80
Safety / EMI-EMC:
EMI-EMC:
IEC 61326-1 Class B
Safety:
IEC 61010-1
Pollution Degree:
II
Installation Category:
III
Vibration Category:
2g Peak (10Hz
–
150Hz)
Shock:
IEC 61010- 1
IP Rating:
IP 65 (Only front Bezel)
Power Requirement:
Supply Voltage (Mains Operated
through adapter):
85-264 V AC
47-63 Hz
Power:
35 W Max with Maximum Configuration
Fuse Type:
None
Analog Input Board
No of Output Channel per Board:
8
No of slots consumed per Board:
1
Sensor Input type:
Refer to table 1
Range and Accuracy:
Refer to table 1
Linearization:
For RTD; Thermocouples; Square Root; 3/2 Power;
5/2 Power; Log10
Linearization Error:
±0.05 °C Max
Resolution:
User Settable up to 0.0001
CJC Accuracy:
±0.5°C
Sensor Open / Short / Out of Range:
Yes
Samples per second:
Max 26 samples per second all channels
Input Impedance RTD / TC / Volt:
>
20 MΩ
Input Shunt for 4-20mA and 0-20mA: 50
Ω ±0.1%
1/4W External
CMRR:
> 120 dB @50, 60Hz @ 50 Samples per second
NMRR:
> 87 dB @50, 60Hz @ 50 Samples per second
Maximum Common Mode Voltage:
30 V DC
Isolation Channel
–
Channel:
2.5 KVrms 1 minute (IEC 61010-1)
Isolation Channel
–
Earth:
2.5 KVrms 1 minute (IEC 61010-1)
Input Protection:
60 V AC/DC Max
Summary of Contents for 62 Series
Page 8: ...7 Figure 3 Panel Mounting...
Page 59: ...58 Figure 81 Historical Vertical Graph Figure 82 Historical Polar Graph...
Page 74: ...73 6 DEVICE TOUR This menu is not available in current version...
Page 75: ...74 7 ABOUT This menu shows the information regarding the company Figure 98 About Menu...