background image

 

Section 10 

 

00-02-0511 

2019-07-10 

Sequence of Operations 

Scanning

Normal Scan

 

During Normal Scan mode, each channel is displayed for the 
period set in the CH SCAN DELAY (Setup 5). The default is 3 
seconds. When the CH SCAN DELAY expires, the display 
changes to show the next channel. After all channels have been 
displayed, the sequence starts again from the first channel. The 
LCD looks like this: 

 

The Normal Scan mode can be turned ON or OFF. To toggle the 
Normal Scan mode, press and hold the SCROLL button until the 
display shows (approx. 1 sec.). 

 

Or 

 

It is possible to disable channels from being displayed, by 
selecting the channel as Ø=Ignored in the TC TYPE / UNITS 
(Setup 1). 

LOCKED SCAN 

During a Locked Scan, the Normal Scan is temporarily interrupted 
and only the Locked Channel is displayed for 60 seconds. A 
channel is locked when the UP or DOWN buttons are used to 
select a channel during Normal Scan mode. To unlock and 
resume Normal Scan mode, press the SCROLL button. 

After 60 seconds, the Normal Scan mode will resume, if no other 
keys have been pressed. 

It should be noted that while only one channel is being displayed, 
all channels are being scanned and checked against their (3) set 
points every 2 seconds. All set points remain active at all times. 

CHANNEL SP1-3 

During Normal or Locked Scan mode, the set points for each 
channel can be viewed. To enter the CHANNEL SP view for the 
channel currently displayed, press and hold the CHANNEL SP1-3 
button for approx. 1 second. 

The display will first show: 

 

From this display, use the UP

 

button to view SP2

 

and SP3. Press 

the CHANNEL

 

SP1

-

3

 

button again to return to the Normal or 

Locked Scan mode. No changes can be made to the set points 
from this view. To change a set point, use the SETPOINTS

 

(setup 

3) menu. 

SP HISTORY 

During Normal or Locked Scan mode, a history of the last channel 
setpoint trip can be viewed. To enter the SP HISTORY channel 
display, press the SP HISTORY button. 

The display will first show: 

 

The value on the right represents the channel that tripped for the 
SP# shown. From this display, use the UP button to view SP2 and 
SP3. For each SP# it is possible to view the set point for that 
channel when the channel tripped. Press the CHANNEL SP1-3 
button to view the setpoint for the channel stored in the history. 

If the group/deviation caused the trip, the display will show: 

 

Pressing the CHANNEL SP1-3 button will show the channel that 
caused the trip and the temperature deviation that caused the trip. 
The temperature deviation shown is an absolute value. In other 
words if the deviation was a negative number, a positive number 
will be shown. 

SP3 LATCH 

The TDXM-DC W/SP3 LATCH is a special version available to 
latch one of the three digital outputs when a trip is detected. For 
this version only, setpoint values are first-out. If a sensor channel 
temperature rises above set point, SP3 will activate and remain 
active until RESET or power is recycled in the unit. The display 
will show 1 2 3 (#3 is ON). The icons for SETPOINT 1 and 2 may 
also be ON depending on the status of those set points. 

If the tripped channel clears, the output for SP3 will not clear and 
the SP History for SP3 will not be overwritten by other SP3 trips. 
Example: If CH21 and CH22 have an SP3 setpoint of 180 and 
CH21 temperature rises to 190, SP3 OUT will be activated, and 
the SP History will show SP3 21 as the cause for trip. If 
temperature for SP3 21 falls below 180 or SP3 22 rises above 
180 after the trip has occurred, the SP3 OUT will remain active, 
and the SP History will not be altered. All channels continue to be 
scanned and compared against SP1 and SP2 setpoint values. 

To RESET the SP3 Output and allow continued scanning of SP3 
set points, press and hold SCROLL ENTER and DOWN ARROW 
keys simultaneously for at least 3 seconds. The display will 
indicate the latch has been cleared when the number 3 is no 
longer visible on the SETPOINT icon display. The display will 
show SETPOINT 1 2 3 (#3 is OFF). The icons for SETPOINT 1 
and 2 may also be ON depending on the status of those set 
points.

 

Summary of Contents for TDXM-DC Series

Page 1: ...00 02 0511 2019 07 10 Section 10 TemperatureScanner Pyrometer ModelTDXM DC Installation and Operations Manual...

Page 2: ...ly if you have any questions A visual inspection of this product for damage during shipping is recommended before installation It is your responsibility to ensure that qualified mechanical and electri...

Page 3: ...85 Serial Port 1 Modbus Integer Holding Registers 1 Replacement Parts 1 TDXM DC Mounting 2 Dimensions 2 TDXM DC Typical Wiring Diagram 3 TDXM DC I O Addresses 4 Sequence of Operations 5 Scanning 5 Set...

Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 5: ...led Control Options Each TDXM DC model features three outputs Two outputs are the Field Effect Transistor FET and one output is the Form C Relay Each channel has three set points one for each of the o...

Page 6: ...140 mm and four mounting holes 0 25 in 6 35 mm dia see diagram 2 Align the mounting studs to the drilled holes and insert the TDXM DC from the front side of the panel 3 Place a washer and a nut on eac...

Page 7: ...input wires away from other wires 2 in 51 mm minimum For hazardous application requirements the TDXM DC complete system must be installed in accordance with the national electrical code NEC Class I D...

Page 8: ...143 Ch 18 40 018 40 048 40 072 40 096 40 120 40 144 Ch 19 40 019 40 049 40 073 40 097 40 121 40 145 Ch 20 40 020 40 050 40 074 40 098 40 122 40 146 Ch 21 40 021 40 051 40 075 40 099 40 123 40 147 Ch 2...

Page 9: ...button The display will first show The value on the right represents the channel that tripped for the SP shown From this display use the UP button to view SP2 and SP3 For each SP it is possible to vi...

Page 10: ...Y SELECTION Setup 7 RTU BAUD SETUP Setup 1 TC TYPE UNITS Each channel can be individually set to display in units C or F for Type J or K thermocouples or ignored completely When a channel is ignored i...

Page 11: ...is set to zero the function is disabled The first group must start with Channel 1 For an example on a 16 cylinder engine group will be set to 16 The first 16 channels will be in the group The group c...

Page 12: ...UP and DOWN buttons to enter the desired RTU Node Number This is adjustable from 0 255 Press the SCROLL ENTER button and enter the baud rate and number of stop bits selection 0 9600 Baud N 8 1 1 19 2...

Page 13: ...Section 10 00 02 0511 2019 07 10 9 Map of Setup...

Page 14: ...Section 10 00 02 0511 2019 07 10 10 Map of Setup continued...

Page 15: ...e following A Be sure the display is in the scan mode The unlatch operation cannot be performed while viewing the history displays B Verify that the channel in the SP3 history has cleared To do this e...

Page 16: ...w channels Error 23 Inconsistent engineering units Error 24 Channels skipped disabled Error 25 Deviation value set to 0 Error 26 Group size goes past the 24th channel CJ Error If a cold junction senso...

Page 17: ...seconds Range Type J 0 F 1538 F 0 C 837 C Type K 0 F 1999 F 0 C 1093 C Display Type Custom 7 segment 7 character type with temperature units indication and setpoint trip indication Accuracy Cold junct...

Page 18: ...Section 10 00 02 0511 2019 07 10 14 Notes...

Page 19: ...Section 10 00 02 0511 2019 07 10 15 Notes...

Page 20: ......

Reviews: