OPERATION - 3
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
3-15
VSRT_IOM_2018-1213
Par. No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
503
No-flame speeds VSD
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
0 %
100 %
0
65 %
65 %
522
Ramp up
5 s
20 s
20 s
523
Ramp down
5 s
20 s
20 s
542
Activation of VSD / PWM fan
0
1
1
544
Modulation Ramp
32 s
80 s
32 s
545
Lower load limit
20 %
100 %
20%
546
Upper load limit
20 %
100 %
100%
600
Actuators
601
Selection of reference point
Index 0 = fuel
Index 1 = air
0 = closed (<0)
1 = open (>90)
0
1
1
0
602
Actuator’s direction of rotation
Index 0 = fuel, Index 1 = air
0 = counterclockwise
1 = clockwise
0
1
0
0
606
Tolerance limit of position monitoring
0.5
2.5
1.7
641
Control of speed standardization of VSD
-25
1
0
642
Standardized speed
Index 0 = uC1
Index 1 = uC2
650
6500
Undefined
645
Configuration of analog output
0 = DC 0…10 V
1 = DC 2…10 V
2 = DC 0/2…10 V
0
2
0
700
Error History
701
Error history: 701-725.01. Code
0
255
.
Error history: 701-725.02. Diagnostic Code
0
255
.
Error history: 701-725.03. Error class
0
6
.
Error history: 701-725.04. Phase
0
255
.
Error history: 701-725.05. Startup counter
0
99999999
725
Error history: 701-725.06. Load
0 %
100 %
900
Process Data
903
Current output
Index 0 = fuel
Index 1 = air
0 %
100 %
0
922
Incremental position of actuators
Index 0 = fuel
Index 1 = air
-50
150
0
935
Absolute speed
0
65535
0
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note:
Customer settings should be recorded in the Customer column for reference.
Table 7 - Steam Program for Siemens LMV3*