FW Murphy TDXM-DC Series Installation And Operation Manual Download Page 5

 

Section 10 

 

00-02-0511 

2019-07-10 

General Information 

Description 

The innovative TDXM-DC gives you a unique, configurable temperature scanner/pyrometer with a built-in power 
supply. The design features a 7-character, 7-segment Liquid Crystal Display window with 1/2 inch (13 mm) easy-
to-read characters. Also located on the faceplate are membrane keys for easy configuring. 

Highly reliable and versatile, the TDXM-DC accepts up to 24 type J or K grounded or ungrounded* 
thermocouples. Each channel has three (3) adjustable set points SP1, SP2 and SP3. The SP1, SP2 and SP3 set 
points correspond to the SP1, SP2 and SP3 outputs. Additionally, it has the selectable feature to monitor and 
alarm or shut down on deviation from an average from up to two groups of temperatures (GRP/DEV; deviation 
from average). One group could be exhaust temperatures, and another group could be bearing temperatures. The 
TDXM-DC is capable of communicating with controllers, PLCs, computers or SCADA systems by a built-in RS485 
serial communications port. The TDXM-DC is available for 10 - 32 VDC systems. 

User Interface 

The User Interface includes a numeric LCD display and a 5-button membrane keypad for readout and channel 
configuration. Thermocouple types can be selected and set points entered through a series of set-up menus.  See 
Setup Menu in Set Up section. 

Thermocouple Types 

Each of the 24 channels on the TDXM-DC can be configured as J or K type thermocouples, and temperature 
units can be selected as °F or °C for the readout of each channel. Unused channels can be set to 

Ignore

 and will 

not be seen in the display and will not affect the outputs. All the unused channels must have the jumper installed. 

Control Options 

Each TDXM-DC model features three outputs: Two outputs are the Field Effect Transistor (FET), and one output 
is the Form-C Relay. Each channel has three set points, one for each of the outputs. This allows for greater 
system flexibility by grouping sets of channels through one output. 

Setpoint History 

The TDXM-DC stores the last setpoint trip for each output in non-volatile memory. For instance, if SP1 of channel 
1 was the last SP1 tripped, the LCD display will read SP1 1 when in the Setpoint History for SP1. 

Pressing the channel SP1-3 key will show the channel and the setpoint for that channel. If the trip was from a 
group function, the offending channel is shown with the value of the deviation from average. 

Sensor Inputs and Terminals 

The TDXM-DC accepts up to 24 type J or K grounded or ungrounded* thermocouples using 24 pairs of screw 
type connections. Each pair has a jumper from the factory. Any tripped setpoint is detected within two seconds 
after the set point is exceeded. 

RS485 Serial Port 

The RS485 serial port (MODBUS RTU slave) on the back of the module is provided for communicating with 
microcontrollers, PCs, PLCs and SCADA systems (see Typical Wiring Diagrams). It is recommended that a 
termination resistor (customer supplied) be used when the TDXM-DC is the last device connected in a daisy-
chain configuration. The baud rate, number of stop bits and slave node number can be set using the keypad. 
Communication is half-duplex. Modbus RTU function codes 3 and 6 are supported. Devices on the RS-485 
network must have a common ground. 

Modbus Integer Holding Registers 

See TDXM-DC I/O Addresses. 

Replacement Parts 

Plug, kit, TDXM-DC: Terminal Plug replacement kit-P/N 10-00-7848 

*   We recommend the use of ungrounded thermocouples. Errors in readings with grounded thermocouples can 
be the result of differences in grounding between different devices.

 

Summary of Contents for TDXM-DC Series

Page 1: ...00 02 0511 2019 07 10 Section 10 TemperatureScanner Pyrometer ModelTDXM DC Installation and Operations Manual...

Page 2: ...ly if you have any questions A visual inspection of this product for damage during shipping is recommended before installation It is your responsibility to ensure that qualified mechanical and electri...

Page 3: ...85 Serial Port 1 Modbus Integer Holding Registers 1 Replacement Parts 1 TDXM DC Mounting 2 Dimensions 2 TDXM DC Typical Wiring Diagram 3 TDXM DC I O Addresses 4 Sequence of Operations 5 Scanning 5 Set...

Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 5: ...led Control Options Each TDXM DC model features three outputs Two outputs are the Field Effect Transistor FET and one output is the Form C Relay Each channel has three set points one for each of the o...

Page 6: ...140 mm and four mounting holes 0 25 in 6 35 mm dia see diagram 2 Align the mounting studs to the drilled holes and insert the TDXM DC from the front side of the panel 3 Place a washer and a nut on eac...

Page 7: ...input wires away from other wires 2 in 51 mm minimum For hazardous application requirements the TDXM DC complete system must be installed in accordance with the national electrical code NEC Class I D...

Page 8: ...143 Ch 18 40 018 40 048 40 072 40 096 40 120 40 144 Ch 19 40 019 40 049 40 073 40 097 40 121 40 145 Ch 20 40 020 40 050 40 074 40 098 40 122 40 146 Ch 21 40 021 40 051 40 075 40 099 40 123 40 147 Ch 2...

Page 9: ...button The display will first show The value on the right represents the channel that tripped for the SP shown From this display use the UP button to view SP2 and SP3 For each SP it is possible to vi...

Page 10: ...Y SELECTION Setup 7 RTU BAUD SETUP Setup 1 TC TYPE UNITS Each channel can be individually set to display in units C or F for Type J or K thermocouples or ignored completely When a channel is ignored i...

Page 11: ...is set to zero the function is disabled The first group must start with Channel 1 For an example on a 16 cylinder engine group will be set to 16 The first 16 channels will be in the group The group c...

Page 12: ...UP and DOWN buttons to enter the desired RTU Node Number This is adjustable from 0 255 Press the SCROLL ENTER button and enter the baud rate and number of stop bits selection 0 9600 Baud N 8 1 1 19 2...

Page 13: ...Section 10 00 02 0511 2019 07 10 9 Map of Setup...

Page 14: ...Section 10 00 02 0511 2019 07 10 10 Map of Setup continued...

Page 15: ...e following A Be sure the display is in the scan mode The unlatch operation cannot be performed while viewing the history displays B Verify that the channel in the SP3 history has cleared To do this e...

Page 16: ...w channels Error 23 Inconsistent engineering units Error 24 Channels skipped disabled Error 25 Deviation value set to 0 Error 26 Group size goes past the 24th channel CJ Error If a cold junction senso...

Page 17: ...seconds Range Type J 0 F 1538 F 0 C 837 C Type K 0 F 1999 F 0 C 1093 C Display Type Custom 7 segment 7 character type with temperature units indication and setpoint trip indication Accuracy Cold junct...

Page 18: ...Section 10 00 02 0511 2019 07 10 14 Notes...

Page 19: ...Section 10 00 02 0511 2019 07 10 15 Notes...

Page 20: ......

Reviews: