3 - OPERATION
© Fulton 2018
3-12
VSRT_IOM_2018-1213
Par. No.
Parameter
Min Value
Max Value
Fulton Setting
Customer
000
Internal Parameters
41
Password
0
65535
NB/SN
100
General
102
Identification Date
0
255
103
Identification Number
0
65535
104
Pre-selected parameter set : Code
0
255
9
105
Pre-selected parameter set : Vers.
0
0xFFFF
V.01.01
107
Software version
0
0xFFFF
V 01.80
108
Software variant
0
255
1
113
Burner identification
0
99999999
121
Manual output
Undefined = automatic mode
0%
100%
Undefined
125
Main frequency
0 = 50 hz
1 = 60 hz
0
1
1
126
Display brightness
0%
100%
100%
127
Timeout for menu operation
10 min
120 min
30 min
128
Fuel meter: pulse valency [pulses per volumetric
flow unit]
0
400
0
130
Delete display of error history: to delete the
display, set to 1 then to 2
-5
2
0
141
Operating mode BACS
0 = off
1 = Modbus
2 = reserved
0
2
1
142
Setback time in the event of communication
breakdown
0 s
7200 s
1 s
143
Reserved
1
8
1
144
Reserved
10 s
60 s
30 s
145
Device address for Modbus
1
247
2
146
Baud rate for Modbus
0 = 9600
1 = 19200
0
1
1
147
Parity for Modbus
0 = none
1 = odd
2 = even
0
2
0
148
Performance standard at interruption of
communication with building automation.
For
modulation operation
…
0…19.9 = burner off
20…100 = 20…100% burner rating
For
multi-stage operation
…
0 = burner off
invalid = no performance
0 %
100%
Undefined
161
Number of faults
0
65535
162
Operating hours resettable
0 h
99999999 h
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note:
Customer settings should be recorded in the Customer column for reference.
Table 7 - Steam Program for Siemens LMV3*