BACnet Gateway for VRF System
INSTRUCTION MANUAL r1.4.0 eng
114/159
Copyright© 2021 Fujitsu General Limited - All rights reserved
5.3.46 IU_rr_uu_AitFlowDirVT_Setting (Multistate Output Object Type)
Vertical air flow direction position can be set for indoor unit.
Property Identifier
Property Datatype
Value
ASHRAE
UTY-
VBGX
Object_Identifier
BACnetObjectIdentifier
(Multistate Output, 12rruu)
R
R
Object_Name
CharacterString
“IU_rr_uu_AirFlowDirVT_Setting”
R
R
Object_Type
BACnetObjectType
MULTISTATE_OUTPUT (14)
R
R
Present_Value
Unsigned
1 ~ 5
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Number_Of_States
Unsigned
5
R
R
State_Text
BACnetArray[N] of
CharacterString
Check Air Flow Dir VT setttings below
O
R
Priority_Array
BACnetPriorityArray
-
R
R
Relinquish_Default
Unsigned
-
R
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
Feedback_Value
Unsigned
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Event_Message_Texts
BACnetArray[3] of
CharacterString
-
O
-
Event_Message_Texts_Config
BACnetArray[3] of
CharacterString
-
O
-
Event_Detection_Enable
BOOLEAN
-
O
R*
Event_Algorithm_Inhibit_Ref
BACnetObjectPropertyRefer
ence
-
O
-
Event_Algorithm_Inhibit
BOOLEAN
-
O
-
Time_Delay_Normal
Unsigned
-
O
-
Reliability_Evaluation_Inhibit
BOOLEAN
-
O
-
Property_List
BACnetArray[N] of
BACnetPropertyIdentifier
BACnetArray[N]
R
R
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured