LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
760
S
Room temp limitation
0.5…4°C
0.5°C
780
S
Quick setback
Off
Down to reduced setpoint
Down to frost prot setpoint
Down to reduced
setpoint
790
S
Optimum start control max
0…360min
180 min
791
S
Optimum stop control max
0…360min
60 min
800
S
Reduced setpoint increase start
-30…10°C
---°C
801
S
Reduced setpoint increase end
-30…10°C
-5°C
830
S
Mixer valve boost
0…50°C
0°C
834
S
Actuator running time
30…873sec
240sec
850
I
Floor curing function
0…5
Off
851
I
Floor curing setpoint manually
0…95°C
25°C
856
I
Floor curing day current
0...32
0
857
I
Floor curing days completed
0...32
0
900
S
Operating mode changeover
Protection
mode
Cooling circuit 1
901
U
Operating mode
Off / Automatic
Automatic
902
U
Comfort setpoint
15.0…40.0°C
24.0°C
907
U
Release
24h/day
Time program HC
Time program 5
24h/day
908
I
Flow temp setpoint at OT 25°C
6.0…35.0°C
20.0°C
909
I
Flow temp setpoint at OT 35°C
6.0…35.0°C
16.0°C
912
I
Cooling limit at OT
---, 8.0…35.0°C
20.0°C
913
S
Lock time at end of heating
---, 8…100h
24h
918
S
Summer compensation start at OT
20…50°C
26°C
919
S
Summer compensation end at OT
20…50°C
35°C
920
S
Summer compensation setpoint
increase
---, 1.0…10.0°C
4.0°C
923
S
Flow temp setpoint min OT 25°C
6.0…35.0°C
18.0°C
924
S
Flow temp setpoint min OT 35°C
6.0…35.0°C
18.0°C
928
S
Room influence
---, 1…100%
80%
932
S
Room temp limitation
---, 0.0…4.0°C
0.5°C
938
S
Mixing valve decrease
0…20°C
0°C
941
S
Actuator running time
30…650sec
120sec
945
S
Mixing valve heating mode
Control / Open
Open
963
S
With primary controller/system pump No/Yes
No