Galaxy GHDX2-2430S/R-24F4D Installation and Hardware Reference Manual
5-12
Subsystem
Maintenance
Figure
5
-8: Dislodging the PSU
Step 4. Gently pull the PSU module out of the chassis
using the
retention handle.
Step 5.
Insert the replacement PSU module
into the slot with the
retention handle at its lowest position. Push the PSU in until
you feel the contact resistance with its back-end connectors.
Do not use force or slam the module into place. Doing so
can damage the back-end connectors or enclosure backplane.
Secure the PSU into the chassis slot. Make sure the saddle
notches of the extraction handle lock onto the anchor pins on
the interior walls of the module slot. Once in place, pull the
extraction handle in an upward motion to secure the module.
Figure 5-9: Securing PSU Using the Extraction Handle