D5032 

- SIL 3 Switch/Proximity Detector Repeater Relay Output 

G.M. International ISM0108-11 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5032 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.5 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5032 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5032 Terminals 

Ch1 
Ch2 

7 - 8 

9 - 10 

Ch1 
Ch2 

7 - 8 

9 - 10 

Io / Isc = 22 mA 

Ch1 
Ch2 

7 - 8 

9 - 10 

Po / Po = 56 mW 

 

Ii/ Imax 

 

Pi / Pi 

 

D5032 Terminals 

D5032 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

IIC (A, B) 

Co / Ca = 2.4 µF 

Co / Ca = 16.8 µF 

Co / Ca = 75 µF 

IIB (C) 
IIA (D) 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot). 

 

Co / Ca = 66 µF 

Co / Ca = 16.8 µF 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 78.3 mH 

Lo / La = 313.4 mH 
Lo / La = 626.9 mH 

IIB (C) 
IIA (D) 

Lo / La = 1028.6 mH 

Lo / La = 313.4 mH 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 635.9 µH/

 

Lo / Ro = 2543.9 µH/

 

Lo / Ro = 5087.9 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 8347.4 µH/

 

Lo / Ro = 2543.9 µH/

 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Summary of Contents for D5032S

Page 1: ...IL 3 Switch Proximity Detector Repeater Relay Output G M International ISM0108 11 SIL 3 Switch Proximity Detector Repeater Relay Output Termination Board Models D5032S D5032D D5032S D5032D INSTRUCTION...

Page 2: ...8 mA short circuit Output voltage free SPST relay contact Contact material Ag Alloy Cd free gold plated Contact rating 4 A 250 Vac 1000 VA 4 A 250 Vdc 120 W resistive load Min switching current 1 mA...

Page 3: ...tion in Zone 2 NO NC switch proximity Detector Input NE ND relay actuation mode Field open and short circuit detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000...

Page 4: ...effective group See parameters indicated in the table below D5032 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5032 Terminals D5032 Associated A...

Page 5: ...Supply 24 Vdc Out 1 SIL3 Out 2 SIL 3 F 9 10 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with volt...

Page 6: ...a condition of contact close open and a line open short circuit fault Installation D5032 series are Switch Proximity Detector Interface housed in a plastic enclosure suitable for installation on custo...

Page 7: ...sabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NE ND Output...

Page 8: ...F ON OFF ND Mode NE Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes relay in fault condition No Fault No Fault 1 OFF 5 OF...

Page 9: ...iguration 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled prox...

Page 10: ...dition ON ON ON 1 IN OUT Operation SW2 NO NE or NC ND ON NO ND or NC NE for SIL application OFF Channel 1 2 SW4 ON OFF D5032D used as double channel Configuration Summary Table WARNING dip switch 6 7...

Reviews: