6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Model: AOHG18KMTA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20
—
—
—
—
0.917
0.900
10
—
—
0.966
0.947
0.932
0.914
7.5
—
0.979
0.970
0.951
0.936
0.918
5
0.992
0.983
0.974
0.955
0.939
0.922
0
1.000
0.991
0.981
0.963
0.946
0.930
Indoor unit is lower than
outdoor unit *
2
-5
1.000
0.991
0.981
0.963
0.946
0.930
-7.5
—
0.991
0.981
0.963
0.946
0.930
-10
—
—
0.981
0.963
0.946
0.930
-20
—
—
—
—
0.946
0.930
HEATING
Pipe length (m)
5
7.5
10
15
20
25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20
—
—
—
—
0.887
0.871
10
—
—
0.952
0.903
0.887
0.871
7.5
—
0.976
0.952
0.903
0.887
0.871
5
1.000
0.976
0.952
0.903
0.887
0.871
0
1.000
0.976
0.952
0.903
0.887
0.871
Indoor unit is lower than
outdoor unit *
2
-5
0.995
0.971
0.947
0.899
0.883
0.866
-7.5
—
0.969
0.945
0.897
0.881
0.865
-10
—
—
0.942
0.894
0.879
0.863
-20
—
—
—
—
0.869
0.854
- 47 -
6-1. Model: AOHG18KMTA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG18, 24KMTA
OUTDOOR UNIT
AOHG18, 24KMTA