When connecting a new enclosure, if the total current consumption of power cords that connect to outlets
OUT1 to OUT4 exceeds 12A, connect to OUT5.
When the total current consumption of power cords that connect to outlets OUT5 to OUT8 exceeds 12A, con-
nect to the next power distribution unit.
For details on the current consumption of each power cord for each type of enclosure, refer to 

"Outlet/Socket

Specifications" (page 38)

.

The following figure shows an example when one frontend enclosure, two controller enclosures and four drive
enclosures are installed.

Figure 37 Power Distribution Unit (Horizontal Type) Installation Example

FE

CE#0

DE#0

DE#1

CE#1

DE#2

DE#3

PDU#3
PDU#2
PDU#1
PDU#0

OUT1

PDU#3

DE#3

DE#3

FE

FE

FE

FE

CE#0

CE#0

DE#0

DE#0

DE#1

DE#1

DE#2

DE#2

CE#1

CE#1

PDU#0

PDU#2

PDU#1

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

PDU number

PDU outlets number

Total current is within 12A

Total current is within 12A

Connect to the outlets using the connection order 
which is the same as the installation order in the rack.

Since the rated current has been
exceeded, the same connection
is not available. Connect to 
the next power distribution unit.

For the following combinations, the total current consumption of outlets OUT1 to OUT4 or the total current
consumption of outlets OUT5 to OUT8 exceeds 12A and then the connection fails.

Connection enclosures

Current consumption
(total for OUT1 to OUT4
or OUT5 to OUT8)

CE

CE

CE

CE

18.4A

CE

CE

CE

13.8A

CE

CE

CE

DE

16.5A

CE

CE

DE

DE

14.6A

CE

DE

DE

DE

12.7A

2. Rack Installation Specifications

Rack Installation Requirements
 

56

FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide

Copyright 2020 FUJITSU LIMITED

P3AM-9422-13ENZ0

Summary of Contents for ETERNUS DX8100 S3

Page 1: ...FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Requirements for transportation installation P3AM 9422 13ENZ0 ...

Page 2: ... 33 Load Bearing Capacity for Floors 37 Outlet Socket Specifications 38 Specifications for Optional Power Supply Products 39 Required Number of Outlets Sockets 43 Circuit Protectors 43 Input Power Supply Lines 47 2 Rack Installation Specifications 48 Rack Installation Requirements 48 Placement in the Rack 48 Power Cord Connection 54 Frontend Cable Connection 58 Backend Cable Connection 74 Installa...

Page 3: ...AC200V Vertical Type 42 Figure 23 Breaking Characteristics of Distribution Board Circuit Protectors 44 Figure 24 Example of a Power Supply Connection When a Power Distribution Unit AC200 240V Horizontal Type Is Used 45 Figure 25 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used 46 Figure 26 Input Power Supply Lines When Connecting to Power Sockets 47 Figure 27 Input P...

Page 4: ... GS 1800mm 69 Figure 47 Frontend Cable Connection Example When Connecting 10 DEs for Each Node in a 19 inch Rack for GS 1800mm 70 Figure 48 Frontend Cable Connection Example When Connecting 12 DEs for Each Node in a 19 inch Rack for GS 1800mm 71 Figure 49 Frontend Cable Connection Example When Connecting 14 DEs for Each Node in a 19 inch Rack for GS 1800mm 72 Figure 50 Frontend Cable Connection Ex...

Page 5: ...able Lengths When Connecting Each Enclosure to the Power Distribution Unit Horizontal Type 54 Table 18 Frontend Cable Connection Usage 19 inch Racks 2000mm with UNIX Industry Standard Server Connec tions 59 Table 19 Required Cable Length Quantity When Connecting Two DEs per Node 60 Table 20 Required Cable Length Quantity When Connecting Three to Four DEs per Node 61 Table 21 Required Cable Length ...

Page 6: ... and other servers or non Fujitsu servers This manual describes the environmental requirements that are necessary to install and use the ETERNUS DX This manual is intended for use of the ETERNUS DX in regions other than Japan Please carefully review the information outlined in this manual Thirteenth Edition January 2020 6 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems...

Page 7: ...torage system fujitsu com doc dx8k Document Conventions Third Party Product Names Oracle Solaris may be referred to as Solaris Solaris Operating System or Solaris OS Microsoft Windows Server may be referred to as Windows Server Notice Symbols The following notice symbols are used in this manual Indicates information that you need to observe when using the ETERNUS storage system Make sure to read t...

Page 8: ...ircle warns against certain actions The action which must be avoided is both illustrated inside the barred circle and written above it e g No Disassem bly The black Must Do circle indicates actions that must be taken The required action is both illustrated inside the black disk and written above it e g Unplug How Warnings are Presented in This Manual A message is written beside the symbol indicati...

Page 9: ...le Mainframe connections are not supported GS racks are not supported The power distribution units described in this manual are not available Preface 9 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 10: ...unit 1 Horizontal type 6 0kg 2 2 3 0kg 2 3 Power Voltage AC 100 120V AC 200 240V Phase Single Frequency 50Hz 60Hz Maximum power consumption Controller enclosure AC 100 120V 870W 880VA AC 200 240V 870W 880VA Drive enclosure 4 2 5 type AC 100 120V 430W 440VA AC 200 240V 430W 440VA 3 5 type AC 100 120V 340W 350VA AC 200 240V 340W 350VA Maximum heat generation Controller enclosure AC 100 120V 3 120kJ ...

Page 11: ...ent salt corro sion Vibration limit Operating 400gal Not operating 1 000gal Noise emission 5 Sound pressure level 53dB A Sound power level 7 0B 1 For power distribution units there are multiple types of exteriors For details refer to Specifications for Optional Power Supply Products page 39 2 These values are for product ID ETSPDHU ETSPDHU L 3 These values are for product ID ETSPDJU ETSPDJU L 4 Th...

Page 12: ...bution unit 1 Horizontal type 6 0kg 2 2 3 0kg 2 3 Vertical type 5 0kg 2 4 Power Voltage AC 200 240V Phase Single Frequency 50Hz 60Hz Maximum power con sumption Frontend enclosure 450W 480VA Controller enclosure 1 200W 1 220VA Drive enclosure 5 2 5 type 430W 440VA 3 5 type 340W 350VA Maximum heat genera tion Frontend enclosure 1 630kJ h Controller enclosure 4 330kJ h Drive enclosure 5 2 5 type 1 60...

Page 13: ...erating 400gal Not operating 1 000gal Noise emission 6 Sound pressure level 60dB A Sound power level 7 7B 1 For power distribution units there are multiple types of exteriors For details refer to Specifications for Optional Power Supply Products page 39 2 These values are for product ID ETSPDHU ETSPDHU L 3 These values are for product ID ETSPDJU ETSPDJU L 4 These values are for product ID ETSPDVU ...

Page 14: ...bution unit 1 Horizontal type 6 0kg 2 2 3 0kg 2 3 Vertical type 5 0kg 2 4 Power Voltage AC 200 240V Phase Single Frequency 50Hz 60Hz Maximum power con sumption Frontend enclosure 560W 590VA Controller enclosure 1 200W 1 220VA Drive enclosure 5 2 5 type 430W 440VA 3 5 type 340W 350VA Maximum heat genera tion Frontend enclosure 2 020kJ h Controller enclosure 4 330kJ h Drive enclosure 5 2 5 type 1 60...

Page 15: ...erating 400gal Not operating 1 000gal Noise emission 6 Sound pressure level 60dB A Sound power level 7 7B 1 For power distribution units there are multiple types of exteriors For details refer to Specifications for Optional Power Supply Products page 39 2 These values are for product ID ETSPDHU ETSPDHU L 3 These values are for product ID ETSPDJU ETSPDJU L 4 These values are for product ID ETSPDVU ...

Page 16: ...9 inch Rack with a DX8000 Series Dedicated Door 2000mm Installation Specifications Item Specification Base rack Expansion rack Dimensions W D H 700 1 090 2 000mm 700 1 272 2 000mm including anti tipping stabilizer Maximum weight 155kg 125kg Service area Refer to Figure 11 in Installation Area page 29 Number of units 42U 19 inch Racks for GS 1400mm The following table shows the installation specifi...

Page 17: ... 19 inch Racks for GS21 2600 2400 1800mm The following table shows the installation specifications of the 19 inch racks for GS21 2600 2400 1800mm Table 8 19 inch Rack for GS21 2600 2400 1800mm Installation Specifications Item Specification Base rack Expansion rack Dimensions W D H 700 1 110 1 800mm Maximum weight 144kg 120kg Service area Refer to Figure 13 in Installation Area page 29 Number of un...

Page 18: ...mension values do not include any protruding parts approximation Figure 1 Frontend Enclosure Dimensions 795mm 222mm 482mm Top Side 1 ETERNUS DX Installation Storage System Dimensions 18 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 19: ... do not include any protruding parts approximation Figure 2 Controller Enclosure Dimensions 809mm 482mm Top Front Side 133mm 1 ETERNUS DX Installation Storage System Dimensions 19 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 20: ...n values do not include any protruding parts approximation Figure 3 2 5 Type Drive Enclosure Dimensions 540mm 88mm 482mm Top Front Side 1 ETERNUS DX Installation Storage System Dimensions 20 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 21: ...Enclosure Dimensions 560mm 88mm 482mm Top Front Side Rack Dimensions The following diagrams show the dimensions of a 19 inch rack The dimension values do not include any pro truding parts approximation 1 ETERNUS DX Installation Rack Dimensions 21 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 22: ...der Installation Methods page 33 Figure 5 19 inch Rack with Standard Door 2000mm Dimensions Front Rear Bottom 2 000mm 1 050mm 700mm Side Top 1 ETERNUS DX Installation Rack Dimensions 22 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 23: ...der Installation Methods page 33 Figure 6 19 inch Rack with a DX8000 Series Dedicated Door 2000mm Dimensions Top Front Rear Side Bottom 2 000mm 1 090mm 700mm 1 ETERNUS DX Installation Rack Dimensions 23 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 24: ...nder Installation Methods page 33 Figure 7 19 inch Rack for GS 1400mm Dimensions Top Front Rear Side Bottom 1 400m 1 050mm 700mm 1 ETERNUS DX Installation Rack Dimensions 24 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 25: ...der Installation Methods page 33 Figure 8 19 inch Rack for GS21 1600 1400 1800mm Dimensions Top Front Rear Side Bottom 1 800mm 1 050mm 700mm 1 ETERNUS DX Installation Rack Dimensions 25 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 26: ...der Installation Methods page 33 Figure 9 19 inch Rack for GS21 2600 2400 1800mm Dimensions Top Front Rear Side Bottom 1 800mm 1 110mm 700mm 1 ETERNUS DX Installation Rack Dimensions 26 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 27: ...1000 3 2 EN61000 3 3 EN55024 VCCI Class A JIS C 61000 3 2 AS NZS CISPR22 Class A TP TC 020 2011 CNS13438 C6357 Class A KN22 Class A KN24 Class A Environmental compliance RoHS compliant Restriction of hazardous substances 2011 65 EU WEEE compliant Waste electrical and electronic equipment 80PLUS GOLD power conversion efficiency 1 ETERNUS DX Installation Compliance Standards 27 FUJITSU Storage ETERN...

Page 28: ...ure 940 640 500mm Approximately 75kg Controller enclosure 1 000 620 320mm Approximately 52kg Drive enclosure 2 5 type 600 660 240mm Approximately 40kg 3 5 type 600 660 240mm Approximately 40kg Drive 2 2 5 type 160 278 106mm Approximately 0 5kg 3 5 type 189 300 116mm Approximately 1 2kg Power distribution unit 3 Horizontal type 390 590 180mm 2 4 540 380 310mm 2 5 Approximately 7kg 2 4 Approximately...

Page 29: ...ea Front service area 1 050mm 850mm or more 850mm or more 1 013mm 18mm 19mm Rear door Front door 700mm Figure 11 Installation Area and Service Area of a 19 inch Rack with a DX8000 Series Dedicated Door 2000mm ETERNUS DX Rear service area Front service area 1 090mm 850mm or more 850mm or more 1 013mm 18mm 59mm Rear door Front door 700mm 59mm or more 1 80mm or more 1 1 ETERNUS DX Installation Instal...

Page 30: ...ore 1 80mm or more 1 Figure 13 Installation Area and Service Area of a 19 inch Rack for GS21 2600 2400 1800mm ETERNUS DX Rear service area Front service area 1 110mm 850mm or more 850mm or more 1 013mm 18mm 79mm Rear door Front door 700mm 79mm or more 1 80mm or more 1 1 ETERNUS DX Installation Installation Area 30 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Pl...

Page 31: ...tails refer to Figure 14 Figure 14 Example of Fujitsu 19 inch Racks Placed Side by Side 19 inch rack for GS21 2600 2400 19 inch rack with standard door 19 inch rack for GS21 2600 2400 19 inch rack with standard door OK Alignment with the front rack frame NG Alignment with the front doors 1 ETERNUS DX Installation Installation Area 31 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Sto...

Page 32: ...ach other In addition check if the ambient temperature in the installation location always satisfies the usage environment temperature by taking into con sideration the room size whether other storage systems are installed and how many people are present in the room When installing air conditioning consider the following Ambient Temperature An ETERNUS DX is cooled by taking in air through the fron...

Page 33: ...Contact your installation contractor for more details regarding installation and how the installation should actually be performed An installation diagram when installing a rack or the floor dimensions of the rack is shown below 19 inch Racks with Standard Door 2000mm Figure 15 Floor Dimensions of the Rack of 19 inch Racks with Standard Door 2000mm 919mm leveling feet 733mm caster Front Rear 523mm...

Page 34: ...veling feet 826mm 733mm caster 570mm leveling feet 523mm caster 700mm 175mm 350mm 47mm 140mm 95mm 1 013mm 1 090mm 65mm 89 mm Rear Front Caster Leveling feet Cable slot 1 ETERNUS DX Installation Installation Environment 34 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 35: ...Rear 549mm caster 409mm 700mm 146mm 1 050mm 50mm 925mm 71mm 76 mm 33mm 975mm 50 mm 559mm leveling feet 124mm Caster Leveling feet Cable slot 1 ETERNUS DX Installation Installation Environment 35 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 36: ...aster Front Rear 549mm caster 409mm 700mm 146mm 1 050mm 50mm 925mm 71mm 76 mm 33mm 975mm 50 mm 559mm leveling feet 124mm Caster Leveling feet Cable slot 1 ETERNUS DX Installation Installation Environment 36 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM 9422 13ENZ0 ...

Page 37: ...d bearing capacity of the floor and the weight of the ETERNUS DX is maintained Load bearing capacity of the floor ETERNUS DX weight Installation area that includes service areas If the condition above is not satisfied additional measures are required to ensure sufficient load bearing capaci ty Contact your installation contractor for details about the necessary measures that must be taken 1 ETERNU...

Page 38: ...res Power can be supplied from two power sources because each enclosure has two power supply units During normal operation each of the power sources supplies half of the necessary power When one of the power supply lines fails all of the necessary power is supplied from only one power source Current Consumption The following table shows the current consumption guideline of each power cord that is ...

Page 39: ...e power cords can be used if the specifications of the connection device allow AC200V Table 11 Specifications for AC200V Power Cords for the EMEIA Central American and Caribbean Regions Usage Plug type Socket type Socket Cable length Voltage rating current rating Used for connection be tween the ETERNUS DX and the socket IEC60320 C13 n IEC60320 C14G IEC60320 C14G IEC60320 C13 1 5m 250V 10A AC200V ...

Page 40: ...wer Cords for Regions other than the EMEIA Central American and Caribbean Regions Usage Plug type Socket type Socket Cable length Voltage rating current rating Used for connection be tween the ETERNUS DX and the socket IEC60320 C13 n IEC60320 C14 IEC60320 C14 IEC60320 C13 0 5m 1 0m 1 5m 3 0m Rating 250V 10A Normal usage rating 8A 1 ETERNUS DX Installation Outlet Socket Specifications 40 FUJITSU St...

Page 41: ...ets Two inlets Figure 21 Power Distribution Unit AC200V Horizontal Type Sixteen outlets Two inlets Table 14 Power Distribution Unit AC200 240V Horizontal Type Specifications Outlet Inlet Voltage rating current rating Socket type Socket Plug type Socket type Socket Cable length IEC60320 C13 NEMA L6 30P NEMA L6 30R 4 0m Rating 250V 30A Normal usage rating 24A 12A 2 1 ETERNUS DX Installation Outlet S...

Page 42: ...15 Power Distribution Unit AC200 240V Vertical Type Specifications Outlet Inlet Voltage rating current rating Socket type Socket Plug type Socket type Socket Cable length IEC60320 C13 NEMA L6 30P NEMA L6 30R 4 0m Rating 250V 30A Normal usage rating 24A 1 ETERNUS DX Installation Outlet Socket Specifications 42 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Plannin...

Page 43: ...on must be secured between the distribution board circuit protectors and the ETERNUS DX or power distribution units to protect the ETERNUS DX by blocking the failed circuit immediately when a power supply input error occurs Distribution board circuit protectors must satisfy the following required conditions and breaking characteristics Required Conditions The distribution board circuit protectors ...

Page 44: ... Characteristics of Distribution Board Circuit Protectors Operation time 0 01 0 02 0 04 0 06 0 1 0 2 0 4 0 6 1 2 4 6 10 20 40 1 2 4 6 10 20 40 60 120 180 1 1 5 2 3 4 5 6 7 8 10 15 20 30 40 50 80 100 Current ratio for the current rating D C B Minutes Seconds 1 ETERNUS DX Installation Outlet Socket Specifications 44 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Systems Site Pl...

Page 45: ...r Supply Connection When a Power Distribution Unit AC200 240V Horizontal Type Is Used CP Distribution board Distribution board Line 0 To power supply facility CP To power supply facility Power distribution unit Line 1 Controller enclosure CP CP CP CP Frontend enclosure PSU PSU PSU PSU PSU PSU PSU PSU Drive enclosure ETERNUS DX PSU Power Supply Unit CP Circuit Protector 1 ETERNUS DX Installation Ou...

Page 46: ...closure Controller enclosure ETERNUS DX PSU Frontend enclosure Distribution board Distribution board To power supply facility To power supply facility PSU PSU PSU PSU PSU PSU PSU PSU Power Supply Unit CP Circuit Protector Only connect the ETERNUS DX to circuit protectors 1 ETERNUS DX Installation Outlet Socket Specifications 46 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage S...

Page 47: ...o a UPS Unit UPS UPS PSU PSU Line 0 Line 1 Power distribution unit ETERNUS DX When the power distribution units are separately connected to line 0 PSU 0 and line 1 PSU 1 the availa bility of the power supply facilities is improved Power distribution unit Power distribution unit ETERNUS DX Line 0 Line 1 PSU Drive enclosure Controller enclosure Frontend enclosure Power supply facility Power supply f...

Page 48: ...e secure a space of 1U or more at the bottom when installing the storage system For 19 inch racks install the power distribution unit horizontal type in the lower part of the rack For 19 inch racks with standard door 2000mm and 19 inch racks with a DX8000 series dedicated door 2000mm install the power distribution unit vertical type in the dedicated spaces at the sides of the rack When connecting ...

Page 49: ...le of an Installation to 19 inch Racks for GS 1800mm Figure 29 Example of an Installation to 19 inch Racks for GS 1800mm Base rack rear DE DE DE DE SCCI PPC PDU 0 PPC CE PDU 1 PDU 2 Base rack rear DE DE DE DE SCCI PPC PDU 0 PPC CE PDU 1 For AC100V connections For AC200V connections 2 Rack Installation Specifications Rack Installation Requirements 49 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX89...

Page 50: ...ntal type are installed in the lower part of each rack A single frontend enclosure is installed in a base rack Controller enclosures and drive enclosures are installed in the order of each node The installation position of controller enclosures is fixed Even if the number of drive enclosures per node is odd leave a space between the drive enclosures Figure 30 Example of an Installation to 19 inch ...

Page 51: ...inch Racks with Standard Door 2000mm When Connecting Five or Six Drive Enclosures per Node Base rack rear Expansion rack 0 Expansion rack 1 Expansion rack 2 FE CE 0 DE DE DE DE CE 1 DE DE DE DE DE DE DE DE DE DE DE DE DE DE CE 3 DE DE DE DE DE DE PDU 4 PDU 5 PDU 3 PDU 2 PDU 1 PDU 0 PDU 3 PDU 2 PDU 1 PDU 0 PDU 3 PDU 2 PDU 1 PDU 0 PDU 3 PDU 2 PDU 1 PDU 0 PDU 3 PDU 2 PDU 1 PDU 0 Expansion rack 3 PDU ...

Page 52: ...DU 4 PDU 1 PDU 3 PDU 5 CE 5 DE 50 DE 54 DE 58 DE 5C DE 51 DE 59 DE 5D DE 55 DE 52 DE 56 DE 5A DE 5E DE 53 DE 5B DE 5F DE 57 PDU 0 PDU 2 PDU 4 PDU 1 PDU 3 PDU 5 PDU 5 Base rack rear Expansion rack 0 Expansion rack 1 Expansion rack 2 Expansion rack 4 CE 6 DE 60 DE 64 DE 68 DE 6C DE 61 DE 69 DE 6D DE 65 DE 62 DE 66 DE 6A DE 6E DE 63 DE 6B DE 6F DE 67 PDU 0 PDU 2 PDU 4 PDU 1 PDU 3 PDU 5 CE 7 DE 70 DE ...

Page 53: ...closures in ascending order starting from the node with the smallest controller enclosure num ber Figure 34 Example of an Installation to 19 inch Racks for GS 1800mm When Connecting Two or Less Drive Enclosures per Node Base rack front Base rack rear Expansion rack 0 FE FE CE 0 DE DE CE 1 DE DE CE 2 DE CE 0 DE DE CE 1 DE CE 2 DE DE PDU 3 PDU 2 PDU 1 PDU 0 CE 3 DE PDU 0 SCCI PPC PPC DE PDU 1 DE DE ...

Page 54: ...ower dis tribution unit horizontal type Power cable length 5U or shorter 1 0m or more 6 16U 1 5m or more 17U or longer 3 0m Figure 35 Distance between Each Enclosure and the Power Distribution Unit Horizontal Type Example Power cord 0 1 2 3 4 5 6 7 8 9 10 11 PDU DE 6U The distance between the enclosure and the power distribution unit in this example is 6U which is calculated by subtracting the PDU...

Page 55: ...istribution unit horizontal type with the ETER NUS DX8700 S3 DX8900 S3 Keep the total current consumption of power cords that connect to outlets OUT1 to OUT8 within 24A for each power distribution unit when connecting Keep the total current consumption of power cords that connect to outlets OUT1 to OUT4 and the total current consumption of power cords that connect to OUT5 to OUT8 within 12A for ea...

Page 56: ... DE 2 CE 1 CE 1 PDU 0 PDU 2 PDU 1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 PDU number PDU outlets number Total current is within 12A Total current is within 12A Connect to the outlets using the connection order which is the same as the installation order in the rack Since the rated current has been exceeded the same connection is not available Connect to the next power distribution unit For the followin...

Page 57: ...the rack When connecting a new enclosure if the total current consumption of each power distribution unit exceeds 24A connect to the next power distribution unit For details on the current consumption of each power cord for each type of enclosure refer to Outlet Socket Specifications page 38 For mainframe connections power distribution units vertical type cannot be installed Power distribution uni...

Page 58: ...at are available for extending the connection are the 3m QSFP copper cable and the 10m or 30m QSFP active optical cable There are no operational issues even if different types of cables exist in the ETERNUS DX Make sure to use the supplied 1 1m QSFP copper cable to connect between the frontend enclosure and the controller enclosure CE 0 Do not use the cables for extending the connection Make sure ...

Page 59: ...ed as standard 1 1m QSFP copper cable 3m management cable The cable used to connect with CE 0 is provided with the base unit Make sure to use the supplied cable to connect between the FE and CE 0 For extensions 3m QSFP copper cable 3m management cable Used for connections between the FE and the CEs that are installed in the same rack when following the standard installation rules Cannot be used fo...

Page 60: ...m 10m Up to eight sets For CE 4 to CE B 1 The required quantity varies depending on the number of CEs that are to be connected Figure 39 Frontend Cable Connection Example When Connecting Two DEs for Each Node in a 19 inch Rack 2000mm Base rack rear Expansion rack 0 Expansion rack 1 FE CE 0 DE DE CE 1 DE DE CE 2 DE CE 3 DE DE DE CE 4 DE DE CE 5 DE DE CE 6 DE CE 7 DE DE DE PDU 4 PDU 5 PDU 3 PDU 2 PD...

Page 61: ...Frontend cables 3m 5m Up to two sets For CE 2 to CE 3 Frontend cables 10m 10m Up to eight sets For CE 4 to CE B 1 The required quantity varies depending on the number of CEs that are to be connected Figure 40 Frontend Cable Connection Example When Connecting Four DEs for Each Node in a 19 inch Rack 2000mm Base rack rear Expansion rack 0 Expansion rack 1 Expansion rack 2 FE CE 0 DE DE DE DE CE 1 DE...

Page 62: ...CE B 1 The required quantity varies depending on the number of CEs that are to be connected Figure 41 Frontend Cable Connection Example When Connecting Six DEs for Each Node in a 19 inch Rack 2000mm Base rack rear Expansion rack 0 Expansion rack 1 Expansion rack 2 FE CE 0 DE DE DE DE CE 1 DE DE DE DE DE DE DE DE DE DE DE DE DE DE CE 3 DE DE DE DE DE DE PDU 4 PDU 5 PDU 3 PDU 2 PDU 1 PDU 0 PDU 3 PDU...

Page 63: ...and later expansion racks or Expansion Rack 3 and later If expansion racks are installed in a pattern that is different from the standard installation rules the cables in the connection examples may not be long enough to connect If expansion racks are installed to the left when facing the rear of the base rack the 3m QSFP copper cable cannot connect between the base rack and the third expansion ra...

Page 64: ... PDU 4 PDU 1 PDU 3 PDU 5 Base rack rear Expansion rack 0 Expansion rack 1 Expansion rack 2 Expansion rack 4 PDU 5 CE 6 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE PDU 0 PDU 2 PDU 4 PDU 1 PDU 3 PDU 5 CE 7 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE PDU 0 PDU 2 PDU 4 PDU 1 PDU 3 CE 8 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE PDU 0 PDU 2 PDU 4 PDU 1 PDU 3 PDU 5 CE 9 DE DE DE DE DE DE DE...

Page 65: ...ith Mainframe Connections Cable length Usage Supplied as standard 1 1m QSFP copper cable 3m management cable The cable used to connect with CE 0 is provided with the base unit Make sure to use the supplied cable to connect between the FE and CE 0 For extensions 3m QSFP copper cable 3m management cable Used for connections between the FE and the CEs that are installed in the same rack when followin...

Page 66: ...andard 1 1m 3m One set supplied as standard For CE 0 Frontend cables 3m 3m Up to two sets For CE 1 to CE 2 Frontend cables 3m 5m Up to one set For CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 43 Frontend Cable Connection Example When Connecting Two DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE C...

Page 67: ... 1 1m 3m One set supplied as standard For CE 0 Frontend cables 3m 3m Up to one set For CE 1 Frontend cables 3m 5m Up to two sets For CE 2 to CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 44 Frontend Cable Connection Example When Connecting Four DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE ...

Page 68: ...as standard For CE 0 Frontend cables 3m 3m Up to one set For CE 1 Frontend cables 3m 5m Up to two sets For CE 2 to CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 45 Frontend Cable Connection Example When Connecting Six DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE DE DE CE 1 DE DE DE CE 2 DE...

Page 69: ... supplied as standard For CE 0 Frontend cables 3m 3m Up to one set For CE 1 Frontend cables 3m 5m Up to two sets For CE 2 to CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 46 Frontend Cable Connection Example When Connecting Eight DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE DE DE CE 1 DE D...

Page 70: ...nd cables 10m 10m Up to one set For CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 47 Frontend Cable Connection Example When Connecting 10 DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE DE DE CE 1 DE DE DE DE CE 2 DE DE DE DE DE DE DE DE PDU 3 PDU 2 PDU 3 PDU 2 PDU 1 PDU 0 PDU 1 PDU 0 DE DE D...

Page 71: ...2 Frontend cables 10m 10m Up to one set For CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 48 Frontend Cable Connection Example When Connecting 12 DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE DE DE CE 1 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE PDU 3 PDU 2 PDU 3 PDU 2 PDU 1 PDU 0 PDU 1 P...

Page 72: ...p to one set For CE 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 49 Frontend Cable Connection Example When Connecting 14 DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE DE DE CE 1 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE PDU 3 PDU 2 PDU 3 PDU 2 PDU 1 PDU 0 PDU 1 PDU 0 DE DE DE DE DE DE DE D...

Page 73: ...E 3 1 The required quantity varies depending on the number of CEs that are to be connected Figure 50 Frontend Cable Connection Example When Connecting 16 DEs for Each Node in a 19 inch Rack for GS 1800mm Base rack rear Expansion rack 0 FE CE 0 DE DE DE DE DE DE CE 1 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE PDU 3 PDU 2 PDU 3 PDU 2 PDU 1 PDU 0 PDU 1 PDU 0 DE DE DE DE DE DE DE DE Expansion rack 1...

Page 74: ...bles with a length of 1 1m 3 5m and 6 0m are Mini SAS HD copper cables and cables with a length of 15m and 30m are Mini SAS HD active optical cables There are no operational issues even if different types of cables exist in the ETERNUS DX Table 32 Backend Cable Connection Usage Cable length Usage 1 1m Provided with drive enclosures 3 5m Used as extension cables when the lengths of the provided cab...

Page 75: ... so the cables that are supplied as standard can be use for connections Figure 51 Backend Cable Connection Example ETERNUS DX8100 S3 Connections in the Same Rack DE DE DE DE PPC SCCI PPC PDU 0 PDU 1 CE Base rack rear Cables that are supplied as standard 1 1m 2 Rack Installation Specifications Rack Installation Requirements 75 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Sys...

Page 76: ... drive enclosures 2U are instal led in a rack Figure 52 Backend Cable Connection Example ETERNUS DX8700 S3 DX8900 S3 Connections in the Same Rack DE DE DE DE DE DE DE DE CE 0 FE Base rack rear Cables that are supplied as standard 1 1m Extension cables 3 5m 2 Rack Installation Specifications Rack Installation Requirements 76 FUJITSU Storage ETERNUS DX8100 S3 DX8700 S3 DX8900 S3 Hybrid Storage Syste...

Page 77: ...xtension cable is necessary for a connection between the drive enclosures installed to the upper part and the controller enclosures Figure 53 Backend Cable Connection Example When Installing 16 DEs for Each Node Connected between Multi ple Racks FE DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE CE 0 DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE DE CE 1 Base rack rear Expansion rack 0 Cables that a...

Page 78: ...nty If the ETERNUS DX needs to be installed in a non Fujitsu rack the following conditions must be satisfied Rack Specifications Use the rack mount kit supplied with the product to install the ETERNUS DX in the rack The rack specifications must satisfy the conditions listed below For rack specifications refer to the manual for the rack that is used Pitch for mounting holes EIA Standard Universal p...

Page 79: ...pace Space between the fixed part of the ETERNUS DX on the front side and the rear of the rack 890mm or more 4 Rack mount kit installation area 482mm or more recommended Placement Requirements When determining service areas refer to the manual of the rack that is to be used Make sure to perform the installation according to the placement requirements described in Installation Specifi cations page ...

Page 80: ... prepared with the utmost attention to detail However Fujitsu shall assume no responsibility for any operational problems as the result of errors omissions or the use of information in this manual Fujitsu assumes no liability for damages to third party copyrights or other rights arising from the use of any information in this manual The content of this manual may not be reproduced or distributed i...

Page 81: ......

Reviews: