EEG7500 Enhanced Electric Governor 8-2021-A8 PIB5115
Once the parameter settings are reviewed and updated as required, start your engine.
1. Crank the engine with DC power applied to the governor system.
2. Set the engine at operating speed with no load.
3. The actuator/ fuel to the engine will be positioned to the level set by the
parameter (default is MAX fuel). Actua
-
tor Ramp Rate controls the rate at which fuel is increased to start the engine. Set it 10 % by default.
4. If the engine is unstable after starting, open the GAConfig Tool and adjust Gain, Stability, and Deadtime in the
in the PID Tuning block, until the engine is relatively stable.
5.
Once the engine is stable you can connect additional devices and further optimization.
Use an overspeed shutdown device, independent of the governor system, to prevent loss of engine control which may cause
personal injury or equipment damage. Do not rely exclusively on the governor system electronic actuator to prevent overspeed.
A secondary shutoff device, such as a fuel solenoid must be used.
ParameTer
ranGe
DefaULT DefInITIon
control mode
Operating Mode
NFSC, FSC,
or PC
NFSC
Operating mode of the actuator.
requires restart of the eeG7500 for changes to take
effect
.
H-Bridge Mode
Bridge
Half Bridge
SeT-UP
Flywheel Teeth
60 - 250
120
Number of teeth on the engine flywheel. This should be set prior to starting the engine.
Overspeed
600 - 6000
1800
rpm set to cause automatic engine shut down. Set this value low enough to prevent mechan-
ical damage but high enough to allow realistic load rejection speeds without stopping the
engine.
Fuel Limit
0 - 100
100 %
Maximum fuel output.
STarT-UP
Actuator Start Fuel
1 - 100 %
100 %
Initial actuator position at start of crank.
Actuator Ramp Rate
1 - 100 %
10
%
The rate of change for the actuator start from the throttle begin point to 100%, during the start/
crank cycle (% / s)
Starter Cutoff
100 - 1000
400
The rpm at which governor switches from starting to governing. Also known as crank termina
-
tion.
Acceleration
25 - 2000
300
Rate of acceleration controlled by the governor when a command to increase rpm is received.
Deceleration
25 - 2000
300
Rate of deceleration controlled by the governor when a command to decrease rpm is received.
Once the control mode for your actuator is selected, the following minimum parameters must be set, or the default settings used, before
starting the engine. GAC suggests using the default settings to first ensure the engine runs smoothly before adding additional devices.
However, you may want to update default settings and additional parameter value depending on the engine, before starting the engine.
oTHer DefaULT SeTTInGS
ParameTer
DefaULT
ParameTer
DefaULT
Speed 1
1500
Gain 1, 2, and 3
50
Speed 2
1500
Stability
50
Speed 3
1500
Deadtime
High
Variable Speed Minimum
1500
Lead Circuit
On
Variable Speed
1500
Light Force Governor Enable
Off
Variable Speed Gain
50
Variable Speed End Gain
50
Analog Input 1
0 - 5 V DC
Input MIN
0 %
Speed Minimum
1500
Input MAX
100 %
Variable Speed Start Gain
50
Input Actual
0
Speed Maximum
1500