background image

 

D5032 

- SIL 3 Switch/Proximity Detector Repeater Relay Output 

G.M. International ISM0108-11 

Function Diagram 

HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, 

HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, 

CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, 

CLASS I, ZONE 0, GROUP IIC 

SAFE AREA, ZONE 2 GROUP IIC T4, 

NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, 

GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 

 

Internal Dip switches programmable 

Relay contact shown in 

de-energized position 

Relay contact shown in 

de-energized position 

Relay contact shown in 

de-energized position 

MODEL D5032D

=

=

=

=

7

8

Termination

board

connector

Supply 24 Vdc

Out 1 (SIL3)

Out 2 (SIL 3)

+

-

F

=

=

=

=

9

10

+

-

In 1

Proximity

voltage free 

Contact

+

-

In 2

Proximity

voltage free 

Contact

voltage free 

Contact

voltage free 

Contact

R1

R2

R1

R2

Resistors R1 - R2 used with 

voltage free contact required 

for line fault detection. 

MODEL D5032D Duplicator or Fault Out

=

=

=

=

7

8

Termination

board

connector

Supply 24 Vdc

Out 1 (SIL3)

Out 2  Duplicator or Fault

+

-

F

9

10

+

-

In

Proximity

voltage free 

Contact

voltage free 

Contact

R1

R2

Resistors R1 - R2 used with 

voltage free contact required 

for line fault detection. 

Terminals 9-10 must be 

shorted to set module as 

Duplicator or Fault Out 

MODEL D5032S

=

=

=

=

7

8

Termination

board

connector

F

Supply 24 Vdc

Out NO Contact (SIL 3)

+

-

+

-

In

Proximity

voltage free

Contact

voltage free

Contact

R1

R2

Resistors R1 - R2 used with 

voltage free contact required 

for line fault detection. 

 (SIL 3)

Summary of Contents for D5032S

Page 1: ...IL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0108 11 SIL 3 Switch Proximity Detector Repeater Relay Output Termination Board Models D5032S D5032D D5032S D5032D INSTRUCTION...

Page 2: ...8 mA short circuit Output voltage free SPST relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA...

Page 3: ...tion in Zone 2 NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000...

Page 4: ...effective group See parameters indicated in the table below D5032 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5032 Terminals D5032 Associated A...

Page 5: ...Supply 24 Vdc Out 1 SIL3 Out 2 SIL 3 F 9 10 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with volt...

Page 6: ...a condition of contact close open and a line open short circuit fault Installation D5032 series are Switch Proximity Detector Interface housed in a plastic enclosure suitable for installation on custo...

Page 7: ...sabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NE ND Output...

Page 8: ...F ON OFF ND Mode NE Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OF...

Page 9: ...iguration 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled prox...

Page 10: ...dition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D5032D used as double channel Configuration Summary Table WARNING dip switch 6 7...

Reviews: