background image

20

 

 

 

 

 

 

 

Governors America Corp. © 2021 Copyright All Rights Reserved

EEG7500 Enhanced Electric Governor   8-2021-A8      PIB5115

10

TUNING WITh ThE EEG

7500

 (CONTINUED)

The EEG7500 supports three fixed speeds and one variable speed de

-

vice. The variable speed can also be used as an additional fixed speed 

by setting speed minimum and speed maximum to the same value.  

By default, upon initial installation, the Selected Speed Mode input is set 

to 1 (Idle).  

A simple drop down on Engine Tuning 

 Speed Configuration 

 Speed 

Mode allows you to choose your speed mode. Using these selections 

also changes the I/O Configuration Physical Input Mapping. 

1. 

Open the GAConfig Tool Physical Input mapping menu. Note the 

default settings:

•  Speed Select A = Digital 1

•  Speed Select B = Digital 2

•  Variable Speed Input = Analog Input 1

•  Auxiliary Input = Analog Input 2

•  Selected Speed Mode = 1 in the 

Quick Access view

2. 

In the Physical Input mapping box, for Speed Select A, check the 

Override and then check the Off selection.  At Speed Select B, 

check Override and then check On.   

3. 

Note the Select Speed Mode is now 2 in Quick Access. 

4. 

Review the chart below for information on how the EEG7500 uses 

Speed Select A and B input to determine speed settings based on 

the state of switch inputs. 

Speed Setting

override

Speed Select a Speed Select B

Speed 1 (Idle)

Checked

Off

Off

Speed 2

Checked

Off

On

Speed 3

Checked

On

Off

Variable Speed (4)

Checked

On

On

5.  Open the 

Engine Tuning

 menu and set the desired settings that map 

the Selected Speed Input Mode 2. For each Selected Speed Mode 

you can set the desired tuning parameter settings using the Engine 

Tuning menu.  

Instead of using physical inputs, you can also check the 

Override

 box, 

and manually set the On or Off state of the selected physical input. The 

On/Off state stays set even after the EEG7500 is disconnected from PC 

software. 

• 

on

 equals a closed state 

•  Off

 is the open state. 

 maPPInG PHYSIcaL InPUTS To SPecIfIc SPeeD moDe

In this example the following is true:

• 

Speed Mode is 2

• 

The device mapped to Speed Mode 2: 

 

»

Fixed Speed = 1900

 

»

Gain 2 = 100 

Engine Status on the Engine Tuning screen and 

Selected Speed Mode will be 2. 

Summary of Contents for EEG7500

Page 1: ...ional or bidirectional torque motor actuators A position feedback sensor is required The Speed PID position request is the input to the Positioner loop the Position PID optimizes response and control...

Page 2: ...governor system to prevent loss of engine control Do not rely exclusively on the governor system electronic actuator to prevent overspeed A secondary shutoff device such as a fuel solenoid must be use...

Page 3: ...nal Selectable polarity 20 9 Analog Input 3 4 20 mA 20 10 Analog Input 4 0 5 V DC 4 20 mA with 200 external resistor 20 11 5 V Excitation 20 REQUIRED with potentiometer on Terminal 7 REQUIRED with pot...

Page 4: ...rs America Corp 2021 Copyright All Rights Reserved EEG7500 Enhanced Electric Governor 8 2021 A8 PIB5115 5 EEG7500 wiring DIAGRAMS continued Wiring for Feedback Speed Control and Non Feedback Speed Con...

Page 5: ...5 Governors America Corp 2021 Copyright All Rights Reserved EEG7500 Enhanced Electric Governor 8 2021 A8 PIB5115 5 EEG7500 wiring DIAGRAMS continued Wiring for Position CONTROL...

Page 6: ...dedicated actuator and mag pickup input as well as configurable analog and digital inputs to support direct communications like CAN J1939 using the GAConfig Tool software The EEG7500 supports analog...

Page 7: ...n box Polarity must be matched for all auxiliary products used with the EEG7500 Auxiliary Input Analog Input 2 Connector 2 Terminal 8 Terminal 9 Analog Input 3 provides dedicated 4 20 mA input signal...

Page 8: ...erminals 16 17 and 18 CAN and RS232 Connector 3 Terminals 19 20 and Terminals 21 23 An actuator position feedback sensor is required for the Control Mode Feedback Speed Control and Position Control bu...

Page 9: ...and connect the USB B port on the EEG7500 Power for the controller comes from the engine battery Ensure the system is powered a green LED displays on the EEG7500 8 Do not start the engine 9 Double cli...

Page 10: ...rmation yellow cautions and other pop up information Setting some parameter values impact other parameter values often displaying a caution One common message indicates the selected Control Mode does...

Page 11: ...h overspeed fuel limit Speed Configuration including Fixed speeds Variable speed settings Tuning Gain Stability Deadtime Lead circuit Light force Governing Speed anticipation Feedback Speed Control FS...

Page 12: ...outside the system such as speed switches and position switches setting a digital output mode mapping the output source to a specific event Physical output mapping sets a specific output to a specific...

Page 13: ...EEG7500 can be set up and used out of the box with an actuator attached using default settings Default settings are shown in section 17 Default Configuration This section details the initial installa...

Page 14: ...ridge Mode is set to Half Bridge but the actuator does not support half bridge 1 attempting to run the engine may harm the engine or actuator The information in the Initial Setup is based on using a N...

Page 15: ...ore Digital Output 1 Source should be set to Speed Switch 1 as shown in the Output Mapping Check the Override box to set the physical input to On or Off By combining settings you can map signals to sp...

Page 16: ...use automatic engine shut down Set this value low enough to prevent mechan ical damage but high enough to allow realistic load rejection speeds without stopping the engine Fuel Limit 0 100 100 Maximum...

Page 17: ...er EEG7500 1 11 2 7 3 6 ADDING A Potentiometer The shutdown STOP button available on the GAConfig tool shuts down fuel to the actuator but does not directly shutdown the engine To shut down the engine...

Page 18: ...ID Tuning section Stability is achieved by balancing PID Gain P Stability I and Deadtime D Gain Proportional changes the initial response of the governor Increasing gain makes the engine more responsi...

Page 19: ...ween 0 to 75 Set Input Maximum to at least 25 greater than the Minimum value Values entered which are not 25 different are automatically reset to the closest accepted value by the GAConfig Tool Variab...

Page 20: ...he Off selection At Speed Select B check Override and then check On 3 Note the Select Speed Mode is now 2 in Quick Access 4 Review the chart below for information on how the EEG7500 uses Speed Select...

Page 21: ...input parameters in I O Configuration Physical Input Mapping menu controls the actu ator position by a fixed amount each time a switch is closed and then opened again These inputs require the use of m...

Page 22: ...e dropdown menu on the Engine Tuning tab 2 In the Variable Position Settings box set the Variable Position Start and Variable Position End for the desired position control range The analog input signa...

Page 23: ...ng a 5 V Nominal 0 10 V DC and selectable response polarity In response the EEG can increase or decrease voltage to maintain constant engine speed Accessories tied to Aux must be shielded Light Force...

Page 24: ...s a controller to select the rpm corresponding to the analog voltage signal and commands the actuator accordingly It can also be used to set up position settings based on other data settings The table...

Page 25: ...sponds to J1939 speed requests with the J1939 speed control taking priority over speeds selected by Speed A and B selections J1939 DTC s are divided into two categories active and stored Active codes...

Page 26: ...00 ms SPN965 Number of ID fields SPN234 Software ID Number of ID fields fixed at 1 65266 Liquid Fuel Economy 100 ms SPN51 Engine Throttle Position SPN51 65241 Auxiliary IO 1 100 ms SPN701 AuxIO 1 SPN7...

Page 27: ...s 3 Click Start The data displays below 4 To save the data click the Save button The file is saved as a printable graphic png file 5 Select Reset Pan to move the cursor on the grid back to start posit...

Page 28: ...100 50 50 PID Gain to use when at the minimum speed while in variable speed PID Gain to use when at the Maximum speed while in variable speed Input Minimum 0 75 Must be 25 apart 0 Variable speed input...

Page 29: ...ensor Primary Redundant Redundant The current actuator position as determined by the feedback sensor input Position Feedback Low Position Feedback High Range 0 to 5 V DC Low 1 High 4 The voltage signi...

Page 30: ...NFC and NFSC mode Position A Input Position B Input Override Disabled Configures the input data signal routing for the operating mode Values are either fixed analog fixed discrete or mapped to a hardw...

Page 31: ...n variable speed mode Trim Range 0 120 rpm Trim for Speeds 1 2 3 Trim Increase Rate Trim Decrease Rate 0 120 rpm s Rate of change for trim SAE J1939 Configuration J1939 Address 0 Sets the CAN address...

Page 32: ...click Engine Shutdown then click System Reset 3 Check for power for the EEG7500 from the engine battery INSTABILITY SYMPTOM PROBABLE CAUSE OF ABNORMAL READING Fast Periodic The engine seems to jitter...

Page 33: ...wiring Actuator does not energize fully 1 Measure the voltage at the battery while cranking 1 If the voltage is less than a 7 V DC for a 12 V DC system or b 14 V DC for a 24 V DC system Then Check or...

Reviews: