5. WIRING
WARNING
Before starting installation work, turn off the power of this product and
the connection destination. Do not turn on the power again until installa-
tion is completed. Otherwise, it will cause electric shock or
fi
re.
Use the accessories or speci
fi
ed connection cable. Do not modify power
supply cable and connection cables other than those speci
fi
ed, do not
use extension cables, and do not use independent branch wiring. It may
cause electric shock or
fi
re.
Install the connection cables securely to the terminal block. Con
fi
rm that
external force of the cable is not applied to the terminal block. Use the
speci
fi
ed cables. If intermediate connection or insertion
fi
xing are imper-
fect, it will cause electric shock,
fi
re, etc.
When connecting the connection cable, route the cables so that the
cover of this product is securely
fi
xed. If the cover is imperfectly
fi
xed, it
may cause
fi
re or overheating of the terminals.
Perform earth (ground) work positively. Do not connect the earth (ground)
cable to a telephone cable, water pipe, or conductor rod.
Perform all wiring works so that the user does not touch the wiring.
Otherwise it will cause injury or electric shock.
If any cable is damaged, do not repair or modify it yourself. Improper
work will cause electric shock or
fi
re.
CAUTION
Do not bind the remote controller cable and the external input cable
together with or parallel to the power supply cable of the indoor and
outdoor units. It may cause erroneous operation.
When performing wiring work, be careful not to damage the cable or
injure yourself. Also, connect the connectors securely. Loose connectors
will cause trouble, heating,
fi
re, or electric shock.
Install the indoor unit, outdoor unit, power supply cable, transmission
cable and remote control cable at least 40 in (1 m) away from a television
or radio.
The purpose of this is to prevent TV reception interference or radio noise.
(Even if they are installed more than 40 in (1 m) apart, you could still
receive noise under some signal conditions.)
Perform wiring so that water does not enter this product along the exter-
nal wiring. Always install a trap to the wiring or take other countermea-
sures. Otherwise it will cause trouble or electric shock or
fi
re.
Con
fi
rm the name of each unit and name of each terminal block of the
unit and connect the wiring in accordance with the directions given in the
manual so that there is no incorrect wiring. Incorrect wiring will damage
the electric parts and cause smoke and
fi
re.
When installing the connection cables near a source of electromagnetic
waves, use shielded cable.
Otherwise, a breakdown or malfunction could result.
The terminal screws and earth (ground) screws have different shapes.
Be sure to install the screws in the correct locations. If the screws are
installed in the wrong locations, the circuit board could be damaged.
4. SELECTING AN INSTALLATION LOCATION
4. 1.
Dimensions
This product is comprised of a body and cover.
Unit :
in (mm)
3-7/16 (86.7)
1-1/16
(27)
1/4 (7)
1/4
(7)
3-7/16 (86.7)
2-7/8 (72.7)
2-7/8 (72.7)
Bottom side
Upper side
Set the bottom side to a
fl
at place.
4. 2.
Speci
fi
cations
Power consumption (W)
0.6
Temperature °F (°C)
Operating
32–114 (0–46)
Packaged
14–140 (-10–60)
Humidity (%)
Packaged
0–95 (RH);
No condensation
Dimensions
H x W x D in (mm)
1-1/16 × 3-7/16 × 3-7/16
(27 × 86.7 × 86.7)
Weight oz. (g)
4 (100)