- (CS01 - 11) -
Control system
- (CS01 - 11) -
C
O
N
TR
O
L
SY
ST
EM
C
O
N
TR
O
L
SY
ST
EM
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
Time program 4 / DHW
560
U
Preselection
Mo-Su / Mo-Fr / Sa - Su /
Mo / Tu / We / Th / Fr / Sa / Su
Mo-Su
561
U
1
st
phase on
00:00…23:50, --:--
00:00
562
U
1
st
phase off
--:--, 00:10…24:00
05:00
563
U
2
nd
phase on
00:00…23:50, --:--
--:--
564
U
2
nd
phase off
--:--, 00:10…24:00
--:--
565
U
3
rd
phase on
00:00…23:50, --:--
--:--
566
U
3
rd
phase off
--:--, 00:10…24:00
--:--
575
U
Copy
576
U
Default values
No/Yes
No
Time program 5 / Cooling circuit
600
U
Preselection
Mo-Su / Mo-Fr / Sa - Su /
Mo / Tu / We / Th / Fr / Sa / Su
Mo-Su
601
U
1
st
phase on
00:00…23:50, --:--
08:00
602
U
1
st
phase off
--:--, 00:10…24:00
20:00
603
U
2
nd
phase on
00:00…23:50, --:--
--:--
604
U
2
nd
phase off
--:--, 00:10…24:00
--:--
605
U
3
rd
phase on
00:00…23:50, --:--
--:--
606
U
3
rd
phase off
--:--, 00:10…24:00
--:--
615
U
Copy
616
U
Default values
No/Yes
No
Holidays heating circuit 1
641
U
Preselection
Period 1…8
Period 1
642
U
Period start (Day / Month)
--:--, 01.01…31.12
--:--
643
U
Period end (Day / Month)
--:--, 01.01…31.12
--:--
648
U
Operating level
Frost protection /
Reduced
Frost
protection
Holidays heating circuit 2
651
U
Preselection
Period 1…8
Period 1
652
U
Period start (Day / Month)
--:--, 01.01…31.12
--:--
653
U
Period end (Day / Month)
--:--, 01.01…31.12
--:--
658
U
Operating level
Frost protection /
Reduced
Frost
protection
Heating circuit 1
710
U
Comfort setpoint
Reduced temp to 35.0°C 20.0°C
712
U
Reduced setpoint
Frost protection temp to
comfort temp
19.0°C
714
U
Frost protection setpoint
4°C to reduced tempt
8.0°C
716
S
Comfort setpoint maximum
20.0…35.0°C
28.0°C
720
I
Heating curve slope
0.10…4.00
0.50
721
I
Heating curve displacement
-4.5…4.5°C
0.0°C
730
I
Summer/winter heating limit
---, 8.0…30.0°C
18.0°C
740
I
Flow temp setpoint min (for fan
convectors)
8...95°C
8°C
741
I
Flow temp setpoint max
8...95°C
55°C
750
S
Room influence
---, 1...100%
50%