D5032
- SIL 3 Switch/Proximity Detector Repeater Relay Output
G.M. International ISM0108-11
Ordering Information
Front Panel and Features
SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 2 / 10 years (
≤
10% / >10 % of total SIF),
considering 100 mA max contact current.
SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 20 years (
≤
10% of total SIF),
considering 100 mA max contact current.
PFDavg (1 year) 4.92 E-05, SFF 90.06 %, with independent channel configuration.
PFDavg (1 year) 4.96 E-05, SFF 93.16 %, with D5032D used as duplicator (both channels) or
as fault indicator (only 1st ch.).
PFDavg (1 year) 4.66 E-05, SFF 93.53 %, with D5032D used as fault indicator (only 2nd ch.).
Systematic capability SIL 3
2 fully independent channels.
Input from Zone 0 (Zone 20), installation in Zone 2.
NO/NC switch/proximity Detector Input, NE/ND relay actuation mode.
Field open and short circuit detection.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, FM, FMC, INMETRO, EAC-EX, UKR TR n. 898, NEPSI, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
High Density, two channels per unit.
Simplified installation using customized Termination Boards.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
+ Input Ch 1 for Proximity or Voltage free Contact
Terminal block connections
HAZARDOUS AREA
- Input Ch 1 for Proximity or Voltage free Contact
+ Input Ch 2 for Proximity or Voltage free Contact
- Input Ch 2 for Proximity or Voltage free Contact
7
8
9
10
7 8
9 10
Model: D5032
1 channel
S
2 channels
D