU Blu velocità media C commutatore di velocità CN Connettore a faston F Fusibile di protezione non fornito 0 Arresto Velocità massima Velocità media Velocità minima Remote control panel comprising a rotary 4 position selector switch 3 speeds stop This panel which may be coupled t...

Page 23: ...GNYE L N F IL RD BU GY BK WH S RL 4 1 2 3 230V 1 50Hz CN C CD 230 1 50 9 8 7 6 5 4 M 1 GNYE L N F IL S RL C 2 3 1 4 CD 3 2 1 N N RF TA CN BU GY BK WH RD T 230 1 50 9 8 7 6 5 4 M 1 GNYE L N F IL 2 1 N N RF c S RL 4 1 2 3 CN CD TA2 RD BU GY BK WH T SF CD CD CD CD CD ...

Page 24: ...eair handling units of the UTNseries isfittedwithaspeedselectorandastart stopselector INSTALLATION Cutpowertothefancoilunitortothe UTNairhandlingunit Remove the front panel by turning the screw as shown in figure1 Fix the base to the wall using the slots as shown in figure 2 Make the electrical connections as shown in the diagrams of the following figures CDE figure3 1 CDE TA figure3 2 CDE TA2 fig...

Page 25: ...1 00 2 1 3 2 9 8 7 6 5 4 230V 1 50Hz M 1 GNYE L N F IL 6 5 4 3 2 1 S CN WH BK BU GY RD CDE c RD BU GY BK WH 230V 1 50Hz 9 8 7 6 5 4 M 1 GNYE L N F IL 3 2 1 N N RF 6 5 4 3 2 1 C S T CDE TA CN 3 1 CDE CDE CDE CDE CDE ...

Page 26: ...26 FC66000941 00 74 74 24 4 3 3 230V 1 50Hz 9 8 7 6 5 4 M 1 GNYE L N F IL 2 1 N N 6 5 4 3 2 1 RF TA2 CDE S T SF CN BK RD WH C BU GY CDE CDE CDE CDE CDE ...

Page 27: ...tilatingunit ON OFF Usuallysuppliedforequipment thatcannotbefittedwiththeon boardadjustment éstro F C F U UTN it comprises the following components fig 1 on off start key part A switch for selecting the ventilating speed part B summer winter deviator for inverting the operating mode part C bimetallic electro mechanical thermostat regulating range 5 to 30 C part D The panel is supplied with a base ...

Page 28: ...28 FC66000941 00 RD BU GY BK WH 6 5 N 4 3 2 1 ACC S 9 8 7 6 5 4 230 1 50 M 1 GNYE L N F SF T IL C TC TD CN 2 1 74 5 24 75 127 25 74 5 18 75 70 75 5 B A C D TD TDC TD TDC TD TDC TD TDC TD TDC ...

Page 29: ... 00 3 L IL F N N 5 6 1 3 4 2 9 10 N 5 6 1 3 4 2 9 10 S S C C 9 8 7 6 5 4 CN M 1 WH BK BU GY RD 9 8 7 6 5 4 CN M 1 WH BK BU GY RD 230V 1 50Hz TC TC SF ACC T ACC T TDC TDC GNYE GNYE TD TDC TD TDC TD TDC TD TDC TD TDC ...

Page 30: ...e is adjusted by means of ON OFF water regulating valves that should be powered at 230V single phase The TD4T panel comprises the following components fig 1 on off start key part A switch for selecting the ventilating speed part B summer winter deviator for inverting the operating mode part C bimetallic electromechanical thermostat regulating range 5 to 30 C part D The panel is supplied with a bas...

Page 31: ...31 FC66000941 00 1 2 RD BU GY BK WH N 4 6 8 3 2 1 7 ACC SF 9 8 7 6 5 4 M 1 GNYE L N F IL 230V 1 50Hz VK CN T C S TD4T 74 5 24 75 127 25 74 5 18 75 70 75 5 B C A D TD4T TD4T TD4T TD4T TD4T ...

Page 32: ...32 FC66000941 00 3 RD BU GY BK WH N 4 6 8 3 2 1 7 ACC 9 8 7 6 5 4 M 1 GNYE L N F IL 230 1 50 VK C VK H CN C T S SF TD4T TD4T TD4T TD4T TD4T TD4T ...

Page 33: ...da figura 1 Fissare il termostato alla parete utilizzando le asole come da figura 2 reinserire la copertura INSTALLATION TD TDC TD4T Cut power to the fan coil unit Choose an area for installing the control panel that is easy to access for setting the functions and suitable for reading the room temperature 1 5 m abovethefloor Thereforeavoid a positions that are directly exposed to sun rays b positi...

Page 34: ...r in summer winter mode with remote selection switch not supplied setting range 5 to 30 C TA2 codeEYTA2 electromechanicalbimetallictypewithsummer winter selection switch setting range 5 to 30 C INSTALLATION Cut power to the unit Choose a position that is easy to access and suitable for measuring the room temperature avoid positions exposed to direct sunlight or subject to directhotorcoldairdraught...

Page 35: ...35 FC66000941 00 74 74 24 5 1 0 15 C 25 3 0 2 1 T T T T TA T A T A T A T A TA2 A2 A2 A2 A2 ...

Page 36: ...5 4 M 1 GNYE L N F IL S RL C 2 3 1 4 WH BK BU RD 3 2 1 N N RF CN CB TA RD BU BK WH T 3 4 230V 1 50Hz 9 8 7 6 5 4 M 1 GNYE L N F IL 2 1 N N RF C S RL 4 1 2 3 WH BK BU RD CN CB TA2 SF T RD BU BK WH T T T T TA T A T A T A T A TA2 A2 A2 A2 A2 ...

Page 37: ...IL F N 9 8 7 6 5 4 M 1 SF CN RD BU GY BK WH 9 8 7 6 5 4 M 1 CN RD BU GY BK WH 1 2 3 4 5 6 S C CDE 3 2 1 4 RL S C CD N N 1 2 3 RF TA TC TC N N 1 2 3 RF TA IL IL F F T T 230 1 50 5 T T T T TA T A T A T A T A TA2 A2 A2 A2 A2 ...

Page 38: ...table in figure 3 according to the fan coil model Batteria addizionale di riscaldamento realizzata in tubi di rame ed alette in alluminio trova impiego negli impianti con distribuzione a 4 tubi e viene collegata al circuito di riscaldamento La batteria é provvista di valvole per lo sfiato dell aria poste sui bocchettoni di collegamento all impianto Le prestazioni dello scambiatore inserito nei ven...

Page 39: ...1a 3 3 3 3 3 2 2 2 2 2 C D B A n A B C D F1 F4 EYDF1 187 99 334 486 1 2 F5 F6 EYDF5 187 99 334 486 1 2 F7 F9 EYDF7 187 99 334 486 1 2 F10 F11 EYDF10 195 120 348 479 1 2 F12 EYDF12 195 120 348 479 1 2 1 1 1 1 1 DF DF DF DF DF ...

Page 40: ...ntareglizoccolidicoperturaalmobilefissandolialle fiancateinplastica 2viti edalpannellofrontale 1vite delmobilestesso figura4 COMEORDINARE Zoccoli di copertura ZA1 da F1A a F9A codice EYZA1 Zoccoli di copertura ZA10 da F10A a F12A codice EYZA10 The covering feet ZA only for the assembly on the F A estro series are supplied as pairs and comprise a spacer for fixing to the bearing unit and an externa...

Page 41: ...41 FC66000941 00 2 1 4 4 4 4 4 A A A A A B B B B B C C C C C 3 3 3 3 3 2 2 2 2 2 1 1 1 1 1 ZA ZA ZA ZA ZA ...

Page 42: ...nagrigliata vederetabella 4 1 ZAG BASE WITHAIR GRILL ASSEMBLYINSTRUCTIONSFORTHEFRONTGRILL Upon having completed the installation of the covering bases or air intake locks fitthefrontgrillbysecuringitwiththe4MAscrewsprovided asshown in the figure These instructions are to be applied to the accessories of the ZAG base with air grill and the manual air lock of the external air intake grill see the ta...

Page 43: ...ORDER Please indicate covering feet ZL1 from F1L to F9L code EYZL1 covering feet ZL10 from F10L to F12L code EYZL Gli zoccoli di copertura ZL previsti per il montaggio unica mente sulla serie éstro FL vengono forniti in coppia e sono composti dai sostegni per il fissaggio all unità base e dalle coperture esterne per il fissaggio al mobile Si utilizzano per mascherare le tubazioni idrauliche proven...

Page 44: ...44 FC66000941 00 2 2 2 2 2 4 4 4 4 4 6 6 6 6 6 5 5 5 5 5 3 3 3 3 3 1 1 1 1 1 C A B ZL ZL ZL ZL ZL ...

Page 45: ...allazionesufancoilgiàdotatidizoccoli di copertura o serranda di presa aria installare la griglia frontale fissandola con le viti 4 MA a corredo come indicato in figura Queste istruzioni si applicano per l accessorio zoccolo grigliato ZLG COMEORDINARE ASSEMBLYINSTRUCTIONSFORTHEFRONTGRID Upon having completed the installation on fan coils pre fitted with coveringbasesorairintakelock fitthefrontgridb...

Page 46: ... fiancate dell unità base figura2 COMEORDINARE Staffe di sostegno D1 per modelli da F1C a F9C codice EYD1 Staffe di sostegno D10 per modelli da F10C a F12C codice EYD10 ThesupportbracketsDaresuppliedinpairsandarematchedtothe éstro F Cseries flush mounted fan coil units when they cannot be wall mounted The height of the support brackets is 100 mm The kit comprises figure 1 One pair of galvanized st...

Page 47: ...ure 1 e 2 COMEORDINARE Versioni F 1 4 F 5 6 F 7 9 F 10 11 F 12 FL FU EYPVL1 EYPVL5 EYPVL7 EYPVL10 EYPVL12 FA EYPVA1 EYPVA5 EYPVA7 EYPVA10 EYPVA12 FB EYPVB1 EYPVB5 EYPVB7 Versions F 1 4 F 5 6 F 7 9 F 10 11 F 12 F L FU EYPVL1 EYPVL5 EYPVL7 EYPVL10 EYPVL12 FA EYPVA1 EYPVA5 EYPVA7 EYPVA10 EYPVA12 FB EYPVB1 EYPVB5 EYPVB7 This accessory is supplied for the installation of fan coil units the rear side of...

Page 48: ...48 FC66000941 00 1 F L F A 2 F B F U B A C PVL PV PVL PV PVL PV PVL PV PVL PVA PVB A PVB A PVB A PVB A PVB ...

Page 49: ...Munirsi di guanti protettivi 2 Montare la chiusura posteriore vedere figura 1 COMEORDINARE VERSIONI F 1 4 F 5 6 F 7 9 F 10 11 F 12 FU EYPH1 EYPH5 EYPH7 EYPH10 EYPH12 The rear painted panel PH is supplied exclusively for the éstro FU range of ceiling mounted fan coil units with the rear side in view This panel is used for hiding the hydraulic fittings and comprises1backclosingpanelmadeofpre painted...

Page 50: ... Installare la bacinella ausiliaria di raccolta condensa principale fissandola con le viti 2 9 X 9 5 a corredo figura 1 COMEORDINARE Bacinella ausiliaria di raccolta condensa BH codice EYBH The BH auxiliary tray for collecting condensate is used in the éstro series fan coil units and is mounted horizontally for collectinganycondensatethatisformedonthepipes adjacent to the hydraulic connections and...

Page 51: ...ella venga utilizzata su ventilconvettori con mobile di copertura FL FA FU ed FB e con tubazioni dell acqua provenienti da pavimento verificare lo spazio utile di passaggio indicato in figura 4 COME ORDINARE BV codice EYBV The task of this accessory is collect any condensate that may form on the valve and the holder It can be fitted on the following wall mounted models FL FA FU FC FB INSTALLATION ...

Page 52: ...0 2 216 122 47 47 F 16 F 12 52 5 20 60 80 20 20 1 3 202 A 54 80 50 B 56 206 50 80 34 A B A B F 1 9 L U 4 112 F 10 12 L U 29 137 F 1 9 B 29 137 A B F 1 9 A 7 115 F 10 12 A 31 139 4 F L F U F B 4 F A B B B B BV V V V V ...

Page 53: ...foro e fissandolo ai fermacavi ricavati sulla coclea del ventilatore raggiungere il lato attacchi elettrici opposto al lato attachi idraulici vedere figura 4 6 Collegare elettricamente al pannello di comando 7 Rimontare il mobile di copertura The 3 way valve VK kit ON OFF motorization connected to the control panels of the éstro fan coil units permits to set the room temperature by cutting off the...

Page 54: ...54 FC66000941 00 A D C B 1 1 1 1 1 VK VK VK VK VK ...

Page 55: ...55 FC66000941 00 2 2 2 2 2 A C B D VK VK VK VK VK ...

Page 56: ...56 FC66000941 00 3 3 3 3 3 4 4 4 4 4 VK VK VK VK VK ...

Page 57: ...ua calda ad esempio ventilconvettori asserviti da una pompa di calore le resistenza elettriche addizionali RE sono utilizzabili sui ventilconvettori serie éstro nei modelli da 1 a 11 Questo accessorio non è utilizzabile nella versione a parete éstro FA Il kit descritto in figura 1 è composto principalmente da A Resistenza elettrica corazzata in alluminio alettato prevista per alimentazione elettri...

Page 58: ...lectronic water temperature probe for MICROPRO D controls EYMICROPRO EYMICROPROD EYSW 5 For éstro FL and FU floor mounted ventilating convectors install the MICROPRO control panel after configuring it by means of the internal microswitches see the manual provided on the side of the base unit opposite the water connections Then fit the frame onto the control panel fasten the door with grille on the...

Page 59: ...59 FC66000941 00 E 2 1 C A D B F G H E I RE RE RE RE RE ...

Page 60: ...60 FC66000941 00 G C B 3 RE RE RE RE RE ...

Page 61: ...a velocità media QA1 portata aria alla velocità minima A sezione utile di passaggio pa perdite di carico lato aria V velocità aria ACCESSORIO F1 F4 F5 F6 F7 F9 F10 F11 F12 GE C 80474 80475 80476 80477 82107 GEF C 80478 80479 80480 80481 82108 GM C 80482 80483 80484 80485 82109 These accessories are used when an external air intake SM motorisedlouvreorSmanuallouvre oraninternalrecoveredairflow are ...

Page 62: ...M 20 m2 0 064 0 064 0 064 0 064 0 071 0 071 0 091 0 091 0 091 0 112 0 112 0 133 A GM 40 m2 0 058 0 058 0 058 0 058 0 066 0 066 0 084 0 084 0 084 0 103 0 103 0 122 A GM 55 m2 0 055 0 055 0 055 0 055 0 061 0 061 0 079 0 079 0 079 0 097 0 097 0 115 B mm 480 480 480 480 680 680 880 880 880 1080 1080 1280 H mm 160 160 160 160 160 160 160 160 160 160 160 160 B 45 159 10 B 13 22 5 5 H 22 5 22 5 B H 45 5 ...

Page 63: ...63 FC66000941 00 6 6 6 6 6 7 7 7 7 7 38 H 11 B 11 10 15 15 15 10 10 GE GEF GM C GE GEF GM C GE GEF GM C GE GEF GM C GE GEF GM C ...

Page 64: ... presa di aria esterna durante le soste dell impianto o utilizzare soluzione antigelo verificandone il punto di congelamento L utilizzo della serranda è esteso a tutta la linea éstro ad eccezione delle versioni FB FC e dei modelli FU installati a pavimento Se installata su ventilconvettori con mobile FL FA ed FU alla serranda è necessario abbinare una coppia di zoccoli di copertura come indicato n...

Page 65: ...65 FC66000941 00 A 80 100 2 3 5 4 A A A A A B B 1 A C D S S S S S A F 1 4 480 F 5 6 690 F 7 9 900 F 10 11 1110 F 12 1320 ...

Page 66: ...66 FC66000941 00 15 15 15 15 6 7 7 7 7 7 A D B C S S S S S ...

Page 67: ...su tutta la gamma dei ventilconvettori serie éstro INSTALLAZIONE 1 Verificare che l installazione desiderata sia rispondente ad una delle configurazioni di figura 2 A Ventilconvettore a parete con serranda di presa aria a 90 B Ventilconvettore a parete con serranda di presa aria in linea C Ventilconvettore a soffitto con serranda di presa aria a 90 D Ventilconvettore a soffitto con serranda di pre...

Page 68: ... configurations in figure 2 A Flush mounted fan coil unit with 90 air inlet louvre B Flush mounted fan coil unit with in line air inlet louvre C Ceiling mounted fan coil unit with 90 air inlet louvre D Ceiling mounted fan coil unit with in line air inlet louvre The outdoor air inlet louvre is always supplied with the sleeve in the back air inlet position 2 Remove the sleeve as shown in figure 3 3 ...

Page 69: ...69 FC66000941 00 B C A D 1 2 A B C D SM SM SM SM SM ...

Page 70: ...70 FC66000941 00 3 4 A 80 100 A F1 F4 480 F5 F6 690 F7 F9 900 F10 F11 1110 F12 1320 SM SM SM SM SM ...

Page 71: ...71 FC66000941 00 5 6 15 15 15 15 A D B C SM SM SM SM SM ...

Page 72: ...72 FC66000941 00 0 50 100 72 5 8 5 116 8 a 8 b 7 SM SM SM SM SM ...

Page 73: ...73 FC66000941 00 230 V 1 50 Hz T 230 24V L N PE L 230V L 0V 1 2 3 M 5 1 2 3 4 C A 2 N L PE 1 LM24SR 1 2 3 5 B IL F 9a SM SM SM SM SM ...

Page 74: ... 1 2 3 5 1 2 3 M 5 N L PE 230 V 1 50 Hz L 230V LM24SR 1 2 3 5 1 2 3 M 5 N L PE LM24SR 1 2 3 5 1 2 3 M 5 N L PE L 0V 1 L 230V L 0V 1 L 230V L 0V 1 1 2 3 4 C A B IL F 2 3 IL F IL F IL F L PE N 1 2 3 TI 230 24V 9b SM SM SM SM SM ...

Page 75: ...75 FC66000941 00 ...

Page 76: ...40010 Bentivoglio BO Via Romagnoli 12 a Tel 051 8908111 Fax 051 8908122 www galletti it ...

Reviews: