10. GLOSSARY OF ACRONYMS

°C:

 Temperature in Celsius degrees.

°F:

 Temperature in Fahrenheit degrees.

Heat.: 

Heating.

LOC:

 Blocked.

OFF:

 Turned off/disabled. 

ON: 

Turned on, enabled.

Refr:

 Refrigeration.

SET (as in "Setting") 

(setting or configuration).

Vac: 

Electrical voltage (volts) of alternating current.

11. OPTIONAL ITEMS - Sold Separately

Ecase protective cover

It is recommended for the Evolution line, keeps water from entering the back part of the instrument. It 
also protects the product when the installation site is washed.

ECASE PROTECTIVE COVER

Extended frame

It allows the installation of Evolution line controllers with sizes 76 x 34 x 77 mm in various situations, 
since it does not require precision in the notch of the instrument fitting panel.
The frame integrates two switches of 10 Amperes that may be used to actuate interior light, air curtain, 
fan, and others.

CONTROLLER

EXTENDED
FRAME

SWITCHES

9. SIGNALS

Error in sensor: Sensor disconnected or damaged.

[Err1]

[er-U]

[Atlo]

[Athi]

[aldi]

[iNib]

[ton,]

[toff]

[LOC,][On,,]

[LOC,][OFF,]

[OFF,]

[eCAL]

[pppp]

Low temperature alarm.

High temperature alarm.

Buzzer inhibited.

Functions lockdown.

Unlocking of functions.

Control functions off.

Contact Full Gauge Controls.

Reconfigure the values of the functions.

Cyclic time on.

Cyclic time off.

 

 - version 2 or higher

EasyProg

It is an accessory that has as its main function to store the parameters of the controllers. At any time, you
can load new parameters of a controller and download them on a production line (of the same
controller), for example.
It has three types of connections to load or unload the parameters:

-

 

Serial RS-485:

 It connects via RS-485 network to the controller (only

for controllers that have RS-485).

- USB:

 it can be connected to the computer via the USB port, using 

Sitrad's Recipe Editor.

- Serial TTL:

 The controller can be connected directly to 

EasyProg by the TTL Serial connection.

EASYPROG

12. ANNEXES - Reference Images

Image III

Image IV

Image V

Y

X

PANEL

PANEL

LOCKS

CONTROLLER

CONTROLLER

VINYL

CONTROLLER

F29- Digital input mode of operation:

It allows to choose in which outputs the digital input will act.

[,,,0]

 - Disabled

[,,,1]

 - Acts only in the 1st stage (contact NA)

[,,,2]

 - Acts only in the 2nd stage (contact NA)

[,,,3]

 - It operates in both stages (contact NA)

[,,,4]

 - Acts only in the 1st stage (NF contact)

[,,,5]

 - Acts only in the 2nd stage (NF contact)

[,,,6]

 - Acts in both stages (contact NF)

The digital input allows the use of an external device to protect the control outputs (door switch or safety 
switch, for example). In the event of an external alarm, the corresponding output is switched off and 

[ALdi]

 is displayed.

F30 - Digital filter intensity applied to the sensor:

This filter has the purpose of simulating increase in thermal mass at the sensor thereby increasing its 
response time (thermal inertia). The higher the value set in this function, the more time the sensor takes 
to respond.
This function can be switched off by setting it at the minimum value 0 

[no,,]

.

F31 - Functions Lockdown:

This enables and configures the functions lockdown:

[,,,0]

- Does not enable the functions lockdown.

[,,,1]

- Enables a partial lock where the control functions will be locked but the adjustment of the 

setpoint, process times, cyclic timer times and visualization of the maximum and minimum record are 
allowed.

[,,,2]

- Enables a total lock, only displaying the time of the cyclic timer and the record of maximum 

and minimum temperatures.

F32 - Time for functions lockdown:

Allow lockdown of control functions (see item 8.3.2).

[,,15]

[,,60]

 Defines the time in seconds for the controller to activate.

F33 - Control functions shutdown:
Enables control functions shutdown (refer to item 8.3.3).

[,,,0]

-Disables control functions shutdown.

[,,,1]

-Enables activation/deactivation of the control functions only if the functions are unlocked.

[,,,2]

-Enables activation/deactivation of the control functions even if the functions are locked.

[,,,3]

-Enables activation/disable control functions only if functions are unlocked by turning the display off.

[,,,4]

-

Enables activation/disable control functions even if functions are locked by turning the display off.

Error in voltage measurement.

Digital input alarm.