background image

 

Section 10 

 

00-02-0511 

2019-07-10 

11 

Deviation from Average 

TDXM-DC 

– Deviation from Average Calculations 

This example is for a 6-cylinder engine

Figure 1 

Figure 2 

Deviation from Average 

Calculations

1

 

TDXM-DC 

Channels

 

Enabling  Channel 

grPA=  6

 

Absolute (1 

– ((2+3+4+5+6)/5))

 

1

 

Included

 

Absolute (2 

– ((1+3+4+5+6)/5))

 

2

 

Absolute (3 

– ((1+2+4+5+6)/5))

 

3

 

Absolute (4 

– ((1+2+3+5+6)/5))

 

4

 

Absolute (5 

– ((1+2+3+4+6)/5))

 

5

 

Absolute (6 

– ((1+2+3+4+5)/5))

 

6

 

 

 

 

Troubleshooting Tips 

If a temperature reading is incorrect, check the following: 

1.  Setup 1 

– TC Type and Units correct? 

2.  Cold junction reading reasonable? 

3.  Install a jumper in place of the TC, should read the same as cold junction temperature. 

4.  Check for proper and recommended wiring practices. 

A.  Shielded thermocouple grade extension wire. 

B.  No splices involving metals other than TC type metals? 

C.  TC wire separation from other wiring. 

5.  Check for possible grounded thermocouple problems. 

6.  Check DC power voltage to see proper range of voltage and possible noise. 

If the display shows all dashes (----------), it means all channels are set to ignore and the cold junction display is 
disabled. 

7.  If the SP3 Latch model does not unlatch, check the following: 

A.  Be sure the display is in the scan mode. The unlatch operation cannot be performed while 

viewing the history displays. 

B.  Verify that the channel in the SP3 history has cleared. To do this exit the SP history and use the 

arrow keys to navigate to the channel in the scan display mode. Take note of the current 
temperature and press and hold Channel SP1-3 to verify the temperature setpoint SP3 for the 
channel. (See mode details on CHANNEL SP1-3 key function.) 

Notes: 

 

Figure 1, these numbers represent the data from the channels. The values that are derived are not 
visible. The deviation from average calculation compares each channel to the rest of the group’s 
averaged value. 

 

Figure 1, the setting group (grPA) selects how many channels are included, from channel 1 for the 
first group. The second group/starts with the first channel after the first group. These channels will be 
involved in the deviation from average calculation. 

 

Figure 2, the setpoint represents the enabling threshold (EnA or Enb).  The current represents the 
enabling channel(s) (EChA or EChb) (0=any channel in the group). When the enabling channel(s) 
exceed the enabling threshold, the deviation from average calculations will take place. 

 

When a channel’s deviation exceeds the deviation (dEvA or dEvb) set point, the deviated channel will 
be recorded in the history. 

Summary of Contents for TDXM-DC Series

Page 1: ...00 02 0511 2019 07 10 Section 10 TemperatureScanner Pyrometer ModelTDXM DC Installation and Operations Manual...

Page 2: ...ly if you have any questions A visual inspection of this product for damage during shipping is recommended before installation It is your responsibility to ensure that qualified mechanical and electri...

Page 3: ...85 Serial Port 1 Modbus Integer Holding Registers 1 Replacement Parts 1 TDXM DC Mounting 2 Dimensions 2 TDXM DC Typical Wiring Diagram 3 TDXM DC I O Addresses 4 Sequence of Operations 5 Scanning 5 Set...

Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 5: ...led Control Options Each TDXM DC model features three outputs Two outputs are the Field Effect Transistor FET and one output is the Form C Relay Each channel has three set points one for each of the o...

Page 6: ...140 mm and four mounting holes 0 25 in 6 35 mm dia see diagram 2 Align the mounting studs to the drilled holes and insert the TDXM DC from the front side of the panel 3 Place a washer and a nut on eac...

Page 7: ...input wires away from other wires 2 in 51 mm minimum For hazardous application requirements the TDXM DC complete system must be installed in accordance with the national electrical code NEC Class I D...

Page 8: ...143 Ch 18 40 018 40 048 40 072 40 096 40 120 40 144 Ch 19 40 019 40 049 40 073 40 097 40 121 40 145 Ch 20 40 020 40 050 40 074 40 098 40 122 40 146 Ch 21 40 021 40 051 40 075 40 099 40 123 40 147 Ch 2...

Page 9: ...button The display will first show The value on the right represents the channel that tripped for the SP shown From this display use the UP button to view SP2 and SP3 For each SP it is possible to vi...

Page 10: ...Y SELECTION Setup 7 RTU BAUD SETUP Setup 1 TC TYPE UNITS Each channel can be individually set to display in units C or F for Type J or K thermocouples or ignored completely When a channel is ignored i...

Page 11: ...is set to zero the function is disabled The first group must start with Channel 1 For an example on a 16 cylinder engine group will be set to 16 The first 16 channels will be in the group The group c...

Page 12: ...UP and DOWN buttons to enter the desired RTU Node Number This is adjustable from 0 255 Press the SCROLL ENTER button and enter the baud rate and number of stop bits selection 0 9600 Baud N 8 1 1 19 2...

Page 13: ...Section 10 00 02 0511 2019 07 10 9 Map of Setup...

Page 14: ...Section 10 00 02 0511 2019 07 10 10 Map of Setup continued...

Page 15: ...e following A Be sure the display is in the scan mode The unlatch operation cannot be performed while viewing the history displays B Verify that the channel in the SP3 history has cleared To do this e...

Page 16: ...w channels Error 23 Inconsistent engineering units Error 24 Channels skipped disabled Error 25 Deviation value set to 0 Error 26 Group size goes past the 24th channel CJ Error If a cold junction senso...

Page 17: ...seconds Range Type J 0 F 1538 F 0 C 837 C Type K 0 F 1999 F 0 C 1093 C Display Type Custom 7 segment 7 character type with temperature units indication and setpoint trip indication Accuracy Cold junct...

Page 18: ...Section 10 00 02 0511 2019 07 10 14 Notes...

Page 19: ...Section 10 00 02 0511 2019 07 10 15 Notes...

Page 20: ......

Reviews: