10. Electrical characteristics
Model name
AOHG18KMTA
AOHG24KMTA
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
13.5
16.0
Starting current
A
7.0
8.6
Wiring
spec.
*2
Circuit breaker current
A
16
20
Power cable
mm
2
2.5
Connection
cable *3
Cross-sectional area
mm
2
1.5—2.5
Limited wiring length
m
26
31
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 53 -
10. Electrical characteristics
OUTDOOR UNIT
AOHG18, 24KMTA
OUTDOOR UNIT
AOHG18, 24KMTA