Table 9. Sequence and Status Hold Information.

Sequence

Status

INITIATE

The LED indicates the burner status, POWER, which is a stabilization period 
for the RM7895 to check for any fluctuations in ac line voltage inputs or 
control input on power-up or during normal operation. The timing of the 
INITIATE period is ten seconds before entering STANDBY.

If the RM7895 is in a HOLD status, the following conditions could exist:

INITIATE HOLD: (AC Frequency/Noise)

The LED indicates the burner status, POWER, and that it is waiting for excess 
line noise to clear up. The burner sequence will not advance into STANDBY 
until the excess line noise, which prevents sufficient reading of the line 
voltage inputs, ceases or a line frequency error is corrected (perhaps caused 
by using a 60 Hz device on a 50 Hz line, or vice versa—devices with a date 
code of 9804 or earlier).

INITIATE HOLD: (AC Line Dropout)

The LED indicates the burner status, POWER, and that ac line power has 
momentarily dropped out. The burner sequence will not advance into 
STANDBY until the ac line voltage has stabilized throughout the INITIATE 
sequence.

INITIATE HOLD: (AC Frequency)

The LED indicates the burner status, POWER, and that line frequency is faster 
than the expected value. The burner sequence will not advance into STANDBY 
until the ac line frequency returns to the proper value.

INITIATE HOLD: (Low Line Voltage)

The LED indicates the burner status, POWER, and that low line voltage has 
occurred. The burner sequence will not advance into STANDBY until the line 
voltage is at a sufficient level for proper operating parameters.

STANDBY

The LED indicates the burner status, POWER. The burner can be placed in 
STANDBY by opening the burner switch or if the operating controller 
indicates its set point has been satisfied. If a demand is present for burner 
operation, the burner sequence will not advance from STANDBY to PURGE 
until the recycle limits close.

If the RM7895 is in a HOLD status, the following conditions could exist:

STANDBY HOLD: F/G (Flame Detected)

The LEDs indicate the burner status, POWER and FLAME, and that a flame is 
detected. A demand is present for burner operation. The burner sequence will 
not advance to PREPURGE because a flame is detected as being present. The 
sequence will not advance to REPURGE until the flame signal clears. If the 
flame signal does not clear within 40 seconds, the RM7895 will lockout.

STANDBY HOLD: T7 (Airflow Interlock)

The LED indicate the burner status, POWER, and that the Airflow Interlock is 
closed. A demand is present for burner operation and the burner sequence 
will not advance to PREPURGE until the Airlock Interlock proves open.

PURGE

The LED indicates the burner status, POWER, and that it is the period of time 
before ignition during which time the blower motor is running. The timing of 
the PURGE period is selectable.

If the RM7895 is in a HOLD status, the following conditions could exist:

PURGE HOLD: F/G (Flame Detected)

The LEDs indicate the burner status, POWER and FLAME, and that a flame is 
detected. The burner sequence will not advance through PREPURGE because 
a flame is detected as being present. The sequence will hold waiting for the 
flame signal to clear. If the time exceeds 30 seconds, the RM7895 will 
lockout.

Summary of Contents for RM7895A

Page 1: ...c input check Dynamic safety relay test Dynamic self check logic Internal hardware status monitoring Tamper resistant timing and logic Access for external electrical voltage checks Application Flexibi...

Page 2: ...ing the current to blow the 15A fuse or breaker in event of an internal short circuit The RM7895 needs a low impedance ground connection to the equipment frame which in turn needs a low impedance conn...

Page 3: ...in Flame Signal Amplifier see Table 2 Plug in Purge Timer Cards selectable ST7800A two sec onds to 30 minutes Q7800A Wiring Subbase Accessories 203541 5 wire connector required when Keyboard Dis play...

Page 4: ...5 127 M3529 5 1 4 133 REMOVE ONLY FOR TERMINAL TEST ACCESS 1 1 BURNER CONTROL R MOUNTING FLANGE 1 2 14 NPSM LEADWIRES FACEPLATE 3 4 14 NPT M1962B 3 3 4 95 7 7 32 183 5 1 8 130 3 7 16 87 5 1 4 133 C701...

Page 5: ...terminal is not energized c No flame present at end of PFEP d Main valve terminal is energized e Internal system fault occurred f Purge card is removed g Purge card is bad 5 RUN PERIOD a No flame pres...

Page 6: ...and self checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY If a flame exists a safety shutdown occurs A standard amplifier is ener...

Page 7: ...trol and the main fuel valve s 2 Two flame detectors can be connected in parallel 3 This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance wit...

Page 8: ...All wiring must comply with applicable electrical codes ordinances and regulations Wiring where required must comply with NEC Class 1 Line Volt age wiring 4 Recommended wire size and type see Table 4...

Page 9: ...quired for the RM7895 Add the required disconnect means and overload protection 2 Check all wiring circuits and complete the Static Checkout see Table 7 before installing the RM7895 on the subbase 3 I...

Page 10: ...lifier flame amplifier signal probes electrical signal voltage probes and electrical connections M3536B G L2 3 4 5 6 7 8 9 10 F L1 13 14 15 16 17 18 19 20 21 22 12 AIR FLOW INTERLOCK MASTER SWITCH IGN...

Page 11: ...Fig 8 2 Insert the two interlocking ears into the two mating slots and with a hinge action push on the upper corners of the Dust Cover to secure it to the RM7895 3 Be sure the Dust Cover is firmly in...

Page 12: ...ut Causes for hold conditions in the INITIATE sequence are AC line dropout is detected AC line frequency error caused by using a 60 Hz device on a 50 Hz line or vice versa devices with a date code pri...

Page 13: ...If 10 second PFEP is chosen main valve terminal 9 is turned on as soon as flame is sensed Ignition terminal 10 is de energized as soon as the main valve is energized The pilot valve remains energized...

Page 14: ...red correctly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly IMPORTANT Do not perform a dielectric test with the RM78...

Page 15: ...oltage at terminal 6 1 Limits 2 Burner controller 3 4 5 7 L2 1 Burner motor fan or blower starts 2 Line voltage at terminal 7 within 10 seconds 1 Burner motor circuit a Manual switch of burner motor b...

Page 16: ...the flame detector s in the FINAL position Equipment Recommended Volt ohmmeter 1 Mohm volt minimum sensitivity with 0 300 Vac capability 0 6000 ohm capability 0 10 Vdc capability Checkout Summary Pre...

Page 17: ...e rod make sure Ground area is large enough Flame rod is properly located in the flame Temperature at the flame rod insulator is no greater than 500 F 260 C 4 For all optical detectors clean the detec...

Page 18: ...16 10 If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer close the manual main fuel shutoff valve s 11 Recycle the sys...

Page 19: ...ents for flame stability and input rating e Shut down the system by lowering the set point of the operating controller Make sure the burner flame goes out and all automatic fuel valves close Proceed t...

Page 20: ...cessary to construct a barrier to block the ignition spark from the detector view Continue adjustments until the flame signal due to ignition spark is less than 0 5 Vdc NOTE The Honeywell Q624A Solid...

Page 21: ...Troubleshooting manual form 65 0233 The RM7895 provides diagnostic information to aid the service mechanic to obtain information when troubleshooting the system see Table 8 The optional Keyboard Disp...

Page 22: ...STANDBY until the line voltage is at a sufficient level for proper operating parameters STANDBY The LED indicates the burner status POWER The burner can be placed in STANDBY by opening the burner swi...

Page 23: ...es shall be connected to the Burner Controller DDL line License agreement Copying and reverse engineering is prohibited by the law PURGE HOLD Airflow Interlock The LED indicates the burner status POWE...

Page 24: ...RM7895A RELAY MODULE U S Registered Trademark 2018 Honeywell International Inc 32 00122 01 M S Rev 08 18 Printed in United States...

Reviews: