2 - INSTALLATION
© Fulton 2018
2-6
VSRT_IOM_2018-1213
Figure 3 - 10/15-HP Model VSRT Dimensions - Top
Side View (All dimensions in inches)
FRONT VIEW
RIGHT SIDE VIEW
DRAWN BY:
CHECKED BY:
B.O.M. REVIEW:
APPROVED BY:
ELECTRICAL REVIEW:
MECHANICAL REVIEW:
REVISION
DRAWING NUMBER
JOB NUMBER:
PROJECT NAME:
PROJECT MANAGER:
DESCRIPTION:
VSRT-10 GAS FIRED MODULATED STEAM BOILER
(150 PSI)
9-SR-010312 - PDS
-
T. KENNEDY
11/16/2017
N/A
N/A
W.W.
11/28/2017
N/A
E.B.W.
11/28/2017
This design and drawings are
proprietary and are the
exclusive property of The
Fulton Companies. The
corporation does not permit
their use except with prior
written consent.
The items shown in this
drawing may be covered by
one or more patents of The
Fulton Companies.
SHEET 1 OF 1
THIRD ANGLE PROJECTION
TOLERANCES
FRACTION &
WHOLE VALUE
(1) PLACE DEC.
(2) PLACE DEC.
1/8
UNLESS OTHERWISE NOTED
DIMENSIONS ARE IN INCHES
0.03
(3) PLACE DEC.
SURFACE FINISH
250 MICRO-INCHES
0.005
0.5 DEG
ANGLE
0.015
Fulton Steam Solutions, Inc.
Fulo
t n
SEE
NOTE
9
SEE NOTES 3 AND 11
32 1/2 (MINIMUM WIDTH)
58 1/4
7 1/16
22 7/8
55 1/8
98 1/2
CLEARANCE REQUIRED
FOR BURNER REMOVAL
41 3/8
(AIR INLET)
73 5/8
(FUEL INLET)
(74)*
(STEAM OUTLET)
70
(MIN HEIGHT)
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
STEAM OUTPUT LB/HR: FROM 0 PSIG AT 212°F (0 KG/CM² AT
100°C)
ALL CLEARANCES ARE FACTORY RECOMMENDATIONS. CONSULT
LOCAL JURISDICTION FOR EXACT CODE COMPLIANCE.
FULTON RECOMMENDS MINIMUM CLEARANCE OF 36" IN FRONT
OF ELECTRICAL PANELS.
FULTON RECOMMENDS 36" CLEARANCE BETWEEN INSPECTION
OPENINGS OF ALL BOILERS, 18" CLEARANCE OF HANDHOLES,
AND 14" FROM EXHAUST STACK.
PLEASE REFER TO THE O&M MANUAL FOR ADDITIONAL
INFORMATION REGARDING CLEARANCES AND INSTALLATION
INSTRUCTIONS.
ALL DIMENSIONS INSIDE ( ) DENOTE REFERENCE DIMENSIONS.
ALL DIMENSIONS INSIDE
DENOTE OVERALL DIMENSIONS.
WE RESERVE THE RIGHT TO CHANGE SPECIFICATIONS
AND/OR DIMENSIONS. ALL INFORMATION IS SUBJECT
TO CHANGE BASED ON ADDITION OF ANY OPTIONAL
EQUIPMENT AND/OR ACCESSORIES. PLEASE CONSULT THE
FACTORY FOR PROJECT SPECIFIC ESTIMATES IF
ADDITIONAL OPTIONS OR ACCESSORIES ARE REQUIRED.
RECOMMENDED STACK RUN IS MINIMUM 24" STRAIGHT OFF
THE REAR OF THE BOILER, PRIOR TO MAKING A
DIRECTIONAL CHANGE.
LOCAL CODES CAN SUPERCEDE FULTON RECOMMENDED
CLEARANCE.
*SIZE DEPENDS ON TRIM PRESSURE.
MAX ALLOWABLE WORKING PRESSURE:
BOILER OUTPUT:
MINIMUM INCOMING GAS PRESSURE:
150 PSI
335,000 BTU/HR
345 LBS/HR
54.5 SQ. FT.
94 GAL.
1,932 LBS.
2,716 LBS.
2,500 LBS.
EQUIPMENT SPECIFICATION CHART
APPROXIMATE FLOODED WEIGHT:
MINIMUM DRAFT REQUIREMENT:
BURNER TURNDOWN:
3,008 LBS.
4:1
-0.25" W.C.
APPROXIMATE SHIPPING WEIGHT:
APPROXIMATE OPERATING WEIGHT:
APPROXIMATE DRY WEIGHT:
WATER CAPACITY (OPERATING):
NET EFFECTIVE HEATING SURFACE:
STEAM OUTPUT/MIN. SRV CAPACITY:
400 CU FT/HR
BOILER INPUT:
3" W.C.
BOILER INPUT: (NATURAL GAS)
400,000 BTU/HR
CUSTOMER CONNECTIONS
ITEM
DESCRIPTION
SIZE
TYPE
A
FEED WATER INLET
1"
N.P.T.
B
BLOWDOWN OUTLET
1"
N.P.T.
C
STEAM OUTLET*
1 1/4"
N.P.T.
D
EXHAUST STACK
6"
- - -
E
SAFETY RELIEF VALVE*
1"
N.P.T.
F
FUEL INLET
1"
N.P.T.
G
WATER COLUMN DRAIN
1"
N.P.T.
H
SIGHT GLASS DRAIN
1/4"
N.P.T.
J
WATER SAMPLE PORT
1/4"
N.P.T.
K
STEAM SAMPLE PORT
1/4"
N.P.T.
L
SURFACE BLOWDOWN (PLUGGED)
3/4"
N.P.T.
M
HIGH WATER PROTECTION (CAPPED)
3/4"
N.P.T.
N
SINGLE SOURCE POWER
- - -
N.P.T.
P
COMBUSTION AIR INLET
6"
- - -
R
AUXILIARY WATER COLUMN (CAPPED)
1"
N.P.T.
5
(BOTTOM BLOWDOWN)
22 3/8
(FEEDWATER)
71 5/8
(
*)
(S.R.V.)
76 3/8*
43 1/16
(EXHAUST STACK)
-
INITIAL RELEASE
-
-
-
-
-
REVISION HISTORY
REV
REVISION DESCRIPTION
B.O.M.
ELEC. ENG. MECH. ENG CHECKED
APPROVED
NOTE: OPERATING FULL LOAD AMPERAGE (FLA)
REFERS TO THE BOILER'S RATED CURRENT DRAW
AT HIGH FIRE.
ELECTRICAL REQUIREMENTS
VOLTAGE
OPERATING FLA
120/1/60
10 AMPS
E
C
P
F
K
J
G
N
B
A
L
R
D
M
7 1/8
H
Note 3: Fulton recommends a minimum clearance of 36” in front of the electrical panels.
Note 9: Fulton recommends 36” clearance between openings of all boilers, 18” clearance of handholes, and 18” from exhaust stack.
Note 11: Local codes supercede Fulton recommended clearances.