17.2 Automatic resets:
You can configure automatic resets for protection alarms. In the reset menu (
1.4.4
) it is possible to define the Number of reset attempts
(
1.4.4.1
), the interval between retries, and the period within which the reset will be retried.
If the number of attempts is set to the minimum value “Off ”, the reset will be manual only. If the number of attempts is set to the maximum value “Always”,
RCK-602
plus
will not limit the number of reset attempts, respecting only the times.
If the value is set between 1 and 10, this number of attempts will be made within the configured reset period (
1.4.4.3
), and a manual reset will be
required after this number of attempts.
Upon the occurrence of each protection alarm, the controller will check how many alarms of the same type occurred within the configured time. If it is
larger than the established time, the
will be locked in alarm condition and a manual reset will be required either via Sitrad or through the
pressostat
interface in the Control Menu, Reset option.
If the reset period has elapsed and the configured number of retries have not occurred, the retry counter will be reset.
17.3 Output signaling
Up to six digital alarm outputs can be configured in menu
1.4.5
. When configured, each output will be activated along with the visual alarm. The
activation mode of this alarm output can be either switched on or cycling.
!
Upon the occurrence of a protection alarm, the controller will check whether three
other alarms of the same type occurred within the last hour. If yes, the
pressostat
will be locked, otherwise it will be reset after five minutes.
Upon the occurrence of a protection alarm, the
will be reset after five
pressostat
minutes with no retry limit and the reset period setting is indifferent.
Example 1:
Number of attempts = 3
Interval between attempts = 5 minutes
Reset period = 1 hour
Example 2:
Number of attempts = always
Interval between attempts = 5 minutes
Reset period = 1 hour
Upon the occurrence of a suction 1
alarm, digital output 5 will cycle with
pressostat
Ton and Toff = 5 seconds. It will be switched off after the alarm condition ceases or
after a reset.
Upon the occurrence of a low pressure alarm on suction 1, output 6 will be
activated until a manual or automatic reset is performed.
Example: Configuring an output in menu
1.4.5.1.
Example: Configuring an output in menu
1.4.5.2.
Digital output = O5 (digital output 5)
Digital output = O6 (digital output 6)
Pressostat: Suction 1
Pressostat: Suction 1
Time on: 5 seconds
Time on: 0 seconds
Output function: Any alarm
Output function: Low pressure
Time off: 5 seconds
Time off: 0 seconds
17.ALARMS
Attention: By factory default, suction and discharge alarms are disabled and an appropriate limit must be configured depending on
the application.