The names of terminal connected to thermostat have the following mean-
ings.

TC

Common (In) from transformer

C

Common to thermostat controller

TR

Power supply from transformer

R

Power supply to thermostat controller

G3

Air

fl

 ow High

G2

Air

fl

 ow Medium

G1

Air

fl

 ow Low

Y2

Cooling Stage 2

Y1

Cooling Stage 1

W2

Heating Stage 2

W1

Heating Stage 1

G

Fan

NOTES:

Up to 16 indoor units may be controlled with a single thermostat control-

ler, Multiple indoor units connected to convertor operate by the same 
operating setting.

Two or more types of VRF1 system, VRF2 system, single model or 

multi systems cannot be mixed together.

5. 2. 

Unit wiring

5. 2. 1  Thermostat cable and Remote controller cable

1-5/16 in
 (33 mm)

1/4 in

(7 mm)

Thermostat cable

Remote controller cable

For 2-wire type

For 3-wire type

9/16 in 

(15 mm)

1/4 in

(7 mm)

9/16 in 

(15 mm)

No polarity

1/4 in

(7 mm)

Y1:Red

Y2:White

Y3:Black

 

WARNING

Tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be occurred and possibly cause heavy 
damage inside the unit.

Tightening torque

M2 screw 
Remote controller / Y1, Y2, Y3
Thermostat input / G, W1, W2, 
Y1, Y2, G1, G2, G3, R, TR, C, TC

1.9 to 2.2 lbf·in

(0.22 to 0.25 N·m)
(2.2 to 2.5 kgf·cm)

 

CAUTION

To peel the sheath from the cables, use a dedicated tool that will not 
damage the conductor of the cable.

When installing a screw on the terminal block, do not cut the cable 
by overtightening the screw. On the other hand, a loosen screw can 
cause faulty contact, which will lead to a communication failure.

6.  INSTALLING THE THERMOSTAT CONVERTOR

 

WARNING

Always use the accessories and speci

fi

 ed installation work parts. Check 

the state of the installation parts. Not using the speci

fi

 ed parts will cause 

units to fall off, electric shock, 

fi

 re, etc.

Install at a place that can withstand the weight of the unit and install 
positively so that the unit will not topple or fall.

When installing this product, make sure that there are no children 
nearby.
Otherwise, injury or electric shock could result.

 

CAUTION

Do not set the DIP switch of this product except as speci

fi

 ed in this instal-

lation manual or the instruction manual supplied with the air conditioner. 
Setting the switches other than speci

fi

 ed will cause an accident or 

trouble.

Use an insulated screwdriver to set the DIP switches.

Before opening the cover of this product, completely discharge static 
electricity charged on your body. Otherwise, failure or malfunction could 
result.

Do not touch the circuit board and circuit board parts directly with your 
hands.
Otherwise, injury or electric shock could result.

Tightening the mounting screws too tight will damage the body of this 
product.

• When using the indoor unit without Fan mode, do not 

connect G (Fan), G1, G2, and G3 signals. Otherwise air 
conditioner might operate incorrectly.

• If the air conditioner system is a heat pump type, please 

select “ Priority on Administrative Indoor Unit” in the setting 
of priority mode by PUSH SWITCH of outdoor unit (refer to 
installation manual of outdoor unit). Furthermore, please 
complete “Administrative Indoor Unit Setting” for indoor unit 
which is connected to this Thermostat Convertor by using 
the wired remote controller (refer to installation manual of 
remote controller.)

NOTES:

When this product is used, do not use the remote controller because 
indoor unit is controlled centrally by thermostat controller.

However, the remote controller connecting is temporarily required for the 
initial setting. During the initial setting by remote controller do not con-
nect Thermostat Convertor to indoor unit. 
After when all initial setting is completed, disconnect  the wired remote 
controller. Then connect Thermostat Converter to indoor unit at 

fi

 rst time.

6. 1. 

Connecting the cables

(1)  For thermostat cable, use the single wire of 18AWG thermostat wire.
(2)  Power-supply voltage of thermostat (TC, TR) is 20 to 30VAC.
(3)  Insert the cable to the connected terminal and 

fi

 x with screw using 

screw driver.

(4)  For remote controller cable, 2 kinds of 2 kinds of type, which are 

2-wire type and 3-wire type are available depending on the device to 
be connected.

(5)  The number of connected thermostat cable is different the type of 

thermostat controller.

(6)  For details of connection method, refer to Case 1 to Case 3 of “5. 

Wiring”.

Summary of Contents for UTY-TTRX

Page 1: ...ervice personnel only MANUEL D INSTALLATION CONVERTISSEUR DE THERMOSTAT Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN CONVERTIDOR DE TERMOSTATO Únicamente para personal de servicio autorizado English Español PART NO 9374707225 Original instructions UTY TTRX ...

Page 2: ...tric shock If children may approach the unit take preventive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed might possibly result in personal harm to the user or damage to property Pay abundant care when transporting this product because it is a preci sion device Improper transportation will cause trouble Do not touch the switches ...

Page 3: ...ure yourself Also connect the connectors securely Loose connectors will cause trouble heating fire or electric shock Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 40 in 1 m away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you ...

Page 4: ...g on the type of thermostat con troller Connect them according to the following Cases For remote controller cable 2 kinds of type which are 2 wire type and 3 wire type are available depending on the device to be connected 1 All wiring shown should be performed with 18 AWG thermostat wire 2 Terminals to thermostat controller on this product support 20 30VAC 3 High medium low fan signals are optiona...

Page 5: ... DIP switch of this product except as specified in this instal lation manual or the instruction manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Use an insulated screwdriver to set the DIP switches Before opening the cover of this product completely discharge static electricity charged on your body Otherwise failure or malfunction...

Page 6: ...rt it to the connector Set to 2WIRE the DIP switch SW1 on the PC board of the indoor unit Layout of Connector and PC board is varies depending on the type of indoor unit Set to 2WIRE the DIP switch SW1 Indoor unit PC board Connector adapter Remote controller cable Non polar Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary SW1 Indoor unit PC bo...

Page 7: ... ON 81 27 Pattern2 ON OFF 75 24 Pattern3 ON ON 70 21 Pattern4 Factory setting 3 2 Two stage setting Cooling setting temperature SW SET3 2 Cooling Stage 1 setting temperature F C Cooling Stage 2 setting temperature F C Remarks OFF 68 20 64 18 Pattern1 ON 72 22 68 20 Pattern2 Factory setting Heating setting temperature SW SET3 3 SW SET3 4 Heating Stage 1 setting temperature F C Heating Stage 2 setti...

Page 8: ...ll be restarted auto matically LED1 green lights This product does not operate during initialization An error code will appear on LED in the event of a malfunction 10 LED DISPLAY 10 1 Normal code Normal indications Normal contents LED1 green LED2 orange LED3 red LED4 blue During initialization during initialization sequence Normally operating Display mode On Off 1s ON 1s OFF 10 2 Error code Error ...

Page 9: ......

Reviews: