BX600 S3
Operating Manual
61
Preparation for Use and Operation
Updating BX600 System Components
Ê
Update the firmware of the server blade (BIOS and BMC).
You have two options for doing this:
1. In the management console (Telnet) select the
TFTP Update
submenu.
The update process is similar to the process via the management blade
web user interface (see below).
2. In the web interface of the management blade, select the menu
System Property–Environ./Maintenance–Firmware Update–Server Blade BMC
or
System Property–Environ./Maintenance–Firmware Update–Server Blade BIOS
I
For security reasons the BIOS and BMC firmware can only be
updated if the relevant server blade was shut down beforehand,
otherwise the update option is not offered in the web menu.
Figure 21: Updating the server blade BIOS via the web interface
Ê
In the
TFTP Server IP Address
field, enter the IP address of the TFTP server
which provides the BIOS image file for the server blade firmware.
Ê
In the
Boot Image File Name
field, enter the file name of the boot image file for
the server blade.
Ê
Use the
Add
and
Delete
buttons to select the server blades whose BIOS is to
be updated.
Ê
Click the
Apply
button. The update file is transferred to all selected server
blades and the update process is started. The progress of the update
process is shown in a status screen.
Ê
Once the update process is complete, the server blade(s) is (are) restarted.