ADJUSTMENTS BEFORE ENGINE STARTUP

START THE ENGINE

SPEED SETTING

START FUEL & IDLE ADJUSTMENT

The speed control unit governed speed setting is factory set at approximately engine idle speed. (1000 Hz., Speed sensor signal or 

600 RPM)

Crank the engine with DC power applied to the governor system.  The actuator will energize to the maximum fuel position until the 

engine starts. The governor system should control the engine at a low idle speed. 

 

The speed set point is increased by clockwise rotation of the Speed adjustment control.  Remote speed adjustment can be obtained with an 

optional 5K Speed Trim Control.

Droop

Idle

Speed

STarT fUeL aDJUSTmenT

1. Place the engine in idle by connecting Terminals M & G and placing the external selector switch in 

the Idle position.

2. Adjust the Idle or operating speed for as low a speed setting as the application allows. (CCW turn 

to lower speed)

3. Adjust the Start Fuel CCW until engine speed begins to fall. Increase the Start Fuel slightly so that 

the idle speed is returned to the desired level.

4. Stop the engine.

 IDLe SPeeD SeTTInG

5. If idle is not set using the external selector switch as described in 

STarT fUeL aDJUSTmenT

,  

place the optional external selector switch in the Idle position.

6. The idle speed set point is increased by the clockwise rotation of the Idle adjustment control. 

When the engine is at idle speed, the speed control unit applies droop to the speed controller to 

ensure stable operation.

Gain

Middle Position   [50%]

Stability

Middle Position   [50%]

Speed

Middle Position   [50%]

Start Fuel

Full CW (Maximum Fuel)   [100%] 

Speed/Fuel Ramp

Full CCW (Fastest)   [100%]

Set the following adjustments before starting the engine. 

The Speed potentiometer is a 25 turn potentiometer

noTe

Contact GAC with any questions on these settings. 

[Factory setting]

5.000

(127)

Ø0.266

(7)

1.031

(26)

5.932

(151)

5.000

(127)

5.650

(144)

A

B C D E

F

G H J

L M N P

ACTUATOR

PICK-UP

BATTERY

AUX

+10V

OUT

K

DROOP

IDLE

-       +

CAUTION

ENGINE SPEED CONTROL

COMPONENT. WHEN INSTALLING

OR SERVICING REFER TO

PRODUCT PUBLICATION.

Start

Fuel

Gain

Droop

Speed

Speed/Fuel

Ramp

Stability

Idle

1
2
3

4
5

ON
ON
ON
ON
ON

GA

C

OVERNORS

MERICA

ORP.

MADE IN USA

Patent Pending

®

1. Lead Circuit

2. Soft Coupling

3. Low Current Act.

4. Dead Time Comp.

5. Dither

ESD5500 - II

5

OTHER SETTINGS

DIP switches allow you to set the following settings on or off as required.  

These must be set prior to startup.  These include [Factory setting]:

• 

1 – Lead / Lag Circuit, adjusts for fast instability in the system [ON]

• 

2 – Soft Coupling, eliminates fast erratic governor behavior caused by very 

soft or worn couplings in the drive train between the engine and generator. 

[OFF]

• 

3 – Low Current Actuator, for use with light force/low current actuators 

including T1 ATB, ALR/ALN, 100-, 103-, and 104-Series actuators. [OFF]

• 

4 – Dead Time Compensation, adjusts for irregularity in engine speed 

above and below 3Hz. [ON]

• 

5 - Dither, reduces actuator sticking or increase stability in contaminated/

dirty environments.

 

[OFF]

Start
Fuel

Droop

Idle

Speed

Speed/Fuel

Ramp

Gain

Stability

Start
Fuel

Droop

Idle

Speed

Speed/Fuel

Ramp

Gain

Stability

[Factory setting]

Summary of Contents for Fusion Series

Page 1: ...Speed Signal Range 1 0 50 0 V AC Actuator Current 77 F 25 C 8 A MAX Continuous Speed Sensor Signal 1 0 120 V RMS Environmental Ambient Temperature 40 to 85 C 40 to 180 F Relative Humidity up to 95 All...

Page 2: ...SD controller 2 One end of each shield including the speed sensor shield should be grounded to a single point on the ESD case 3 Terminal A B E and F should be 16 AWG or larger Long cables require incr...

Page 3: ...2 Use shielded cable for all external connections to the ESD controller One end of each shield including the speed sensor shield should be grounded to a single point on the ESD case A 15 amp fuse mus...

Page 4: ...ol When the engine is at idle speed the speed control unit applies droop to the speed controller to ensure stable operation Gain Middle Position 50 Stability Middle Position 50 Speed Middle Position 5...

Page 5: ...procedure steps 1 3 as the Gain parameter Gain Stability Start Fuel Speed Fuel Ramp Start the engine and accelerate directly to the operating speed METHOD 1 Procedure 1 Remove the connection between T...

Page 6: ...an damage the speed control unit Never jumper Terminal P directly to Terminal N Droop is typically used for paralleling engine driven generators When in droop operation the engine speed will decrease...

Page 7: ...ce Defective speed sensor 3 P G 10 V DC Internal Supply Short on Terminal P Defective speed control unit 4 F A 1 0 2 0 V DC while cranking Speed parameter set too low Short open in actuator wiring Def...

Page 8: ...stem or b 14 V for a 24 V DC system Then Check or replace battery Momentarily connect Terminals A and F The actuator should move to the full fuel position Actuator or battery wiring in error Actuator...

Reviews: