background image

 

D5032 

- SIL 3 Switch/Proximity Detector Repeater Relay Output 

G.M. International ISM0108-11 

ON 

D5032S 

A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode. 

 

WARNING:

  Dip-switch 7-8 must be set to “OFF” position. 

 

Configuration 

Dip switch configuration 

1

2

3

4

7-8 must be set to "OFF" position

3-4-6 Not used

5

6

7

8

ON

CH 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, 

de-energizes relay in fault condition) 

1

 

OFF 

5

OFF 

1

ON 

5

ON 

 

Input Input 

Input 

Input 

 

NO 

OR 

NC 

 

NO 

OR 

NC 

Output 

NE 

Output 

NE 

Output 

ND 

Output 

ND 

Position in fault condition 

2

ON 

2

OFF 

1

2

3

4

5

6

7

8

ON

Dip switch factory settings. All Switches are OFF 

For SIL Application 

For SIL Application 

Summary of Contents for D5032S

Page 1: ...IL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0108 11 SIL 3 Switch Proximity Detector Repeater Relay Output Termination Board Models D5032S D5032D D5032S D5032D INSTRUCTION...

Page 2: ...8 mA short circuit Output voltage free SPST relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA...

Page 3: ...tion in Zone 2 NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000...

Page 4: ...effective group See parameters indicated in the table below D5032 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5032 Terminals D5032 Associated A...

Page 5: ...Supply 24 Vdc Out 1 SIL3 Out 2 SIL 3 F 9 10 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with volt...

Page 6: ...a condition of contact close open and a line open short circuit fault Installation D5032 series are Switch Proximity Detector Interface housed in a plastic enclosure suitable for installation on custo...

Page 7: ...sabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NE ND Output...

Page 8: ...F ON OFF ND Mode NE Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OF...

Page 9: ...iguration 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled prox...

Page 10: ...dition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D5032D used as double channel Configuration Summary Table WARNING dip switch 6 7...

Reviews: