19.PARAMETER TABLE
1.9
Sensors:
Configurations related to sensors.
1.9.x
Sensors S1-S6:
The letter x represents sensor inputs S1 to S6.
1.9.x.1
Pressure at 4 mA:
Sensor pressure value at 4 mA (lower scale limit).
1.9.x.2
Pressure at 20 mA:
Sensor pressure value at 20 mA (upper scale limit).
1.9.x.3
Pressure offset:
Allows compensating deviations in the pressure reading.
1.9.x.4
Temperature offset:
Allows compensating deviations in the temperature reading.
1.10
SAnalog outputs:
Configuration of limit values for analog outputs.
1.10.x
Analog outputs A1-A2:
The letter x represents analog outputs A1 to A2.
1.10.x.1
Analog output minimum value:
Minimum value the analog output will present when activated. This value limits the minimum rotation speed of the compressor or fan.
1.10.x.2
Analog output start value:
Value of the analog output during the starting up time.
1.10.x.3
Analog output maximum value:
Maximum value the analog output will present when activated. This value limits the maximum rotation speed of the compressor or fan.
1.11
Custom refrigerant table: - Point 1 to point 20:
Allows adjusting a custom saturated refrigerant curve. If the refrigerant used is not included in the list, the saturation, pressure and temperature values
can be entered here. The pressure and temperature values must be entered in ascending order from 1 to 20, i.e. the values of point 2 must be greater
than the values of point 1. A minimum of 10 points must be defined for the control. (Point 1 to point 10).
The letter “x” represents points 1 to 20.
1.11.x.1
Point x - Pressure of the mapped curve:
Pressure value of the point.
1.11.x.2
Point x - Pressure/temperature of the mapped curve:
Temperature value of the point.
1.9.x.1
1.9.x.2
1.9.x.3
1.9.x.4
850,0 (58,6)
850,0 (58,6)
-50,0 (-90,0)
0 (0)
0
850,0 (58,6)
0
0
Psi (Bar)
Psi (Bar)
Psi (Bar)
°C (°F)
-50,0 (-3,4)
0
50,0 (-3,4)
50,0 (-90,0)
Pressure at 20 mA
Temperature offset
Pressure at 4 mA
Pressure offset
1.10.x.1
1.10.x.2
1.10.x.3
100
100
0
0
0
0
%
%
%
0
100
100
Analog output start value
Analog output minimum value
Analog output maximum value
1.11.x.1
1.11.x.2
200,0 (392,0)
850,0 (58,6)
-50,1 (-58,2)
-14,8 [off] (-1,1)
-14,8 [off] (-1,1)
-50,1 (-58,2)
Psi (Bar)
°C (°F)
Point x - Temperature of the mapped curve
Point x - Pressure of the mapped curve
Function
Function
Function
Minimum
Minimum
Minimum
Maximum
Maximum
Maximum
Unit
Unit
Unit
Default
Default
Default
Description
Description
Description