FW Murphy TDXM-DC Series Installation And Operation Manual Download Page 10

 

Section 10 

 

00-02-0511 

2019-07-10 

 

 

Setup

To enter the SETUP routines, press the SCROLL ENTER and 
CHANNEL SP1-3 buttons simultaneously for 5 seconds. The 
display will first show: 

 

While continuing to depress the two buttons, the display will show 
progress in the form of dashes until the 5 seconds expires, as 
shown here: 

 

After the 5-second delay expires, the user will be required to enter 
a passcode. This shows that display (code is on a single sheet of 
paper provided with the instructions to the original buyer of the 
product): 

 

Use the UP and DOWN buttons to set the correct code and press 
the SCROLL ENTER button to enter the SETUP menu. If the 
correct code is not entered, the display will show: 

 

After three attempts, the display will return to Normal Scan mode. 
Upon entering the correct code, the SETUP menus can be 
accessed. The LCD will display: 

 

Use the UP and DOWN buttons to select the desired SETUP 
number and press the SCROLL ENTER button. To exit the 
SETUP menu, select Setup 0 and press the SCROLL ENTER 
button. In the SETUP menu, a zero shortcut can be used to return 
to a zero value such as CH 0 or SETUP 0. Press the CHANNEL 
SP1-3 button to zero any menu value. 

SETUP MENU 

The Setup menu is as follows: 

Setup 0 =    EXIT 

Setup 1 =    TC TYPE / UNITS 

Setup 2 =    OFFSET 

Setup 3 =    SETPOINTS 

Setup 4 =    GRP / DEV SETUP  

Setup 5 =    CH SCAN DELAY 

Setup 6 =    CJ DISPLAY SELECTION  

Setup 7 =    RTU / BAUD SETUP 

Setup 1 TC TYPE / UNITS 

Each channel can be individually set to display in units °C or °F 
for Type J or K thermocouples or ignored completely. When a 
channel is ignored, it is no longer scanned or displayed. Ignored 
channels do not appear in other SETUP menus. When the display 
shows SETUP 1, pressing the SCROLL ENTER button will 
change the display to the entrance and exit display for this setup. 

The LCD will first display the Channel Select display: 

 

Use the UP and DOWN buttons to select the desired channel to 
set up. (Select CH 0 to exit.) Press the SCROLL ENTER button, 
and the display will read: 

 

0 =   Ignore 

1 =   J type for °F 

2 =   K type for °F 

3 =   J type for °C 

4 =   K type for °C 

NOTE: All unused channels must have the jumper installed.

 

Use the UP and DOWN buttons to set the desired channel type. 
Press the SCROLL ENTER button to return to the Channel Select 
display. Repeat until all channels are configured. Return to CH 0 
to exit this setup. Press the UP button to go to SETUP 2. 

Setup 2 OFFSET 

It is possible to adjust the temperature value for each channel to 
match analog gauges or other instrumentation. This OFFSET is 
added to the actual scanned temperature. The offset for each 
channel is adjustable from -20 to +20 in the units set (for °F or °C) 
for that channel. For example, a reading of 100° C with an 
OFFSET of 5 would be adjusted to 105° C. This adjusted value is 
used for comparison to set points as well as display. At SETUP 2, 
press SCROLL ENTER. The LCD will first display the Channel 
Select entrance/exit display: 

Summary of Contents for TDXM-DC Series

Page 1: ...00 02 0511 2019 07 10 Section 10 TemperatureScanner Pyrometer ModelTDXM DC Installation and Operations Manual...

Page 2: ...ly if you have any questions A visual inspection of this product for damage during shipping is recommended before installation It is your responsibility to ensure that qualified mechanical and electri...

Page 3: ...85 Serial Port 1 Modbus Integer Holding Registers 1 Replacement Parts 1 TDXM DC Mounting 2 Dimensions 2 TDXM DC Typical Wiring Diagram 3 TDXM DC I O Addresses 4 Sequence of Operations 5 Scanning 5 Set...

Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 5: ...led Control Options Each TDXM DC model features three outputs Two outputs are the Field Effect Transistor FET and one output is the Form C Relay Each channel has three set points one for each of the o...

Page 6: ...140 mm and four mounting holes 0 25 in 6 35 mm dia see diagram 2 Align the mounting studs to the drilled holes and insert the TDXM DC from the front side of the panel 3 Place a washer and a nut on eac...

Page 7: ...input wires away from other wires 2 in 51 mm minimum For hazardous application requirements the TDXM DC complete system must be installed in accordance with the national electrical code NEC Class I D...

Page 8: ...143 Ch 18 40 018 40 048 40 072 40 096 40 120 40 144 Ch 19 40 019 40 049 40 073 40 097 40 121 40 145 Ch 20 40 020 40 050 40 074 40 098 40 122 40 146 Ch 21 40 021 40 051 40 075 40 099 40 123 40 147 Ch 2...

Page 9: ...button The display will first show The value on the right represents the channel that tripped for the SP shown From this display use the UP button to view SP2 and SP3 For each SP it is possible to vi...

Page 10: ...Y SELECTION Setup 7 RTU BAUD SETUP Setup 1 TC TYPE UNITS Each channel can be individually set to display in units C or F for Type J or K thermocouples or ignored completely When a channel is ignored i...

Page 11: ...is set to zero the function is disabled The first group must start with Channel 1 For an example on a 16 cylinder engine group will be set to 16 The first 16 channels will be in the group The group c...

Page 12: ...UP and DOWN buttons to enter the desired RTU Node Number This is adjustable from 0 255 Press the SCROLL ENTER button and enter the baud rate and number of stop bits selection 0 9600 Baud N 8 1 1 19 2...

Page 13: ...Section 10 00 02 0511 2019 07 10 9 Map of Setup...

Page 14: ...Section 10 00 02 0511 2019 07 10 10 Map of Setup continued...

Page 15: ...e following A Be sure the display is in the scan mode The unlatch operation cannot be performed while viewing the history displays B Verify that the channel in the SP3 history has cleared To do this e...

Page 16: ...w channels Error 23 Inconsistent engineering units Error 24 Channels skipped disabled Error 25 Deviation value set to 0 Error 26 Group size goes past the 24th channel CJ Error If a cold junction senso...

Page 17: ...seconds Range Type J 0 F 1538 F 0 C 837 C Type K 0 F 1999 F 0 C 1093 C Display Type Custom 7 segment 7 character type with temperature units indication and setpoint trip indication Accuracy Cold junct...

Page 18: ...Section 10 00 02 0511 2019 07 10 14 Notes...

Page 19: ...Section 10 00 02 0511 2019 07 10 15 Notes...

Page 20: ......

Reviews: