Fujitsu UTY-TTRX Installation Manual Download Page 2

En-1

1. SAFETY PRECAUTIONS

 

The “SAFETY PRECAUTIONS” indicated in this manual contain impor-
tant information pertaining to your safety. Be sure to observe them.

 

Request the user to keep this manual on hand for future use, such as 
for relocating or repairing the unit.

WARNING

This mark indicates procedures which, if improp-
erly performed, might lead to the death or serious 
injury of the user.

Perform electrical work by an authorized service personnel in accordance 
with this manual and the electrical wiring regulations or implementation 
regulations of the country. Also do not install this product by yourself. 
Improper electric work will cause electric shock or a 

fi

 re.

Perform installation work in accordance with this manual. Request an 
authorized service personnel to perform installation work. Do not install 
this product by yourself. Improper installation will cause injury, electric 
shock, 

fi

 re, etc.

In the event of a malfunction (burning smell, etc.), immediately stop 
operation, turn off the electrical breaker, and consult authorized service 
personnel.

Do not install the unit in the following areas:

 

Do not install the unit near a source of heat, steam or 

fl

 ammable gas. 

 

Area 

fi

 lled with mineral oil or containing a large amount of splashed oil 

or steam, such as a kitchen. It will deteriorate plastic parts, causing the 
parts to fail or the unit to leak water.

 

Area that generates substances that adversely affect the equipment, 
such as sulfuric gas, chlorine gas, acid or alkali. It will cause the copper 
pipes and brazed joints to corrode, which can cause refrigerant leak-
age.

 

Area containing equipment that generates electromagnetic interfer-
ence. It will cause the control system to malfunction, preventing the unit 
from operating normally. 

 

Area that can cause combustible gas to leak, contains suspended 
carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint 

thinner or gasoline. If gas leaks and settles around the unit, it can 
cause a 

fi

 re.

 

Install the unit in a well-ventilated place avoiding rains and direct sun-
light.

Do not operate this product when your hands are wet. Touching the unit 
with wet hands will cause an electric shock.

If children may approach the unit, take preventive measures so that they 
cannot reach the unit.

CAUTION

This mark indicates procedures which, if improp-
erly performed, might possibly result in personal 
harm to the user or damage to property.

Pay abundant care when transporting this product because it is a preci-
sion device. Improper transportation will cause trouble.

Do not touch the switches with sharp objects. Doing so will cause injury, 
trouble, or electric shock.

Do not expose this product directly to water. Doing so will cause trouble, 
electric shock, or heating.

Do not set vessels containing a liquid on this product. Doing so will cause 
heating, 

fi

 re, or electric shock.

Dispose of the packing materials safely. Tear and dispose of the plastic 
packing bags so that children cannot play with them. There is the danger 
of suffocation if children play with the original plastic bags.

NOTES:

This product is manufactured to metric units and tolerances. 
United States customary units are provided for reference only. In cases 
where exact dimensions and tolerances are required, always refer to 
metric units.

2.  MAIN UNIT AND ACCESSORIES

The following installation parts are supplied. Use them as required.

Name and Shape

Q’ty

Application

Thermostat convertor

1

This product

Installation manual

1

This manual

Screw (M4 x 16 mm)

2

For mounting this product

3. ELECTRICAL REQUIREMENT

Use

Size

Cable type

Remarks

Remote con-
troller cable

(2-wire type)

16~22AWG

(0.33 to 1.25 mm

2

)

Sheathed 

PVC cable*

Non-polar 2 core, 
twisted pair
Maximum cable length: 
1,640 ft (500m)

Remote con-
troller cable

(3-wire type)

22AWG

(0.33 mm

2

)

Sheathed 

PVC cable*

Polar 3core

Maximum cable 

length: 82 ft (25m)

Thermostat 
wires

18AWG

(0.82 mm

2

)

Sheathed 

PVC cable*

Maximum cable 
length: 164 ft (50m)

*:  Use shielded cable in accordance with local rules for remote controller 

cable.

INSTALLATION MANUAL

PART NO. 9374707225
THERMOSTAT CONVERTOR

Contents

1. SAFETY 

PRECAUTIONS 

……………………………………………… 1

2. 

MAIN UNIT AND ACCESSORIES  …………………………………… 1

3. ELECTRICAL 

REQUIREMENT 

………………………………………… 1

4.  SELECTING AN INSTALLATION LOCATION  ……………………… 2

4. 1.  Dimensions  ……………………………………………………… 2
4. 2.  Speci

fi

 cations  …………………………………………………… 2

5. WIRING 

…………………………………………………………………… 2

5. 1.  Wiring method  …………………………………………………… 3
5. 2.  Unit wiring ………………………………………………………… 4

6.  INSTALLING THE THERMOSTAT CONVERTOR …………………… 4

6. 1.  Connecting the cables …………………………………………… 4

7.  CONNECTION OF REMOTE CONTROLLER CABLE ……………… 5
8.  CIRCUIT BOARD SETTING …………………………………………… 6
9.  TURNING ON THE POWER …………………………………………… 7
10. LED DISPLAY …………………………………………………………… 7

10. 1. Normal code ……………………………………………………… 7
10. 2. Error code ………………………………………………………… 7

11. USAGE …………………………………………………………………… 7

Summary of Contents for UTY-TTRX

Page 1: ...ervice personnel only MANUEL D INSTALLATION CONVERTISSEUR DE THERMOSTAT Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN CONVERTIDOR DE TERMOSTATO Únicamente para personal de servicio autorizado English Español PART NO 9374707225 Original instructions UTY TTRX ...

Page 2: ...tric shock If children may approach the unit take preventive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed might possibly result in personal harm to the user or damage to property Pay abundant care when transporting this product because it is a preci sion device Improper transportation will cause trouble Do not touch the switches ...

Page 3: ...ure yourself Also connect the connectors securely Loose connectors will cause trouble heating fire or electric shock Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 40 in 1 m away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you ...

Page 4: ...g on the type of thermostat con troller Connect them according to the following Cases For remote controller cable 2 kinds of type which are 2 wire type and 3 wire type are available depending on the device to be connected 1 All wiring shown should be performed with 18 AWG thermostat wire 2 Terminals to thermostat controller on this product support 20 30VAC 3 High medium low fan signals are optiona...

Page 5: ... DIP switch of this product except as specified in this instal lation manual or the instruction manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Use an insulated screwdriver to set the DIP switches Before opening the cover of this product completely discharge static electricity charged on your body Otherwise failure or malfunction...

Page 6: ...rt it to the connector Set to 2WIRE the DIP switch SW1 on the PC board of the indoor unit Layout of Connector and PC board is varies depending on the type of indoor unit Set to 2WIRE the DIP switch SW1 Indoor unit PC board Connector adapter Remote controller cable Non polar Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary SW1 Indoor unit PC bo...

Page 7: ... ON 81 27 Pattern2 ON OFF 75 24 Pattern3 ON ON 70 21 Pattern4 Factory setting 3 2 Two stage setting Cooling setting temperature SW SET3 2 Cooling Stage 1 setting temperature F C Cooling Stage 2 setting temperature F C Remarks OFF 68 20 64 18 Pattern1 ON 72 22 68 20 Pattern2 Factory setting Heating setting temperature SW SET3 3 SW SET3 4 Heating Stage 1 setting temperature F C Heating Stage 2 setti...

Page 8: ...ll be restarted auto matically LED1 green lights This product does not operate during initialization An error code will appear on LED in the event of a malfunction 10 LED DISPLAY 10 1 Normal code Normal indications Normal contents LED1 green LED2 orange LED3 red LED4 blue During initialization during initialization sequence Normally operating Display mode On Off 1s ON 1s OFF 10 2 Error code Error ...