19.PARAMETER TABLE
1.7.5.x.1
Operation mode:
Defines the operating mode as off, compression or decompression.
1.7.5.x.2
to
1.7.5.x.7
Pressure setpoint 01-06:
Pressure setpoint of output 01-06.
1.7.5.x.8
to
1.7.5.x.13
Pressure hysteresis 01-06:
Hysteresis of output 01-06.
1.7.5.x.14
Pressure sensor:
Specifies the pressure sensor.
1.7.5.x.15
to
1.7.5.x.20
Digital output address 01-06
Address of the digital output x.
1.7.5.x.21
Low pressure alarm:
Enables the alarm indication when the pressure is lower than the configured value.
1.7.5.x.22
High pressure alarm:
Enables the alarm indication when the pressure is higher than the configured value.
1.7.5.x.23
Alarm hysteresis:
Hysteresis of the pressure alarms.
1.7.5.x.24
Minimum time between activations:
The function applies to the main control outputs of the individual
and is the minimum time between two activations of the main digital outputs.
pressostat
This time ensures that no simultaneous activations of digital outputs will occur, preventing surges in the power network and excessive fluctuations of the
control variable.
1.7.5.x.25
Minimum output on/off time:
Minimum time the output remains on/off.
1.8
Maintenance time:
Configuration of the times for maintenance of compressors and fans.
1.8.x
Suction/Discharge:
The letter x represents the suctions (x between 1 and 3) and discharges (x between 4 and 6).
1.8.x.1
Maintenance time for compressor/fan 1 to 6:
Alarm time for compressor or fan operating hours.
0 = Not configured
Sensor options:
1 = S1
2 = S2
3 = S3
5 = S5
4 = S4
6 = S6
Note:
If a sensor already in use is selected, it
will be replaced.
1.8.x.1
1.8.x.2
1.8.x.3
1.8.x.4
9999
9999
0 [off]
0 [off]
0 [off]
0 [off]
0 [off]
0 [off]
h
h
h
h
h
h
0 [off]
0 [off]
1.8.x.5
1.8.x.6
0 [off]
0 [off]
0 [off]
0 [off]
9999
9999
9999
9999
Maintenance time for compressor/fan 02
Maintenance time for compressor/fan 06
Maintenance time for compressor/fan 04
Maintenance time for compressor/fan 01
Maintenance time for compressor/fan 05
Maintenance time for compressor/fan 03
Function
Minimum
Maximum
Unit
Default
Description