11. Safety devices
Type of
protection
Protection form
Model
AOHG18KMTA
AOHG24KMTA
Circuit
protection
Current fuse (PCB*)
250 V, 25 A
250 V 5 A
250 V, 3.15 A
Fan motor
protection
Thermal protection program
Activate
100±15°C
Fan motor stop
Reset
95±10°C
Fan motor restart
Compressor
protection
Thermal protection program
(Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection program
(Outdoor temp.)
(Only in COOL or DRY mode)
Activate
-20 °C
Compressor stop
-15 °C
Compressor stop
Reset
-15 °C
Compressor restart
-10 °C
Compressor restart
- 54 -
11. Safety devices
OUTDOOR UNIT
AOHG18, 24KMTA
OUTDOOR UNIT
AOHG18, 24KMTA