Menu functions:
Navigate the main menu with the UP / DOWN buttons.
Main screen part 1
Temperature T1 ° C
Shows the measured in ambient air temperature.
Humidity in RH
Shows the measured in the room relative humidity.
Temepratur T2 in C °
Displays measured in the water temperature.
Time
Displays the current time in hours and minutes.
Main screen part 2
Fanspeed 1
shows in% the fan speed of the exhaust air fan.
Fanspeed 2
shows in% the fan speed from the supply air fan.
Main screen part 3
Alarms of the exceeded maximum values.
T1
= Temperature sensor 1 max.
RH
= Humidity sensor 1 max.
T2
= Temperature sensor 2 max.
Alarms of underrun minimum values.
T1
= Temperature sensor 1 min.
RH
= Humidity sensor 1 min.
T1
= Temperature sensor 2 min.
Confirm with the SAVE / EXIT button an alarm. The 9. alarm LED will switch off should the
actual value be below the set value. Depending on the model there is located a dry contact
in the inside the 16A controller. This contact is closed on alarm.
Main menu:
Go with the ENTER button one level deeper into the menu. Here is a selection of the four
main menu items.
1. Set fan settings = Ventilator settings
2. Set exit 1 = Output setting of exit 1
3. Set exit 2 = Output setting of exit 2
4. General settings = General Settings
page 7 of 15
Mainscreen 1
T1=23.4C° RH=60%
T2=19.1C° 09:13
Fanspeed 1 90%
T1--- T2--- H---
Fanspeed 2 70%
T1--- T2--- H---